•CFM information in the above table is with high velocity, permanent filter(s) as shipped with the furnace. If the furnace is shipped with two
side return filters, this table assumes both filters are used.
•All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
•For most jobs, about 400 CFM per ton when cooling is desirable.
•This chart is for furnaces installed at 0 - 4000 feet. At higher altitudes, a properly derated unit will have the same temperature rise at a particular
CFM, while the ESP at that CFM will be lower.
•The shaded area ( )indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation,
external static pressure should not exceed 0.5” W.C. The data for 0.6” W.C. to 0.8” W.C. is shown for air conditioning purposes only.
•The dashed (-----) areas indicate a temperature rise not recommended for this model.
•The installation must be adjusted to obtain a temperature rise within the range listed on the furnace nameplate.
2
Accessibility Clearances (Minimum)
WARNING
To avoid death, personal injury or property
damage due to fire, clearances to combustible surfaces listed as below must be
observed.
36 inches front clearance is required for servicing or cleaning.
NOTE: In all cases, accessibility clearance must take
precedence over clearances from the enclosure where
accessibility clearances are greater.
CLEARANCES TO COMBUSTIBLE SURFACES
GUD_ MODEL FURNACES (Inches)
FRONT3TOP1
RIGHT1FLUE0
LEFT1FLOORC
REAR0--------
C = If placed on combustible floor, floor MUST be wood only.
High Altitude Installations
For installations above 4000 feet, please refer to your
Amana distributor for required kit(s).
GasAl titudeKi tOrifice
Natural 0-4000 Ft.None#433.5" W.C.
Propane 0-4500 Ft. LPTK09#5510.0" W.C.
NOTE: In Canada, gas furnaces are certified to 4,500 feet
only.
IMPORTANT NOTES:
1. All furnaces have a redundant gas valve and blower
door interlock switch.
2. All furnaces are manufactured for use on 115 VAC, 60
Hz, single phase electrical supply.
3. IMPORTANT: While the data is presented as a guide,
it is very important to properly size fuses and wires and
make electrical connections in accordance with the
National Electrical Code and/or all existing local codes.
4. Performance figures are based on Department of Energy information and requirements under continuous
operating conditions. Performance will vary with weather
conditions and use.
Manif old
Pressure
5. Drain connections must conform to local codes.
6. Installer must supply the following gas line fittings
according to which entrance is used:
TopTwo 90° Elbows
One Close Nippl e
Left
Right
One 90° Elbow
One 90° Elbow
One 45° Elbow
One Close Nippl e
Flame Sensor
Flame sensor output is 1 to 4 microamps at 115 volts.
* Quantity - Inches (Total Minimum Surface Area in Square Inches)
Permanent filter sizes are as shipped with furnace. The minimum
permanent filter size area is based on allowable face velocity of 620
feet per minute.
Bottom Return Filter Sizes
Model Filter Size (Inches) Type
4514 x 25 x 1P
7016 x 25 x 1*P
9020 x 25 x 1P
11520 x 25 x 1P
P = Permanent
* As Shipped With Furnace
The figure below shows how the filter is retained over the
bottom return air opening.
Filter Retainer
Filter
Furnace Bottom
Filter Retainer
3
WARNING
To prevent death, personal injury or property damage due to electrical shock, disconnect electrical power to this furnace
before servicing or performing maintenance.
THERMOSTAT
Y
CONNECTIONS
W
R
G
C
TERMINAL ORDER REARRANGED FOR CLARITY
L
E
E
H
H
I
A
A
U
U
N
C
C
M
M
E
H
H
N
H
N
O
O
E
O
E
T
T
U
T
U
120 V
TRANS-
FORMER
24 V
4
PS
CONTROL
X
X
F
F
M
M
R
R
H
N
H
O
E
T
P
L
T
T
U
H
S
I
R
NO
C
NC
5
**
*
C
H
P
H
O
E
A
L
M
M
O
A
R
O
V
V
L
T
K
L
I
M
I
T
GV
CAPACB
C
NO
L1
DOOR
SWITCH
GND
6
C
P
A
R
K
L
I
I
N
R
E
I
N
I
G
N
N
E
E
G
F
N
D
U
U
N
P
D
S
F
E
L
N
A
S
M
O
E
R
CB
N
IGNITOR
WARNING:DISCONNECT POWER BEF ORE
SERVICING.WIRING TO UNIT MUST BE
PROPERLY POLARIZED AND GROUNDED.
SEE
INSTALLATION
INSTRUCTIONS
TO DETERMINE
PROPER
COOLING
BLOWER SPEED.
LOW VOLTAGE FIELD
HI VOLTAGE FIELD
PRESSURE SWITCH (PS)
COM
NC
NO
OR
-16
BU-15
GN
YL
-11
CAPACITOR
(CAP)
WH-33
BU-36
RD-22
WH-
23
IGNITOR
BK-6
BK-3
DOOR SWITCH (CLOSED
WHEN D OOR IN PLACE )
WARNING:DISCONNECT POWER
BEFORE SERVICING.W IRING TO
UNIT MU ST BE PROPERLY
POLARIZED AND GROUNDED.
COLOR CODE
YL YELLOW
OR ORANGE
VT VIOLE T
GN GREE N
BK BLACK
BR BROWN
WH WHITE
BU BLUE
GY GRAY
RD RED
LOW VOLTAGE
HI VOLTAGE
115V FIE LD
CONNECT
ELECTRONIC
AIR CLEANER
VT
-55
RD
-22
5
BK-6
BK-1
**
*
L
T
K
K
E
R
E
R
OR-16
AIR
BR
CIRCULATION
BLOWER
BR
(ACB)
#26 BK (HI)
#23 BU (MED)
#29 OR (MED LOW)
#24 RD (LOW)
WH
BU-25
6
GY-47
THERMOSTAT
CONNECTIONS
WY
BR-21
BK-1
WH-2
LINE
TRANSFORMER
LOAD
115V FIE LD
CONNECT
HUMIDIFIER
BU-25
GY-25
OR-3
IMPORTANT:
READ BEFORE OPERATING OR SERVICING THIS UNIT.
1. SET HEAT ANTICIPAT OR ON ROOM THERMOSTAT AT 0.7 AMPS.
2. AMANA SPECIFIED RE PLACEMENT PARTS MUST BE USED WHEN SERVICING.
3. IF ANY OF THE ORIGIN AL WIRE AS S UP PLIED WITH THE FURNACE MUST BE
REPLACED, IT MUST BE REPLACED WI T H WIRING MAT ERIAL HAVING A TEMPERATURE RATI NG
OF AT LEAST 105C. USE COPPER CONDU CTORS ON LY.
4. UNUSE D BLOWER MOTOR LEADS MUST BE PLACE D ON "PARK" TERMINALS OF CONTROL OR TAPED.
5 IF HEATING AND COOLING BLOWER SPEEDS ARE NOT THE SA ME DISCARD JU M PER BEFORE
CONNECTING BLOWER LEADS.
6 DIAGNOSTIC LIGHT:STEADY=REPLACE CONTR OL;1 FLASH=LOCKOUT;2 FLASHES=PS ST UCK CLOSED;
3 FLASHES=PS STUCK OPEN;4 FLASHE S=OPEN HIGH LIMIT SWI TCH;
5 FLASHES=O PEN ROLLOUT CO NTROL ;
CONTINUOUS FLASHING=FLAME-NO CALL FOR HEAT
CIRCU LATOR BLO WER
COO
HEA
PAR
PAR
LIN
XFM
EAC
HUM
IND
IGN
CIR
LIN
XFM
EAC
HUM
R G C
HOT 120 VAC
NEUTRAL 120VAC
YL-11
CONTROL
MV GND HLI
RO1TR
PSRO2MV
12
11852
GY
GN
-25
RD-44
11165501 REV . 0
TH FP HLO
369
OR-3
BU
-36
14710
VT
-14
RD-44
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.