ASSISTANCE OU SERVICE ............... COUVERTURE ARRIÈRE
W10773360A
W10773369A-SP
Dryer Safety
2
3
Installation Instructions
Tools and Parts
Tools needed
Gather the required tools and parts before starting installation.
Read and follow the instructions provided with any tools
listed here.
Parts supplied
Remove parts package from the dryer drum. Check that all parts
listed are included.
Flat-blade screwdriver#2 Phillips screwdriver
¼” nut driver or socket
wrench (recommended)
Tape measureVent clamps
Tin snips (new vent
installations)
Cycle control knob
Leveling legs (4)
Start button
Parts needed
Check local codes, existing electrical supply and venting, and
see “Venting Requirements” and “Electrical Requirements” before
purchasing parts.
■ Mobile home installations require metal exhaust
system hardware.
Location Requirements
LevelPliers
Adjustable wrench that
opens to 1” (25 mm) or
hex-head socket wrench
Wire Stripper (direct wire
installations)
4
Caulking gun and
compound (for installing
new exhaust vent)
Wood block
You will need
■ A location that allows for proper exhaust installation. See
“Venting Requirements.”
■ A separate 30-amp circuit.
■ A grounded electrical outlet located within 2 ft (610 mm) of
either side of the dryer. See “Electrical Requirements.”
■ A sturdy floor to support the dryer weight (dryer and load)
of 115 lbs (52 kg). The combined weight of a companion
appliance should also be considered.
■ A level floor with a maximum slope of 1" (25 mm) under
entire dryer.
Do not operate your dryer at temperatures below 45°F (7°C). At
lower temperatures, the dryer might not shut off at the end of an
automatic cycle. Drying times can be extended.
The dryer must not be installed or stored in an area where it will
be exposed to water and/or weather.
Check code requirements. Some codes limit, or do not permit,
installation of the dryer in garages, closets, mobile homes, or
sleeping quarters. Contact your local building inspector.
Installation Clearances
(787 mm)
36"
(25 mm)
(600 mm)
(210 mm)
(83 mm)
(303 mm)
AB
(25 mm)
AB
The location must be large enough to allow the dryer door to
open fully.
Dryer Dimensions
Front View
3
/4"
*20
(527 mm)
31"
Minimum spacing for recessed area and
closet installation
The following dimensions shown are for the minimum spacing
allowed when the dryer is to be operated with, or without, the
Stack Stand Kit. To purchase a Stack Stand Kit, see “Assistance
or Service.”
■ Additional spacing should be considered for ease of
installation and servicing.
■ Additional clearances might be required for wall, door, and
floor moldings.
■ For closet installation with a door, minimum ventilation
openings in the top and bottom of the door are required.
Louvered doors with equivalent ventilation openings
are acceptable.
■ Companion appliance spacing should also be considered.
Recessed or closet installation - Dryer only
14"*
(356 mm)
81/4"
235/8"
1"
1"
(25 mm)
237/8"
(606 mm)
Side View
(914 mm)
(527 mm)
Back View
3
20
/4"
117/8"
1"
(25 mm)
31/4"
18"* (457 mm)
51/2"*
(140 mm)
A. Side view - closet or confined area
B. Recessed area
1"
(25 mm)
1"
*Most installations require a minimum 5½" (140 mm) clearance
behind the dryer for the exhaust vent with elbows. See “Venting
Requirements.”
Recessed or closet installation - Stacked
12"*
12"*
(25 mm)
51/2"
(76 mm)
48 in. *
DRYER
WASHER
1"
1"
(25 mm)
1"*
(25 mm)
(309.7 cm )
24 in. *
(154.8 cm )
2
2
2
2
3"*
(76 mm)
3"*
(76 mm)
C
A. Recessed area
B. Side view - closet or confined area
C. Closet door with vents
Mobile Home - Additional Location Requirements
This dryer is suitable for mobile home installations. The
installation must conform to the Manufactured Home
Construction and Safety Standard, Title 24 CFR, Part 3280
(formerly the Federal Standard for Mobile Home Construction
and Safety, Title 245, HUD Part 280) or Standard CAN/CSAZ240 MH.
Mobile home installations require:
Metal exhaust system hardware, which is available for purchase
from your dealer.
Special provisions must be made in mobile homes to introduce
outside air into the dryer. The opening (such as a nearby window)
should be at least twice as large as the dryer exhaust opening.
5
Electrical Requirements
It is your responsibility
■ To contact a qualified electrical installer.
■ To be sure that the electrical connection is adequate and in
conformance with the National Electrical Code, ANSI/NFPA
70-latest edition and all local codes and ordinances.
The National Electrical Code requires a 4-wire supply
connection for homes built after 1996, dryer circuits involved
in remodeling after 1996, and all mobile home installations.
A copy of the above code standards can be obtained from:
National Fire Protection Association, One Batterymarch Park,
Quincy, MA 02269.
■ To supply the required 3 or 4 wire, single phase, 120/240 volt,
60 Hz., AC only electrical supply (or 3 or 4 wire, 120/208 volt
electrical supply, if specified on the serial/rating plate) on a
separate 30-amp circuit, fused on both sides of the line. A
time-delay fuse or circuit breaker is recommended. Connect
to an individual branch circuit. Do not have a fuse in the
neutral or grounding circuit.
■ Do not use an extension cord.
■ If codes permit and a separate ground wire is used, it is
recommended that a qualified electrician determine that the
ground path is adequate.
Electrical Connection
To properly install your dryer, you must determine the type of
electrical connection you will be using and follow the instructions
provided for it here.
■ If local codes do not permit the connection of a neutral ground
wire to the neutral wire, see “Optional 3-wire connection” in
the “Electrical Connection” section.
■ This dryer is manufactured ready to install with a 3-wire
electrical supply connection. The neutral ground wire is
permanently connected to the neutral conductor (white wire)
within the dryer. If the dryer is installed with a 4-wire electrical
supply connection, the neutral ground wire must be removed
from the external ground conductor screw (green screw), and
secured under the neutral terminal (center or white wire) of the
terminal block. When the neutral ground wire is secured under
the neutral terminal (center or white wire) of the terminal block,
the dryer cabinet is isolated from the neutral conductor.
■ A 4-wire power supply connection must be used when the
appliance is installed in a location where grounding through
the neutral conductor is prohibited. Grounding through the
neutral is prohibited for (1) new branch-circuit installations, (2)
mobile homes, (3) recreational vehicles, and (4) areas where
local codes prohibit grounding through the
neutral conductors.
If using a power supply cord:
Use a UL listed power supply cord kit marked for use with
clothes dryers. The kit should contain:
■ A UL listed 30-amp power supply cord, rated 120/240 volt
minimum. The cord should be type SRD or SRDT and be
at least 4 ft (1.22 m) long. The wires that connect to the
dryer must end in ring terminals or spade terminals with
upturned ends.
■ A UL listed strain relief.
If your outlet looks like this:
4-wire receptacle (14-30R)
Then choose a 4-wire power supply cord with ring or spade
terminals and UL listed strain relief. The 4-wire power supply
cord, at least 4 ft (1.22 m) long, must have four 10-gauge copper
wires and match a 4-wire receptacle of NEMA Type 14-30R. The
ground wire (ground conductor) may be either green or bare. The
neutral conductor must be identified by a white cover.
If your outlet looks like this:
3-wire receptacle (10-30R)
Then choose a 3-wire power supply cord with ring or spade
terminals and UL listed strain relief. The 3-wire power supply
cord, at least 4 ft (1.22 m) long, must have three 10-gauge copper
wires and match a 3-wire receptacle of NEMA Type 10-30R.
If connecting by direct wire:
Power supply cable must match power supply (4-wire or 3-wire)
and be:
■ Flexible armored cable or nonmetallic sheathed copper cable
(with ground wire), protected with flexible metallic conduit. All
current-carrying wires must be insulated.
■ 10-gauge solid copper wire (do not use aluminum).
■ At least 5 ft (1.52 m) long.
6
Electrical Connection
A
B
C
D
A
Power Supply Cord
Direct Wire
1. Disconnect power.
2. Remove the hold-down screw and terminal block cover.
B
C
D
A. Terminal block cover
B. External ground conductor screw
C. Center terminal block screw
D. Hold-down screw location
E. Neutral ground wire
F. Hole below terminal block opening
3. Install strain relief.
Style 1: Power supply cord strain relief
■ Remove the screws from a ¾" (19 mm) UL listed strain relief
(UL marking on strain relief). Put the tabs of the two clamp
sections into the hole below the terminal block opening so
that one tab is pointing up and the other is pointing down, and
hold in place. Tighten strain relief screws just enough to hold
the two clamp sections together.
E
F
A. Strain relief tab pointing up
B. Hole below terminal block opening
C. Clamp section
D. Strain relief tab pointing down
7
■ Put power supply cord through the strain relief. Be sure that
(127 mm)
(89 mm)
A
BF
the wire insulation on the power supply cord is inside the
strain relief. The strain relief should have a tight fit with the
dryer cabinet and be in a horizontal position. Do not further
tighten strain relief screws at this point.
Electrical Connection Options
If your home has:And you will be
connecting to:
4-wire receptacle
(NEMA Type 14-30R)
A UL listed,
120/240-volt
minimum,
30-amp, dryer
power supply
cord*
Go to Section
4-wire connection:
Power supply cord
Style 2: Direct wire strain relief
■ Unscrew the removable conduit connector and any screws
from a ¾" (19 mm) UL listed strain relief (UL marking on strain
relief). Put the threaded section of the strain relief through
the hole below the terminal block opening. Reaching inside
the terminal block opening, screw the removable conduit
connector onto the strain relief threads.
A
B
C
A. Removable conduit connector
B. Hole below terminal block opening
C. Strain relief threads
■ Put direct wire cable through the strain relief. The strain
relief should have a tight fit with the dryer cabinet and be in
a horizontal position. Tighten strain relief screw against the
direct wire cable.
4-wire direct
5"
3-wire receptacle
(NEMA type 10-30R)
A fused
disconnect or
circuit breaker
box*
A UL listed,
120/240-volt
minimum,
4-wire connection:
Direct Wire
3-wire connection:
Power supply cord
30-amp, dryer
power supply
cord*
3-wire direct
3¹₂"
A fused
disconnect or
circuit breaker
box*
3-wire connection:
Direct Wire
*If local codes do not permit the connection of a cabinet-ground
conductor to the neutral wire, go to “Optional 3-wire
connection” section.
4-wire connection: Power Supply Cord
IMPORTANT: A 4-wire connection is required for mobile
homes and where local codes do not permit the use of
3-wire connections.
C
D
A. 4-wire receptacle (NEMA type 14-30R)
B. 4-prong plug
C. Ground prong
D. Neutral prong
E. Spade terminals with upturned ends
F. ¾" (19 mm) UL listed strain relief
G. Ring terminals
1. Remove center terminal block screw.
E
G
4. Now complete installation following instructions for your type
of electrical connection:
4-wire (recommended)
3-wire (if 4-wire is not available)
8
2. Remove neutral ground wire from external ground conductor
D
E
D
F
(127 mm)
E
screw. Connect neutral ground wire and the neutral wire (white
or center wire) of power supply cord under center terminal
block screw. Tighten screw.
A
B
C
4-wire connection: Direct Wire
IMPORTANT: A 4-wire connection is required for mobile
homes and where local codes do not permit the use of 3-wire
connections.
Direct wire cable must have 5 ft (1.52 m) of extra length so dryer
can be moved if needed.
Strip 5" (127 mm) of outer covering from end of cable, leaving
bare ground wire at 5" (127 mm). Cut 1½" (38 mm) from 3
remaining wires. Strip insulation back 1" (25 mm). Shape ends of
wires into a hook shape.
1"
(25 mm)
5"
A. External ground conductor screw - Dotted line
shows position of NEUTRAL ground wire before
being moved to center terminal block screw
B. Center terminal block screw
C. Neutral wire (white or center wire)
D. ¾" (19 mm) UL listed strain relief
E. Neutral ground wire
3. Connect ground wire (green or bare) of power supply cord to
external ground conductor screw. Tighten screw.
A
B
C
E
A. External ground conductor screw
B. Center terminal block screw
C. Neutral wire (white or center wire)
D. ¾" (19 mm) UL listed strain relief
E. Neutral ground wire
F. Ground wire (green or bare) of power supply cord
4. Connect the other wires to outer terminal block screws.
Tighten screws.
5. Tighten strain relief screws.
6. Insert tab of terminal block cover into slot of dryer rear panel.
Secure cover with hold-down screw.
7. You have completed your electrical connections. Now go to
“Venting Requirements.”
When connecting to the terminal block, place the hooked end of
the wire under the screw of the terminal block (hook facing right),
squeeze hooked end together and tighten screw, as shown.
1. Remove center terminal block screw.
2. Remove neutral ground wire from external ground conductor
screw. Connect neutral ground wire and place the hooked end
(hook facing right) of the neutral wire (white or center wire) of
direct wire cable under the center screw of the terminal block.
Squeeze hooked ends together. Tighten screw.
A
B
C
D
A. External ground conductor screw - Dotted line
shows position of NEUTRAL ground wire before
being moved to center terminal block screw
B. Center terminal block screw
C. Neutral wire (white or center wire)
D. ¾" (19 mm) UL listed strain relief
E. Neutral ground wire
9
3. Connect ground wire (green or bare) of power supply cable to
F
G
D
E
(89 mm)
external ground conductor screw. Tighten screw.
A
B
C
E
D
2. Connect neutral wire (white or center wire) of power supply
cord to the center terminal screw of the terminal block.
Tighten screw.
B
C
A
A. External ground conductor screw
B. Center terminal block screw
C. Neutral wire (white or center wire)
D. ¾" (19 mm) UL listed strain relief
E. Neutral ground wire
F. Ground wire (green or bare) of power supply cable
4. Place the hooked ends of the other power supply cable wires
under the outer terminal block screws (hooks facing right).
Squeeze hooked ends together. Tighten screws.
5. Tighten strain relief screws.
6. Insert tab of terminal block cover into slot of dryer rear panel.
Secure cover with hold-down screw.
7. You have completed your electrical connections. Now go to
“Venting Requirements.”
3-wire connection: Power Supply Cord
Use where local codes permit connecting cabinet-ground
conductor to neutral wire:
B
D
A
C
A. 3-wire receptacle (NEMA type 10-30R)
B. 3-wire plug
C. Neutral prong
D. Spade terminals with up turned ends
E. ¾" (19 mm) UL listed strain relief
F. Ring terminals
G. Neutral (white or center wire)
1. Loosen or remove center terminal block screw.
E
F
A. Neutral ground wire
B. External ground conductor screw
C. Center terminal block screw
D. Neutral wire (white or center wire)
E. ¾" (19 mm) UL listed strain relief
3. Connect the other wires to outer terminal block screws.
Tighten screws.
4. Tighten strain relief screws.
5. Insert tab of terminal block cover into slot of dryer rear panel.
Secure cover with hold-down screw.
6. You have completed your electrical connections. Now go to
“Venting Requirements.”
3-wire connection: Direct Wire
Use where local codes permit connecting cabinet-ground
conductor to neutral wire.
Direct wire cable must have 5 ft (1.52 m) of extra length so dryer
can be moved if needed.
Strip 3½" (89 mm) of outer covering from end of cable. Strip
insulation back 1" (25 mm). If using 3-wire cable with ground
wire, cut bare wire even with outer covering. Bend ends of wires
into a hook shape.
1"
(25 mm)
3½"
When connecting to the terminal block, place the hooked end of
the wire under the screw of the terminal block (hook facing right),
squeeze hooked end together and tighten screw, as shown.
10
1. Loosen or remove center terminal block screw.
D
D
E
F
2. Place the hooked end of the neutral wire (white or center wire)
of power supply cable under the center screw of terminal
block (hook facing right). Squeeze hooked end together.
Tighten screw.
B
C
Optional 3-wire connection
Use for direct wire or power supply cord where local codes do
not permit connecting cabinet-ground conductor to neutral wire.
1. Remove center terminal block screw.
2. Remove neutral ground wire from external ground conductor
screw. Connect neutral ground wire and the neutral wire
(white or center wire) of power supply cord/cable under center
terminal block screw. Tighten screw.
B
A
C
A
A. Neutral ground wire
B. External ground conductor screw
C. Center terminal block screw
D. Neutral wire (white or center wire)
E. ¾" (19 mm) UL listed strain relief
E
3. Place the hooked ends of the other power supply cable wires
under the outer terminal block screws (hooks facing right).
Squeeze hooked ends together. Tighten screws.
4. Tighten strain relief screw.
5. Insert tab of terminal block cover into slot of dryer rear panel.
Secure cover with hold-down screw.
6. You have completed your electrical connections. Now go to
“Venting Requirements.”
A. External ground conductor screw
B. Neutral ground wire
C. Center terminal block screw
D. Neutral wire (white or center wire)
E. ¾" (19 mm) UL listed strain relief
F. Grounding path determined by a qualified electrician
3. Connect the other wires to outer terminal block screws.
Tighten screws.
4. Tighten strain relief screws.
5. Insert tab of terminal block cover into slot of dryer rear panel.
Secure cover with hold-down screw.
6. Connect a separate copper ground wire from the external
ground conductor screw to an adequate ground.
11
Venting
Venting Requirements
Exhaust hoods:
■ Must be at least 12" (305 mm) from ground or any object
that may obstruct exhaust (such as flowers, rocks, bushes,
or snow).
Recommended Style:
Louvered hoodBox hood
Acceptable Style:
WARNING: To reduce the risk of fire, this dryer MUST BE
EXHAUSTED OUTDOORS.
IMPORTANT: Observe all governing codes and ordinances.
Dryer exhaust must not be connected into any gas vent,
chimney, wall, ceiling, attic, crawlspace, or a concealed space
of a building. Only rigid or flexible metal vent shall be used for
exhausting.
4" (102 mm) heavy metal exhaust vent
■ Only a 4" (102 mm) heavy metal exhaust vent and clamps
may be used.
■ Do not use plastic or metal foil vent.
Rigid metal vent:
■ Recommended for best drying performance and to avoid
crushing and kinking.
Flexible metal vent: (Acceptable only if accessible to clean)
■ Must be fully extended and supported in final dryer location.
■ Remove excess to avoid sagging and kinking that may result
in reduced airflow and poor performance.
■ Do not install in enclosed walls, ceilings, or floors.
■ The total length should not exceed 7¾ ft. (2.4 m).
NOTE: If using an existing vent system, clean lint from entire
length of the system and make sure exhaust hood is not
plugged with lint. Replace plastic or metal foil vents with rigid
metal or flexible metal vents. Review “Vent System Chart” and,
if necessary, modify existing vent system to achieve best
drying performance.
Angled hood
Elbows
45° elbows provide better airflow than 90° elbows.
Good
Clamps
■ Use clamps to seal all joints.
■ Exhaust vent must not be connected or secured with screws
or other fastening devices that extend into the interior of the
duct, because they can catch lint. Do not use duct tape.
Improper venting can cause moisture and lint to collect
indoors, which may result in:
Moisture damage to woodwork, furniture, paint, wallpaper,
carpets, etc.
Housecleaning problems and health problems.
Better
12
Plan Vent System
C
Choose your exhaust installation type
Recommended exhaust installations:
Typical installations vent the dryer from the rear of the dryer.
Other installations are possible.
A
B
A. Exhaust hood
B. Flexible metal or rigid metal vent
C. Elbow
Alternate installations for close clearances:
Venting systems come in many varieties. Select the type best
for your installation. Two close-clearance installations are shown.
Refer to the manufacturer’s instructions.
A B
A. Over-the-top installation
(also available with one offset elbow)
B. Periscope installation
NOTE: The following kits for close clearance alternate
installations are available for purchase. For information on
ordering, see “Assistance or Service.”
■ Over-the-Top Installation:
Part Number 4396028
■ Periscope Installation (for use with dryer vent to wall
vent mismatch):
Part Number 4396037 - for mismatch of 0" (0 mm) to
18" (457 mm)
Part Number 4396011 - for mismatch of 18" (457 mm) to
29" (737 mm)
Part Number 4396014 - for mismatch of 29" (737 mm) to
50" (1.27 m)
Special provisions for mobile home installations
The exhaust vent must be securely fastened to a noncombustible
portion of the mobile home structure and must not terminate
beneath the mobile home. Terminate the exhaust vent outside.
Determine vent path
■ Select the route that will provide the straightest and most
direct path outdoors.
■ Plan the installation to use the fewest number of elbows
and turns.
■ When using elbows or making turns, allow as much room
as possible.
■ Bend vent gradually to avoid kinking.
■ Use the fewest 90° turns possible.
Determine vent length and elbows needed for
best drying performance
■ Use the “Vent System Chart” below to determine type of vent
material and hood combinations acceptable to use.
NOTE: Do not use vent runs longer than those specified in
the Vent system chart. Exhaust systems longer than those
specified will:
■ Shorten the life of the dryer.
■ Reduce performance, resulting in longer drying times and
increased energy usage.
The “Vent System Chart” provides venting requirements that will
help to achieve the best drying performance.
Vent System Chart
Number of
90° turns or
elbows
0
1
2
Type of ventBox or
louvered
hoods
Rigid metal36 ft (11 m)26 ft (7.9 m)
Rigid metal26 ft (7.9 m)16 ft (4.9 m)
Rigid metal16 ft (4.9 m)6 ft (1.8 m)
Angled
hoods
13
Install Vent System
1. Install exhaust hood.
12" min.
(305 mm)
12" min.
(305 mm)
3. Start to screw legs into holes by hand. Use a wrench to finish
turning legs. They should stick out about 1" (25 mm).
Install exhaust hood and use caulking compound to seal
exterior wall opening around exhaust hood.
2. Connect vent to exhaust hood.
Vent must fit inside exhaust hood. Secure vent to exhaust
hood with 4" (102 mm) clamp. Run vent to dryer location.
Use the straightest path possible. See “Determine vent path”
in “Plan Vent System.” Avoid 90° turns. Use clamps to seal
all joints. Do not use duct tape, screws, or other fastening
devices that extend into the interior of the vent to secure vent,
because they can catch lint.
Install Leveling Legs
4. Place a carton corner post from dryer packaging under each
of the 2 dryer back corners. Stand the dryer up. Slide the
dryer on the corner posts until it is close to its final location.
Leave enough room to connect the exhaust vent.
Connect Vent
1. Connect vent to exhaust outlet.
Using a 4" (102 mm) clamp, connect vent to exhaust outlet
in dryer. If connecting to existing vent, make sure the vent is
clean. Dryer vent must fit over dryer exhaust outlet and inside
exhaust hood. Check that vent is secured to exhaust hood
with a 4" (102 mm) clamp.
2. Move dryer into its final location. Avoid crushing or kinking
the vent.
1. To avoid damaging floor, use a large flat piece of cardboard
from dryer carton. Place cardboard under entire back edge of
the dryer.
2. Firmly grasp dryer body and gently lay dryer on cardboard.
See illustration.
14
3. Once exhaust vent connection is made, remove corner posts
and cardboard.
Level Dryer
1. Check levelness of dryer. Check levelness first side to side,
then front to back.
Not Level LEVEL Not Level
2. Tighten and adjust leveling legs.
If dryer is not level, prop the dryer up using a wood block.
Use a wrench to adjust the legs up or down and check again
for levelness. Once legs are level, make sure all four legs are
snug against the floor before tightening them.
Complete Installation
1. Check that all parts are now installed. If there is an extra part,
go back through the steps to see what was skipped.
2. Check that you have all of your tools.
3. Dispose of/recycle all packaging materials.
4. Check dryer’s final location. Be sure vent is not crushed
or kinked.
5. Check that dryer is on a level surface.
6. For power supply cord installation, plug into an outlet. For
direct wire installation, turn on power.
7. Remove film on the console and any tape remaining on dryer.
Remove tape from lint screen (located on inside back wall
of dryer).
8. Read “Dryer Use.”
9. Wipe dryer drum interior thoroughly with a damp cloth to
remove any dust.
10. To test the dryer, set the dryer on a full heat cycle (not an air
cycle) for 20 minutes and start the dryer.
If the dryer will not start, check the following:
■ Controls are set in a running or “On” position.
■ START button has been firmly pressed.
■ Dryer is plugged into an outlet and/or electrical supply
is on.
■ Household fuse is intact and tight, or circuit breaker has
not tripped.
■ Dryer door is closed.
11. When the dryer has been running for 5 minutes, open the
dryer door and feel for heat. If you feel heat, cancel cycle and
close the door.
If you do not feel heat, check the following:
■ Controls are set on a heated cycle, not an air cycle.
NOTE: You may notice an odor when dryer is first heated. This
odor is common when the heating element is first used. The odor
will go away.
15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.