Amana AVPTC37B14, AVPTC33C14, AVPTC37C14, AVPTC31C14, AVPTC39C14 Installation & Operating Instructions Manual

...
Page 1
AVPTC**14**
AIR HANDLERS INSTALLATION & OPERATING INSTRUCTIONS
Contents
© 2018 Goodman Manufacturing Company, L.P.
5151 San Felipe, Suite 500, Houston, TX 77056
www.goodmanmfg.com - or - www.amana-hac.com P/N: IOA-4030 Date: May 2018
1 Important Safety Instructions ................................... 2
2 Shipping Inspection ................................................... 3
3 Codes & Regulations ................................................. 3
4 Replacement Parts ..................................................... 3
5 Pre-Installation Considerations................................. 3
6 Installation Location................................................... 3
7 Refrigerant Lines........................................................ 5
8 Condensate Drain Lines ............................................ 8
9 Ductwork .................................................................... 9
10 Return Air Filters ........................................................ 9
11 Achieving 1.4% and 2.0% Airflow Low
Leakage Rate .............................................................. 9
12 Electric Heat ............................................................... 9
13 Electrical and Control Wiring .................................. 10
14 AVPTC Motor Orientation .........................................11
15 Cool Cloud HVAC Phone Application ........................11
16 Quick Start Guide for Communicating
Outdoor Units........................................................... 12
17 Quick Start Guide for Non-Communicating
Outdoor Units........................................................... 12
18 Dehumidification ....................................................... 14
19 Auxiliary Alarm Switch ............................................. 14
20 Start-Up Procedure.................................................. 14
21 Accessories .............................................................. 14
22 Ramping Profiles ...................................................... 15
23 Electric Air Cleaner Warning ................................... 15
24 Start-Up Procedure.................................................. 16
25 Regular Maintenance ............................................... 16
26 Air Handler Troubleshooting Matrix ........................ 17
27 Air Handler Display .................................................. 19
28 Airflow Label ............................................................. 22
29 Wiring Diagram ........................................................ 23
O
NLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL, ADJUST, SERVICE OR
REPAIR (HEREINAFTER
SHOULD SERVICE THE EQUIP MENT
FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR
SERVICE PROCED URES
FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT
JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES TO SERVICE THE EQUIPMENT
SPECIFIED IN THIS MANUAL, ONLY LICENSED PERSONNEL SHOULD SERVICE THE
EQUIPMENT
THE EQUIP MENT SPECIFIED IN THIS MANUAL, OR ATT EM PT ING TO INSTALL, ADJUST
SERVICE OR REPAIR THE EQUIP MENT SPECIFIED IN THIS MANUAL WITHOUT PROPER
TRAINING MAY RESULT IN PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH
, “
SERVICE
”)
THE EQUIPM ENT SPECIFIED IN THIS MANUAL
. THE
MANUFACTURER WILL NOT BE RESPONSIBLE
. IF
YOU SERVICE THIS UNIT, YOU ASSUME RESPONSIBILITY
. IN
ADDITION, IN
. I
MPROPER INSTALLATION, ADJUSTME NT, SERVICING OR REPAIR OF
.
,
RECOGNIZE THIS SYMBOL AS A
SAFETY PRECAUTION.
ATTENTION INSTALLING PERSONNEL
Prior to installation, thoroughly familiarize yourself with this Installa­tion Manual. Observe all safety warnings. During installation or repair, caution is to be observed. It is your responsibility to install the product safely and to educate the customer on its safe use.
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
-
Page 2
1 Important Safety Instructions
The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards. It is the owner’s and installer’s responsibility to read and comply with all safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of personal injury, property damage, and/or product damage.
To prevent the risk of property damage, personal injury, or death, do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this unit.
This product is factory-shipped for use with 208/240/1/60 electrical power supply. reconfigure this air handler to operate with any other power supply.
To avoid property damage, personal injury or death due to electrical shock, this unit MUST have an uninterrupted, unbroken
electrical ground. The electrical ground circuit may consist of an appropriately sized electrical wire connecting the ground lug in the unit control box to the building electrical service panel. Other methods of grounding are permitted if performed in accordance with the National Electric Code (NEC)/American National Standards Institute (ANSI)/National Fire Protection Association (NFPA) 70 and local/state codes. In Canada, electrical grounding is to be in accordance with the Canadian Electric Code (CSA) C22.1.
When installing or servicing this equipment, safety clothing, including hand and eye protection, is strongly recommended. If installing in an area that has special safety requirements (hard hats, etc.), bserve these requirements.
DO NOT
o
CO can cause serious illness includ ing permanent brain dama ge or d eath.
Advertencia especial para la instalación de calentadores ó manejadoras de aire en áreas cerradas c omo estacionamientos ó c uartos de servi cio.
Las emisiones de monóxido de carbono pueden circular a través del aparato cuando se opera en cualquier modo.
El monóxido de carbono puede causar enfermedad es severas como daño cerebral perma nente ó muerte.
RISQUE D'EMPOISONNEMENT AU
MONOXYDE DE CARBONE
Do not connect to or use any device that is not design­certified by the manufacturer for use with this unit. Serious property damage, personal injury, reduced unit performance and/or hazardous conditions may result from the use of such non-approved devices.
HIGH VOLTAGE!
Disconnect ALL power before servicing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
Cette ventilation est nécessaire pour éviter le danger d'intoxication au CO pouvant survenir si un appareil produisant du monoxyde de carbone con tinue de fonctionne r au sein de la zone confinée.
2
Page 3
2 Shipping Inspection
Always transport the unit upright; laying the unit on its side or top during transit may cause equipment damage. The installer should inspect the product upon receipt for shipping damage and subse­quent investigation is the responsibility of the carrier. The installer must verify the model number, specifications, electrical charac­teristics, and accessories are correct prior to installation. The dis­tributor or manufacturer will not accept claims from dealers for transportation damage or installation of incorrectly shipped units.
2.1 Parts
Also inspect the unit to verify all required components are present and intact. Report any missing components imme­diately to Goodman or to the distributor. Use only factory authorized replacement parts (see Section 5). Make sure to include the full product model number and serial number when reporting and/or obtaining service parts.
2.2 Handling
Use caution when transporting/carrying the unit. Do not move unit using shipping straps. Do not carry unit with hooks or sharp objects. The preferred method of carrying the unit after ar­rival at the job site is to carry via a two-wheel hand truck from the back or sides or via hand by carrying at the cabinet cor­ners.
3 Codes & Regulations
This product is designed and manufactured to comply with appli­cable national codes. Installation in accordance with such codes and/or prevailing local codes/regulations is the responsibility of the installer. The manufacturer assumes no responsibility for equip­ment installed in violation of any codes or regulations.
The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduction and disposal of refrigerants. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines.
Should you have any questions please contact the local office of the EPA and/or refer to EPA’s website www.epa.gov.
4 Replacement Parts
When reporting shortages or damages, or ordering repair parts, give the complete product model and serial numbers as stamped on the product. Replacement parts for this product are available through your contractor or local distributor. For the location of your nearest distributor consult the white business pages, the yel­low page section of the local telephone book or contact:
HOMEOWNER SUPPORT
GOODMAN MANUFACTURING COMPANY, L.P.
19001 KERMIER ROAD,
WALLER, TX 77484
(877) 254-4729
5 Pre-Installation Considerations
5.1 Preparation
Keep this document with the unit. Carefully read all instruc­tions for the installation prior to installing product. Make sure each step or procedure is understood and any special considerations are taken into account before starting instal­lation. Assemble all tools, hardware and supplies needed to complete the installation. Some items may need to be pur­chased locally. Make sure everything needed to install the product is on hand before starting.
5.2 System Matches
The entire system (combination of indoor and outdoor sec­tions) must be manufacturer approved and Air-Condition­ing, Heating, and Refrigeration Institute (AHRI) listed. NOTE: Installation of unmatched systems is not permitted. Damage or repairs due to installation of unmatched systems is not covered under the warranty.
5.3 Interconnecting Tubing
Give special consideration to minimize the length of refriger­ant tubing when installing air handlers. Refer to Remote Cool­ing/Heat Pump Service Manual RS6200006, and TP-107 Long Line Set Application R-410A for tubing guidelines. If possible, allow adequate length of tubing such that the coil may be removed (for inspection or cleaning services) from the cabi­net without disconnecting the tubing.
5.4 Clearances
The unit clearance from a combustible surface may be 0". However, service clearance must take precedence. A mini­mum of 24" in front of the unit for service clearance is re­quired. Additional clearance on one side or top will be re­quired for electrical wiring connections. Consult all appro­priate regulatory codes prior to determining final clearances. When installing this unit in an area that may become wet (such as crawl spaces), elevate the unit with a sturdy, non­porous material. In installations that may lead to physical damage (i.e. a garage) it is advised to install a protective barrier to prevent such damage. Always install units such that a positive slope in condensate line (1/4" per foot) is allowed.
5.5 Horizontal Applications
If installed above a finished living space, a secondary drain pan (as required by many building codes), must be installed under the entire unit and its condensate drain line must be routed to a location such that the user will see the conden­sate discharge.
6 Installation Location
NOTE: These air handlers are designed for indoor installation
only. The AVPTC**14** product line may be installed in one of the
upflow, downflow, horizontal left or horizontal right orientations as shown in Figures 2, 3, 4 and 5. The unit may be installed in upflow or horizontal left orientation as shipped (refer to specific sections for more information).
3
Page 4
Minor field modifications are necessary to convert to downflow or horizontal right as indicated in below sections.
6.1 Upflow Installation
No field modifications are mandatory; however, to obtain maximum efficiency, the horizontal drip shield, side drain pan and drain pan extension can be removed.
Side Drain Pan and Extension Removal: Refer to Figure 1, re­move the two (2) screws that secure the drip shield support brackets to the condensate collectors (front and back). Un­snap the side drain pan from the main drain pan using a screw driver or any small lever. The side drain pan, drip shield brack­ets and the drain pan extension may now be removed. From Figure 1, drain port labeled (A) is the primary drain for this application and condensate drain line must be attached to this drain port. Drain port (a) is for the secondary drain line (if used).
Drip Pan Extension
Side Drain Pan
Screw
b
B
Drip Shield Bracket
Drip Shield
CMK0008
Condensate
Kit
AVPTC25B14 AVPTC29B14 AVPTC31C14 AVPTC49D14 AVPTC33C14 AVPTC49C14
CMK0009
Condensate
Kit
AVPTC37B14 AVPTC37C14 AVPTC61D14 AVPTC39C14
CMK0010
Condensate
Kit
AVPTC 37D 14
AVPTC59C14
AVPTC 59D 14
CMK0012
Condensate
Kit
CMK0013
Condensa te
Kit
CMK0014
Condensate
Kit
CONDENSATE KIT
TABLE 1
6.3 Downflow/Horizontal Right Installation
IMPORTANT NOTE: In the downflow application, to prevent coil pan “sweating”, a downflow kit (DFK) is available through your local Goodman distributor. The DFK is not supplied with the air handler and is required by Goodman on all downflow installations. See Table 2 for the correct DFK and follow the instructions provided for installation.
MODEL LIST FOR DOWNFLOW KITS
DFK-B
Downflow Kit
DFK-C
Downflow Kit
DFK-D
Downflow Kit
AVPTC25B14** AVPTC31C14** AVPTC37D14**
AVPTC29B14** AVPTC37C14** AVPTC49D14**
AVPTC35B14** AVPTC59C14** AVPTC59D14**
AVPTC37B14** AVPTC33C14** AVPTC61D14**
AVPTC39C14**
AVPTC49C14**
DOWNFLOW KIT
TABLE 2
Pna
A
Main Drain Pan
SIDE DRAIN PAN REMOVAL
Figure 1
6.2 Horizontal Left Installation
No field modifications are permissible for this application.
The bottom right drain connection is the primary drain for this application and condensate drain line must be attached to this drain connection. The top connection of the three drain connections on the drain pan must remain plugged for this application. The bottom left drain connection is for the sec­ondary drain line (if used).
In applications where the air handler is installed in the hori­zontal left position, and the return air environment see hu­midity levels above 65% relative humidity coupled with total external static levels above 0.5” e.s.p., a condensate kit is available for field application. Kit nomenclature can be found in Table 1.
Refer to Figure 6 and 7 for the location of the compo­nents referenced in the following steps.
1. Before inverting the air handler, remove blower access panel and coil access panel. The coil access panel and tubing panel may remain screwed together during this procedure. Remove and retain the seven (7) screws securing the coil access panel to the cabinet and the six (6) screws securing the blower access panel to the cabinet.
2. Slide the coil assembly out using the drain pan to pull the assembly from the cabinet.
NOTE: DO NOT USE MANIFOLDS OR FLOWRATOR TO PULL THE COIL ASSEMBLY OUT. FAILURE TO DO SO MAY RESULT IN BRAZE JOINT DAMAGE AND LEAKS.
3. Removal of the center support is required on units with 21" wide cabinet. Remove and retain the two (2) screws that secure the center support to the cabinet. Remove the center support.
4. Using the drain pan to hold the coil assembly, slide the coil assembly back into the cabinet on the downflow brackets as shown in Figure 8.
5. Re-install the center support (if removed) using the two (2) screws removed in Step 4.
6. Re-install the access panels removed in Step 1 as shown
4
Page 5
in Figure 9.
7. The bottom left drain connection is the primary drain for this application and condensate drain line must be attached to this drain connection. The top connection of the three drain connections on the drain pan must remain plugged for this application. The bottom left drain connection is for the secondary drain line (if used).
HORIZONTAL RIGHT
Figure 5
7 Refrigerant Lines
NOTE: Refrigerant tubing must be routed to allow adequate ac-
cess for servicing and maintenance of the unit.
7.1 Tubing Size
For the correct tubing size, follow the specification for the condenser/heat pump.
7.2 Tubing Preparation
All cut ends are to be round, burr free, and clean. Failure to follow this practice increases the chances for refrigerant leaks. The suction line is spun closed and requires tubing cutters to remove the closed end.
UPFLOW DOWFLOW
Figure 2 Figure 3
NOTE: If removing only the coil access panel from the unit, the filter access panel must be removed first. Failure to do so may result in panel damage.
Do not install the air handler in a location that violates the instructions provided with the condenser. If the unit is located in an unconditioned area with high ambient temperature and/or high humidity, the air handler may be subject to nuisance sweating of the casing. On these installations, a wrap of 2" fiberglass insulation with a vapor barrier is recommended.
NOTE: To prevent possible damage to the tubing joints, do not handle coil assembly with manifold or flowrator tubes. Always use clean gloves when handling coil assemblies.
NOTE: The use of a heat shield is strongly recommended when brazing to avoid burning the serial plate or the finish of the unit. Heat trap or wet rags must be used to protect heat sen­sitive components such as service valves and TXV valves sens­ing bulb.
This product is factory-shipped with R410A and dry nitrogen mixture gas under pressure. Use appropriate service tools and follow these instructions to prevent injury.
A quenching cloth is strongly recommended to prevent scorching or marring of the equipment finish when brazing close to the painted surfaces. Use brazing alloy of 5% minimum silver content.
CAUTION
Applying too much heat to any tube can melt the tube. Torch heat required to braze tubes of various sizes must be proportional to the size of the tube. Service personnel must use the appropriate heat level for the size of the tube being brazed.
HORIZONTAL LEFT
Figure 4
5
Page 6
Upper Tie Plate
Control
Deck
Blower
Access
Panel
Downflow
Bracket
Center
Support
Filter
Bracket
Filter
Access
Panel
INTERNAL PART TERMINOLOGY
Figure 6
Coil Slides on the downflow bracket
Access
Remove side drain pan extension for downflow application
Coil
Panel
Tubing Panel
UV Knockout
EXTERNAL PART TERMINOLOGY
Figure 7
IMPORTANT NOTE:
Ensure coil slides on the rails along the groove provided on the drain pan side walls. Failure to do so will result in improper condensate drainage.
COIL INSTALLATION FOR DOWNFLOW
Figure 8
6
ACCESS PANEL CONFIGURAATION
FOR DOWNFLOW
OR HORIZONTAL RGHT
Figure 9
Page 7
7.3 Tubing Connections for TXV Models
TXV models come with factory installed TXV with the bulb
pre-installed on the vapor tube.
1. Remove refrigerant tubing panel or coil (lower) access panel.
2. Remove access valve fitting cap and depress the valve stem in access fitting to release pressure. No pressure indicates possible leak.
3. Replace the refrigerant tubing panel.
4. Remove the spin closure on both the liquid and suction tubes using a tubing cutter.
5. Insert liquid line set into liquid tube expansion and slide grommet about 18" away from braze joint.
6. Insert suction line set into suction tube expansion and slide insulation and grommet about 18" away from braze joint.
7. Braze joints. Quench all brazed joints with water or a wet rag upon completion of brazing.
NOTE: The sensing bulb must be permanently located. A heat shield, heat trap, or wet rag must be used during brazing to pre­vent damage to the TXV valve.
8. Replace access panels, suction line grommet, insulation and all screws.
SUCTION LINE WITH SPIN CLOSURE
RUBBER GROMMET
Suction Line Grommet
Figure 11
7.4 Thermal Expansion Valve System Adjustment
Run the system at Cooling for 10 minutes until refrigerant pressures stabilize. Use the following guidelines and meth­ods to check unit operation and ensure that the refrigerant charge is within limits. Charge the unit on low stage.
1. Purge gauge lines. Connect service gauge manifold to base-valve service ports.
2. Temporarily install a thermometer on the liquid line at the liquid line service valve and 4-6’’ from the compressor on the suction line. Ensure the thermometer makes adequate contact and is insulated for best possible readings. Use liquid line temperatice to determine subcooling and vapor temperature to determine super­heat.
3. Check subcooling and superheat. Systems with TXV application should have a subcooling of 7 to 9°F and superheat of 7 to 9°F
a. If subcooling and superheat are low, adjust TXV to 7 to 9°F, and then check subcooling.
NOTE: To adjust superheat, turn the valve stem clockwise to in­crease and counter clockwise to decrease.
b. If subcooling is low and superheat is high, add charge to
raise subcooling to 7 to 9°F, and then check superheat.
c. If subcooling and superheat are high, adjust TXV valve to
7 to 9° superheat, then check subcooling.
d. If subcooling is high and superheat is low, adjust TXV valve
to 7 to 9° superheat and remove charge to lower the subcooling to 7 to 9°F.
NOTE: Do NOT adjust the charge based on suction pressure un­less there is a gross undercharge.
4. Disconnect manifold set, and installation is complete
NOTE: Check the Schrader ports for leaks and tighten valve cores if necessary. Install caps finger-tight.
SUBCOOL FORMULA= SAT. LIQUID LINE TEMP - LIQUID LINE TEMP SUPERHEAT FORMULA= SUCT. LINE TEMP - SAT. SUCT. TEMP
SATURATED SUCTION PRESSURE
TEMPERATURE CHART
SUCTION PRESSURE
PSIG R-22 R-410A
50 26 1
52 28 3
54 29 4
56 31 6
58 32 7
60 34 8
62 35 10
64 37 11
66 38 13
68 40 14
70 41 15
72 42 16
74 44 17
76 45 19
78 46 20
80 48 21
85 50 24
90 53 26
95 56 29
100 59 31
110 64 36
120 69 41
130 73 45
140 78 49
150 83 53
160 86 56
7
170 90 60
SATURATED SUCTION
TEMPERATURE ºF
Page 8
SATURATED LIQUID PRESSURE
TEMPERATURE CHART
CAUTION
LIQUID PRESSURE
PSIG R-22 R-410A
200 101 70
210 105 73
220 108 76
225 110 78
235 113 80
245 116 83
255 119 85
265 121 88
275 124 90
285 127 92
295 130 95
305 133 97
325 137 101
355 144 108
375 148 112
405 155 118
415 157 119
425 n/a 121
435 n/a 123
445 n/a 125
475 n/a 130
500 n/a 134
525 n/a 138
550 n/a 142
575 n/a 145
600 n/a 149
625 n/a 152
SATURATED LIQUID
TEMPERATURE ºF
8 Condensate Drain Lines
The coil drain pan has a primary and a secondary drain with 3/4" NPT female connections. The connectors required are 3/4" NPT male, either PVC or metal pipe, and should be hand tightened to a torque of no more than 37 in-lbs. to prevent damage to the drain pan connection. An insertion depth of approximately 3/8” to 1/2” (3-5 turns) should be expected at this torque.
1. Ensure drain pan hole is not obstructed.
2. To prevent potential sweating and dripping on to finished space, it may be necessary to insulate the condensate drain line located inside the building. Use Armaflex® or similar material.
A secondary condensate drain connection has been provided for areas where the building codes require it. Pitch all drain lines a minimum of 1/4" per foot to provide free drainage. Provide re­quired support to the drain line to prevent bowing. If the second­ary drain line is required, run the line separately from the pri­mary drain and end it where condensate discharge can be easily seen.
NOTE: Water coming from secondary line means the coil primary drain is plugged and needs immediate attention.
If secondary drain is not installed, the secondary access must be plugged.
Insulate drain lines located inside the building or above a fin­ished living space to prevent sweating. Install a condensate trap to ensure proper drainage.
NOTE: When units are installed above ceilings, or in other locations where damage from condensate overflow may occur, it is MANDATORY to install a field fabricated auxiliary drain pan under the coil cabinet enclosure.
The installation must include a “P” style trap that is located as close as is practical to the evaporator coil. See Figure 12 for details of a typical condensate line “P” trap.
NOTE: Units operating in high static pressure applications may require a deeper field constructed “P” style trap than is shown in Figure 12 to allow proper drainage and prevent condensate over­flow.
Drain
Connection
Air Handler
POSITIVE LIQUID SEAL REQUIRED
AT T R AP
2" MIN.
3" MIN.
Figure 12
NOTE: Trapped lines are required by many local codes. In the
absence of any prevailing local codes, please refer to the require­ments listed in the Uniform Mechanical Building Code.
A drain trap in a draw-through application prevents air from being drawn back through the drain line during fan operation thus preventing condensate from draining, and if connected to a sewer line to prevent sewer gases from being drawn into the air­stream during blower operation.
Use of a condensate removal pump is permitted when necessary. This condensate pump should have provisions for shutting off the control voltage should a blocked drain occur. A trap must be installed between the unit and the condensate pump.
IMPORTANT NOTE: The evaporator coil is fabricated with oils that may dissolve styrofoam and certain types of plastics. Therefore, a removal pump or float switch must not contain any of these materials. Tip: Priming the “P” trap may avoid improper draining at the ini­tial installation and at the beginning of the cooling season.
8
Page 9
9 Ductwork
This air handler is designed for a complete supply and return ductwork system.
To ensure correct system performance, the ductwork is to be sized to accommodate 350-450 CFM per ton of cooling with the static pressure not to exceed 0.5" in w.c. Refer to ACCA Manual D, Manual S and Manual RS for information on duct sizing and application. Flame retardant ductwork is to be used and sealed to the unit in a manner that will prevent leakage.
NOTE: A downflow application with electric heat must have an L­shaped sheet metal supply duct without any outlets or registers located directly below the heater.
9.1 Return Ductwork
DO NOT LOCATE THE RETURN DUCTWORK IN AN AREA THAT CAN INTRODUCE TOXIC, OR OBJECTIONABLE FUMES/ ODORS INTO THE DUCTWORK. The return ductwork is to be connected to the air handler bottom (upflow configu­ration).
10 Return Air Filters
Each installation must include a return air filter. This filtering may be performed at the air handler using the factory filter rails or externally such as a return air filter grille. When using the factory filter rails, a nominal 16x20x1”, 20x20x1” or 24x20x1” (actual dimension must be less than 23-½”x20”) filter can be in­stalled on a B, C and D cabinet respectively (the cabinet size is the seventh letter of the model number).
11 Achieving 1.4% and 2.0% Airflow Low Leakage Rate
Ensure all the gaskets remain intact on all surfaces as shipped with the unit. These surfaces are areas between the upper tie plate and coil access panel, blower access and coil access panels, and between the coil access and filter access panels. Ensure upon installation, that the plastic breaker cover is sitting flush on the blower access panel and all access panels are flush with each other and the cabinet. With these requirements satisfied, the unit achieves less than 1.4% airflow leakage @ 0.5 inch wc static pressure and less than 2% airflow leakage @1inch wc static pres­sure when tested in accordance with ASHRAE Standard 193.
12 Electric Heat
Do not operate this product without all the ductwork attached.
CFM
800 121923313756 1000 9 1519253044 1200 8 12152125374962 1400 7 11131821324253 1600 6 9 12 15 19 28 37 46 1800 5 8 10 14 16 25 33 41 2000 5 7 9 1215223037
3 5 6 8 10 15 19/20 25
HEAT KIT NOMINAL kW
230/1/60 SUPPLY VOLTAGE - TEMP. RISE °F
Table 2
CFM
800 111822303554 1000 9 1418242842 1200 7 12152024354759 1400 6 10131720304051 1600 6 9 11 15 18 27 35 44 1800 5 8 10 13 16 24 31 39 2000 4 7 9 12 14 21 28 35
3568101519/2025
HEAT KIT NOMINAL kW
220/1/60 SUPPLY VOLTAGE - TEMP. RISE °F
Table 3
CFM
800 1017212833 1000 8 1317222740 1200 7 11141922334556 1400 6 10121619293848 1600 5 8 10 14 17 25 33 42 1800 5 7 9 12 15 22 30 37 2000 4 7 8 11 13 20 27 33
3568101519/2025
HEAT KIT NOMINAL k W
208/1/60 SUPPLY VOLTAGE - TEMP. RISE °F
Table 4
Model
AVPTC25B14 550 650 700 800 850 875 AVPTC29B14 550 650 700 800 875 875 AVPTC35B14 550 650 700 800 875 1050 AVPTC37B14 550 650 700 800 875 1050 AVPTC31C14 600 700 770 880 97 0 1090 1280 AVPTC33C14 600 700 750 850 92 0 95 0 AVPTC37C14 700 770 880 970 1090 1280 AVPTC39C14 700 770 880 970 1090 1280 AVPTC49C14 800 800 950 1 090 1290 1345
AVPTC59C14 800 800 950 1 090 1290 1345 AVPTC37D14 870 970 1060 1120 1220 1250 AVPTC49D14 950 1060 1150 1220 1520 AVPTC59D14 990 1110 1200 1240 1520 1520 AVPTC61D14 1030 1150 1 250 1320 1 650 1690 1750
35681015192025
HEATE R (kW)
MINIMUM CFM REQUIREMENTS FOR HEATER KITS
Table 5
Refer to the installation manual provided with the electric heat kit for the correct installation procedure. All electric heat must be field installed. If installing this option, the ONLY heat kits that are permitted to be used are the HKS series. Refer to the air han­dler unit’s Serial and Rating plate or the HKS specification sheets to determine the heat kits compatible with a given air handler. No other accessory heat kit besides the HKS series may be in­stalled in these air handlers.
The heating mode temperature rise is dependent upon the sys­tem airflow, the supply voltage, and the heat kit size (kW) selected. Use data provided in Tables 3, 4 and 5 to determine the tempera­ture rise (°F).
NOTE: For installations not indicated above the following formula is to be used:
TR = (kW x 3412) x (Voltage Correction) / (1.08 x CFM)
Where: TR = Temperature Rise
kW = Heater Kit Actual kW 3412 = Btu per kW VC* = .96 (230 Supply Volts)
= .92 (220 Supply Volts) = .87 (208 Supply Volts)
1.08 = Constant CFM = Measured Airflow
VC* (Voltage Correction)
9
Page 10
NOTE: The Temperature Rise Tables can also be used to estimate the air handler airflow delivery. When using these tables for this purpose set the room thermostat to maximum heat and allow the system to reach steady state conditions. Insert two thermometers, one in the return air and one in the supply air. The temperature rise is the supply air temperature minus the return air temperature. Using the temperature rise calculated, CFM can be estimated from the TR formula above. See Spec Sheets and/or Service Manual for more information.
13 Electrical and Control Wiring
IMPORTANT: All routing of electrical wiring must be made
through provided electrical knockouts. Do not cut, puncture or alter the cabinet for electrical wiring.
13.1 Building Electrical Service Inspection
This unit is designed for single-phase electrical supply only.
DO NOT OPERATE ON A THREE-PHASE POWER SUPPLY. Mea­sure the power supply to the unit. The supply voltage must be measured and be in agreement with the unit nameplate power requirements and within the range shown.
Wire used must carry the Minimum Circuit Ampacity
(MCA) listed on the unit’s Series and Rating Plate.
Refer to the NEC (USA) or CSA (Canada) for wire sizing. The unit MCA for the air handler and the optional electric heat kit can be found on the unit Series and Rating Plate.
Wire must be sized to allow no more than a 2% voltage
drop from the building breaker/fuse panel to the unit.
Wires with different insulation temperature rating have varying ampacities - be sure to check the temperature rat­ing used.
Refer to the latest edition of the National Electric Code or in Canada the Canadian Electric Code when determining the correct wire size.
13.3 Maximum Overcurrent Protection (MOP)
Every installation must include an NEC (USA) or CEC (Canada) approved overcurrent protection device. Also, check with local or state codes for any special regional re­quirements.
Nominal Input Minimum Voltage Maximum Voltage
208-240 197 253
ELECTRICAL VOLTAGE
Table 6
13.2 Wire Sizing
Wire size is important to the operation of your equipment. Use the following check list when selecting the appropriate wire size for your unit.
FIRE HAZARD! To avoid the risk of property damage, personal injury or fire, use only copper conductors.
HIGH VOLTAGE!
Disconnect ALL power before servicing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
Protection can be in the form of fusing or HACR style circuit breakers. The Series and Rating Plate provides the maxi­mum overcurrent device permissible.
NOTE: Fuses or circuit breakers are to be sized larger than the equipment MCA but not to exceed the MOP.
13.4 Electrical Connections – Supply Voltage
IMPORTANT NOTE: USE COPPER CONDUCTORS ONLY.
Knockouts are provided on the air handler top panel and sides of the cabinet to allow for the entry of the supply voltage conductors, as shown in Figure 13. If the knockouts on the cabinet sides are used for electrical conduit, an adapter ring must be used in order to meet UL1995 safety requirements. An NEC or CEC approved strain relief is to be used at this entry point. Some codes/municipalities re­quire the supply wire to be enclosed in conduit. Consult your local codes.
Top of
Cabinet
HIGH VOLTAGE! To avoid property damage, personal injury or death due to electrical shock, this unit MUST have an uninterrupted, unbroken electrical ground circuit may consist of an appropriately sized electrical wire connecting the ground lug in the unit control box to the building electrical service panel. Other methods of grounding are permitted if performed in accordance with the National Electric Code (NEC)/American National Standards Institute (ANSI)/National Fire Protection Association (NFPA) 70 and local/state codes. In Canada, electrical grounding is to be in accordance with the Canadian Electric Code (CSA) C22.1.
electrical ground. The
Side of
Cabinet
KNOCK-OUT FOR ELECTRICAL CONNECTIONS
Figure 13
10
Page 11
13.4.1 Air Handler Only (Non-Heat Kit Models)
A
A
The building supply connects to the stripped black and red wires contained in the air handler electrical compartment cavity. A ground screw is also contained in this area. Attach the Supply wires to the air handler conductors as shown in the unit wiring diagram using appropriately sized solderless connectors or other NEC or CEC approved means.
13.4.2 Air Handler - Non-Circuit Breaker Heat Kits
A terminal block is provided with the HKS kit to attach the power supply and air handler connections. Follow the HKS Installation Manual and wiring diagram for complete wir­ing details.
13.4.3 Air Handler With Circuit Breaker Heat Kit
The air handler has a plastic cover on the upper access panel that will require either one or both sections to be removed to allow the heat kit circuit breaker(s) to be in­stalled. The circuit breakers have lugs for power supply connection. See the HKS Installation Instructions for fur­ther details.
14 AVPTC Motor Orientation
If the unit is in the upflow position, there is no need to rotate the motor. If the unit is in the downflow position, loosen motor mount and rotate motor as shown in the AVPTC Motor Orientation figure below. Be sure motor is oriented with the female connections on the casing down. If the motor is not oriented with the connections down, water could collect in the motor and may cause premature failure.
15 Cool Cloud HVAC Phone Application
Actual screens may look different based on the mobile device being used.
FRONT VIEW
FEMALE CONNECTIONS
AVPTC Motor Orientation
Figure 14
SIDE VIEW
W
RNING
SOFTW
RE VER.
TOP
Figure 15
This air handler is Bluetooth ready and functions with the Cool Cloud HVAC phone application designed to improve the contractor’s setup / diagnostic experience. Users can see specific model information, review active diagnostic error codes, observe system menu testing of all operational modes (heat / cool / fan) directly from the phone. The phone application is also capable of directly updating the air handler software anytime updates are available. The application will automatically notify the user.
NOTE: The software update may take up to 20 minutes to complete.
11
Page 12
16 Quick Start Guide for Communicating Outdoor Units
EXTREMELY IMPORTANT: For all cooling calls the system only requires a single Y input from the thermostat. For all heating calls (including applications with backup electric heater kits) the system only requires a single W input from the thermostat. Internal algorithms will control all available cooling and heating stages based on these inputs. Any single-stage 24VAC thermostat can be used. For proper operation, the thermostat must be setup to control a single stage AC outdoor unit and to control single stage electric heat operation. The control board does not accommodate an O wire thermostat input (reversing valve signal). If a heat pump is installed, the thermostat should be setup as stated above. Setting the thermostat for the heat pump control or multistage control may result in incorrect performance.
1. Connect all necessary thermostat wires to the thermostat connector on the air handler control as instructed by the applicable wiring diagrams shown in this section.
2. Connect the 1 & 2 wires between the indoor and outdoor unit for communicating operation. Note: Verify two stage outdoor units include a 24VAC transformer (for outdoor control board power). Two stage outdoor units may not behave properly without this 24 VAC transformer.
16.2 Electric Heater Kit Testing
1. Select the electric heat icon after entering the air handler menus in the Cool Cloud HVAC phone application.
2. Select any value less than 50% for low stage operation and any value greater than 50% for high stage operation.
3. Confirm thermostat heating and cooling calls function properly with equipment.
17 Quick Start Guide for Non-Communicating Outdoor
Units
EXTREMELY IMPORTANT: For two stage electric heat kit control the system only needs a single W input. Internal algorithms will control staging automatically based on the single W input. For non-communicating outdoor unit wiring, see instructions below:
1. Use the wiring diagrams on the next page to connect low voltage thermostat wires.
NOTE: When installing the air handler with a non­communicating heat pump, wire directly to the “O” terminal on the non-communicating heat pump. See the following figures.
Figure 16
3. Download the Cool Cloud HVAC phone application for charging and to configure /test system.
NOTE: When new versions of Bluetooth Communication Soft­ware and Air Handler Control Software are available, the phone application notifies the user. Software updates are classified as either optional or mandatory and installed by using the phone application. Ensure all mandatory software updates and install if necessary.
16.1 Charging
1. Two-stage outdoor units using the Cool Cloud HVAC application:
a. Using the cooling icon after entering the outdoor
unit menus, energize the outdoor unit at 100% capacity.
b. Charge the outdoor unit as required using the
charging information provided with the outdoor equipment.
Figure 17
FIgure 18
12
Page 13
Figure 19
4. Go to the Tonnage Units Menu () and select the
tonnage value that corresponds to the desired airflow for the outdoor unit. See the following table.
NOTE: For the two stage non-communicating outdoor units, system will stage airflow automatically for low stage operation.
NOTE: The system will not provide airflows above the max Airflow Value.
Figure 20
2. Download the Cool Cloud HVAC phone application.
Note: When new versions of Bluetooth Communication Software and Air Handler Control Software are available, the phone application notifies the user. Software updates are classified as either optional or mandatory and installed by using the phone application. Ensure all mandatory software updates have been installed. Review notes for optional software updates and install if necessary.
3. Go to the Non-Comm Outdoor Setting Menu () using the on board push buttons or the Cool Cloud HVAC phone application. Selec t “” for single stage Air Conditioners, “” for single stage Heat Pumps, “” for two stage Air Conditioners and “” for 2 stage Heat Pumps.
Model MAX CFM
AVPTC25B14 AVPTC29B14 AVPTC35B14 AVPTC37B14
AVPTC33C14 1300
AVPTC31C14 AVPTC37C14 AVPTC39C14
AVPTC37D14 AVPTC49C14
AVPTC49D14 AVPTC59C14
AVPTC59D14 AVPTC61D14
1200
1600
1800
1900
2100
5. Use the Cool Cloud HVAC phone application to configure/
test air handler operations.
NOTE: The phone application cannot test a non- communicating outdoor unit. The thermostat will be required for outdoor unit testing.
17.1 Electric Heater Kit Testing
1. Two-stage outdoor units:
a. Provide a second stage cooling call from the
thermostat and charge accordingly.
2. Single-stage outdoor units:
a. Provide a cooling call from the thermostat and
charge accordingly.
13
Page 14
17.2 Electric Heater Kit Testing
1. Select the electric heat icon after entering the air handler menus while using the Cool Cloud phone application.
2. Select any value less than 50% for low stage operation and any value greater than 50% for high stage operation.
3. Confirm thermostat heating and cooling calls function properly for high stage operation.
18 Dehumidification
Dehumidification allows the air handler’s circulator blower to operate at a reduced speed during a combined thermostat call for cooling and a dehumidification call from the thermostat or humidistat. This lower blower speed increases dehumidification of the conditioned air as it passes through the indoor coil. The control board is equipped with a 24 volt dehumidification input (DH) located on the thermostat wiring connector. The terminal can be configured to enable dehumidification when the input is energized or de-energized. When using an external dehumidistat, connect it between the R and DH terminals. If the humidistat closes on humidity rise or the thermostat energizes this terminal when dehumidifcation is required, set the control board Dehum Logic Menu () to “” using the push buttons or Cool Cloud HVAC phone application. If the humidistat opens on humidity or the thermostat de-energizes this terminal when dehumidification is required, set the Dehum Logic Menu to “” using the push buttons or Cool Cloud HVAC phone application.
19 Auxiliary Alarm Switch
The control is equipped with a 24VAC Aux Alarm to be used for a condensate switch install (designated by CON-DENSATE
IN/OUT on the control). By default, the connected AUX switch is normally closed and opens when the water level in the evaporator coil base pan reaches an undesirable level. The control responds by displaying a “”
error code and turning off the outdoor condensing unit. If the AUX switch is detected to be in the closed position for 30 seconds, normal operation resumes and the error message is no longer displayed.
enter into a main menu and to then permanently select options within those menus. NOTE: After scrolling to the desired option within a menu, that option may be flashing on the 7-segment displays. This indicates the option has not been officially selected. Pressing the Center button two times will select that option. The first press will stop the flashing. The second will make the selection official and return you to the main
menu.
21 Accessory Control (Humidifiers, Dehumidifiers,
Ventilators)
If an external humidifier, dehumidifier or ventilator is installed, it may require airflow from the HVAC system to function properly.
1. Make sure the installed 24VAC thermostat is capable of controlling the accessory or accessories.
2. Connect the appropriate accessory control wires to the accessory devices from the thermostat (see thermostat manual for connection and setup instructions).
3. If the thermostat is capable of providing a continuous fan call (G signal) during accessory operation: Make sure to connect the thermostat G terminal to the G terminal on the indoor unit. Setup thermostat to ensure G signal is energized during accessory operation.
20 Start-Up Procedure
Figure 21
The air handler includes three on-board push buttons allowing users to navigate indoor and outdoor system menus. The Right and Left buttons allow the user to scroll through the main menus and to then scroll through available options within specific menus. The Center button is used to
FIgure 22
4. Select the appropriate fan only airflow for the accessory using the indoor unit push button menus or the Cool
Cloud HVAC phone application.
5. Using the thermostat, independently test each accessory in addition to the independently testing continuous fan mode.
14
Page 15
22 Ramping Profiles
The variable-speed circulator offers four different ramping profiles. These profiles may be used to enhance cooling
performance and increase comfort level. Select the desired ramping profile using the Cool Cloud phone application or the push button menus.
23 Electric Air Cleaner Warning
The control is equipped with an Accessory Relay and a pair of ¼ inch accessory terminals which is normally open, labeled EAC-IN and EAC-OUT (see accessory contacts graphic). The Accessory
Relay is configured to close anytime the blower is running. A closed relay means the two terminals will have continuity be­tween them (the control does not energize these contacts). It is recommended to utilize 24VAC with these terminals and limit the current to 1A.
Figure 23
FIgure 24
15
Page 16
24 Start-Up Procedure
Prior to start-up, ensure that all electrical connections are properly sized and tightened.
All panels must be in place and secured. For Air Tight application, neoprene gasket must be positioned at prescribed locations to achieve low airflow as stated in section 13.
Tubing must be leak free.
Unit should be elevated, trapped and pitched to allow for drainage.
Low voltage wiring is connected.
Auxiliary drain is installed when necessary and pitched to allow for drainage.
Drain pan and drain tubing has been leak checked.
Return and supply ducts are sealed.
Unit is elevated when installed in a garage or where flammable vapors may be present.
Unit is protected from vehicular or other physical damage.
Return air is not obtained from any areas where there may be objectionable odors, flammable vapors or products of combustion such as carbon monoxide (CO), which may cause serious personal injury or death.
25 Regular Maintenance
HIGH VOLTAGE!
Disconnect ALL power before servicing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
The only item to be maintained on a regular basis by the user is the circulating air filter(s). Filter should be cleaned or replaced regularly. A certified service technician must perform all other services.
NOTE: THESE INSTRUCTIONS ARE SPECIFICALLY FOR AVPTC MODELS. DO NOT USE THESE DIAGRAMS FOR ANY OTHER MODELS. SEE SEPARATE INSTALLATION AND OPERATING INSTRUCTIONS FOR ATUF, ARUF, ARPT, ADPF, AND ASPF MODELS.
NOTICE: THIS PRODUCT CONTAINS ELECTRONIC COMPO­NENTS WHICH REQUIRE A DEFINITE GROUND. PROVISIONS ARE MADE FOR CONNECTION OF THE GROUND. A DEDICATED GROUND FROM THE MAIN POWER SUPPLY OR AN EARTH GROUND MUST BE PROVIDED.
16
Page 17
26 Air Handler Troubleshooting Matrix
Symptoms of Abnormal Operation
Diagnostic /
Status LED
Codes
Fault Description Possible Causes Corrective Actions
Imp rop er low voltage wiring
No outd oor u ni t operati ons 
No Ai r Hand ler operation  Open fu se Shor t in low voltage wi ri ng
No Ai r Hand ler operation 
No Ai r Hand ler operation  Data not yet on network No network data
No Ai r Hand ler operation  Invalid memory card data
Operation dif feren t than exp ected or n o oper ation
No Ai r Hand ler operation 
 Invalid memory card data
Communication error with outdoor u ni t
Auxilary switch (condensate switch) open
Cir cu lator bl ower motor not running with demand present
between the in door and outd oor u ni t
Outdoor control board lost power duirng operation
High water level in the evaporation coil
Air Handler blower does not contain an ap pr opriate shared data set
Shared d ata set on memory card has been rejected by integrated control module
Loos e or di sconnected wirin g connection at circulator motor power leads
Open ci rcui t in i nductor or loose wir in g con nection at indu ctor (3/4 Hp and 1 Hp models only)
Failed circu lator bl ower motor
Locate an d correct i mpr oper l ow vol tag e wiri ng iss ue
Identi fy reason outdoor control board los t power during operation
Locate and correct sh ort in l ow voltage wiri ng
Replace fuse with 3-amp automotive type
Check evap orator drai n pan , trap, p ip in g
Populate shared data set using memory card
Populate correct shared data using memory card
Verif y shared data set is correct for th e specifc model. Re-populate data using correct memory card if required
Ti ghten or correct wiring connection
Verify continuous circuit through inductor.
Repl ace i f open or sh ort ci rcuit
Check ci rculator b lower motor
No Ai r Hand ler operation 
No Ai r Hand ler operation 
Ai r Handler oper ates at r edu ced performance
Ai rf ow del iv ered is l ess than expected

Integrated control modul e has lost communications with ci rcu lator b lower motor
Cir cu lator bl ower motor horse power in shared data set does not match circulator blower motor horse power
Cir cu lator bl ower motor is oper atin g in a power, temp eratu re, or sp eed l im iti ng condition
Loos e wiring con necti on at circulator motor control leads
Failed circu lator bl ower motor
Failed integrated control module
Incorrect circulator blower motor in Air Handler
Incorrect sh ared data set in integrated control module
Blocked flters
Restrictive or undersized ductwork
Hi gh amb ien t tem peratu res
Ti ghten or correct wiring connection
Check ci rculator b lower motor, repl ace i f necessary
Check integ rated control module, replace i f necessary
Verif y circ ul ator b lower if motor horse p ower is th e same specifed for the specifc Air Handler model, replace if necessary
Verif y shared data set is correct for th e specifc model, re-populate data using correct memory card if required
Check f il ters for bl ockage, cl ean flters or remove obstruction
Check ductwork for blockage, remove obstruction and verify all registers are fully open
Verify ductwork is appropriately sized for system and resize/replace ass needed
17
Page 18
26 Air Handler Troubleshooting Matrix (continued)
Symptoms of Abnormal Operation
Diagnostic /
Status LED
Codes
Fault Description Possible Causes Corrective Actions
No Ai r Hand ler operation 
No Ai r Hand ler operation 
No Ai r Hand ler operation 
No Ai r Hand ler operation 
Cir cu lator bl ower motor senses a loss of rotor control
Cir cu lator bl ower motor senses high current
Cir cu lator bl ower motor fails to start 10 consecutive times
Cir cu lator bl ower motor sh uts down for over or under voltage condition
Cir cu lator bl ower motor sh uts down du e to over temperature condition on power module
Cir cu lator bl ower motor does not have en oug h i nformati on to operate pr oper ly
Motor fail s to start 40 con secu ti ve ti mes
Abnormal motor loading, sudden change in speed or torque, sudden blockage of air handler air inlet or outlet
Obstruction in circulator blower housing
Sei zed Circ ul ator b lower motor bearings
Failed circu lator bl ower motor
High or low AC line voltage to air handler
Hi gh amb ien t tem peratu res
Error with integrated control module shared d ata
Check filters, filter grills/registers, duct system an d ai r h and ler in let/outlet f or blockages
Check ci rculator b lower for obstructions
Remove and repair/replace wheel/motor if necessary
Check ci rculator b lower motor s haf t rotation and motor, replace motor if necessary
Check power to air handler
Verif y l in e voltage i s wi thi n the ran ge specified on the rating plate
Verify control is populated with the correct sh ared data
Ai r Handler oper ates at r edu ced per for mance or op erates on low stage when hi gh stage is exp ected

Airflow is lower than demanded
Blocked filters or restrictive ductwork
Undersized ductwork
Check f il ters for bl ockage, cl ean fil ters or remove obstruction
Check ductwork for blockage, remove obstruction and verify all registers are fully open
Verify ductwork is appropriately sized for system, resize/replace ductwork if necessary
18
Page 19
27 Air Handler Display
LED Display Menu Description


 
View 6 most rec ent fault codes and Clear Fault Codes if desired (furnace)
Restart communications between the indoor and outdoor unit.
Control Firmware Revision Number
Control Shared Data Revision Number

   





   


  







Constant Fan Speed as percent of maximum airflow. Default = 30%
Electric Heater Kit Wattage (kW )
Electric Heat Off Delay (seconds)
Electric Heat On Delay (seconds)
Electric Heat Airflow Trim (percentage)
Percentage of high stage electric heating airflow to run duirng low stage electric heat operation 1 = system will try to satisfy the thermostat quickly. 5 (default) = system will try to satsify the thermostat more slowly. Select "" to enable dehumidification when the thermostat DH terminal is energized. Select "" to enable dehumidification when the thermostat DH terminal is de-energized. (default = ) Select number of stages for the non-communicating outdoor unit. ( for single-stage Air Conditioners,  for single stage Heat Pumps,  for two stage Air Conditioners or  for two stage heat pumps) Indoor Airflow for non-communicating outdoor units. (values based on 400CFM per ton) (default = 3.0 Ton)
Cooling Airflow Trim (default 0%)
Cooling Airflow Profile setting (default = profile D shown as 4)
Cooling Airflow On Delay Time (default = 5 seconds)
Cooling Airflow Off Delay Time. (default = 60 seconds)
Percentage of high stage cooling airflow to run during low stage operation. (default = 70%) Electric heat operation during defrost. 1 = low stage 2 (default) = high stage
Heat Pump Indoor Airflow Trim (default = 0%)
Heat Pump Heating Airflow Off Delay Time (default = 60 seconds)
Heat Pump Heating Airflow On Delay Time (default = 5 seconds)
Percentage of high stage heat pump heating airflow to run during low stage operation. (defaullt = 70%) When heat pump heating and electric heat are running at the same time, this percentage is used for additional airflow trim Enables or disables dehumidification feature in the outdoor unit. (default = Enabled) Balance point temperature. The Compressor will not operate below temperature. (Default = 0°F)
Backup Heat Balance Points
Compressor run time between defrost cycles. (default = 30 minutes) (2 stage units) Compressor off delay at the beginning and end of a defrost cycle. (default = 30 seconds)
19
Page 20
27 Air Handler Display (continued)
LED Display Menu Description






View 6 most recent fault codes and Clear Fault Codes if desired (outdoor communicating units) Menu is enabled if the the system will attempt to satisfy the thermostat. Menu is enabled if the past the target time when the system will enable electric heat operation during heat mode. Menu is enabled if the the next heat call if the heat pump fails to satisfy the custom target time for this number of consecutive cycles) (default = 20 cycles) Menu is enabled if the stage electric heat is able to consecutively satisfy the thermostat under the set target time for this number of cycles, the system will transition to the heat pump for primary heating) Menu is enabled if the help determine when switching back to heat pump only operation is appropriate. Default = 20%. If target time = 20 minutes, the addtion of low stage electric heat must staisfy the thermostat by less than 16 minutes. (target time - 20% default = 16 minutes).
menu is set to 6. Select the target time

menu is set to 6. Select the percentage

is set to 6. (Electric heat will run during

menu is set to 6. (if the additi on of low

menu is set to 6. (this percentage will

20
Page 21
27 Air Handler Display (continued)
LED Display Description of System Status
 

   

   

     
Idle
Constant Fan
Compressor Cooling, Single-Stage (non-comm units)
Compressor Cooling, Low Stage (non-comm units)
Compressor Cooling, High Stage (non-comm units)
Compressor Cooling, Low Stage (comm units)
Compressor Cooling, High Stage (comm units)
Compressor Heat, Single-Stage (non-comm. units)
Compressor Heat, Low Stage (non-comm units)
Compressor Heat, High Stage (non-comm units)
Compressor Heat, Low Stage (Comm Units)
Compressor Heat, High Stage (Comm Units)
Electric Heat, Single Stage
Electric Heat, Low Stage
Electric Heat, High Stage
Defrost, Single Stage Electric Heat
Defrost, Low Stage Electric Heat
Defrost, High Stage Electric Heat
Dehumidification
21
Page 22
28 Air Handler Label
Menu Navigation and Selection Instructions
Using Phone Application over Bluetooth Network:
1) Connect to the air handler (instructions provided by phone during connection process).
2)
Select desired settings menu
3) Select item that requires adjustment and m
4) Submit Changes
Using On-Board Push Buttons:
1) Use the Right and Left Buttons to scroll between menus
2) Use the Center Button to select desired menu when menu code is
shown on 7-segment displays
3) Use the Left and Right Buttons to scroll through options within the desired menu (the display will flash while scrolling through options for
selection)
4)
Use the Center Button to select the displayed option (when selected
the display will stop flashing
5) Use the Center Button to finalize selection and return to the main menu
Profiles
1 -------- -------- 60 sec/100% 2 -------- 30 sec/50% 60 sec/100% 3 -------- 7.5 min/82% 60 sec/100% 4 30 sec/50% 7.5 min/82% 60 sec/100%
Airflow Settings Instructions
1) For non-communicating installations, select the type of unit installed in the
1HP 2HP
2) Use the Tonnage Menu ( (non-communicating installation). Tonnage selection options and correspo [Airflow = Tonnage Selection x 400] Default selection is 6.0 tons.
3)
[Optional] Use the Cooling Trim Menu (
4) [Optional] Use the Heating Trim Menu(HtF) to adjust the heat pump
5) [Optional] percentage of maximum airflow for continuous fan
6) [Optional] Use the Cooling Airflow Profile Menu ( between 5 cooling airflow profiles. Profile options 1-4 are listed above (option 5 is adjustable). See installation manual for further details
Htr Kw
3 5 6
8 10 15 19 20 21 25
Selecting Heater Kit: Use the Electric Heating Wattage Menu ( above. Default selection is 0 (No Heat Kit). Select installed heater kit for heater kit operation.
NR - Not Rated ++ For match up with a 3 ton outdoor unit: Airflow for 5kW up to 15kW heater kits shall be set to 1220 CFM by selecting 10 in the Electric Heating Wattage ( +++ For match up with a 3.5 ton outdoor unit: Heater kit application shall not exceed 20 kW. Airflow for 5kW up to 20kW heater kits shall be set to 1320 CFM by selecting 10 in theElectric Heating Wattage (
menu (
0d5
= single-stage heat pump,
= 2 stage heat pump) Default =
nding airflow CFM can be found to the right.
airflow
from -10% to +10% (2% increments). stage communicating outdoor units and single or 2 stage non-communicating ou outdoor units require an equipment relay board to function with this system). For inverter Intermediate and L adjustment.
airflow
from -10% to +10% (2% increments). stage communicating outdoor units and single or 2 stage non-communicating ou units require an equipment r available). For inver Intermediate and L adjustment.
Use the Constant Fan Menu (
AVPTC25B14 AVPTC29B14
550 650 700 800 850 875
NR NR NR NR
ake necessary selection
)
Pre-Run Short-Run OFF Delay
= single-stage air conditioner,
1AC
ow menus(
ow menus (
2AC
= 2 stage air conditioner,
OFF
(no outdoor unit).
ton
) to select Cooling/Heat Pump Airflow
CtF
) to adjust the cooling
This applies for 2
tdoor units (2 stage
outdoor units use Cooling Trim
CtH,Ct
tdoor units (all non-communicating outdoor
elay board for the trim option to be
ter outdoor units use Heating Trim Factor High,
HtH,Ht1
non-communicating
1
, and CtL) for trim
This applies for 2
,and
HtL
) for trim
F5d
) to select the
CAP
Factor High,
) to select
Electric Heat Airflow Table
550 650 700 800 875 875
NR NR NR NR
AVPTC29B14
AVPTC29B14
EHt
) menu.
AVPTC31C14 AVPTC31C14
550 650 700 800 875
1050
NR NR NR NR
600 700 770 880
970 1090 1280
NR NR NR
Tonnage Menu (t o n)
Tonnage
Selection
1.0 400
1.1 440
1.2 480
1.3 520
1.4 560
1.5 600
1.6 640
1.7 680
1.8 720
1.9 760
2.0 800
2.1 840
2.2 880
2.3 920
2.4 960
2.5 1000
2.6 1040
2.7 1080
2.8 1120
2.9 1160
3.0 1200
3.1 1240
3.2 1280
3.3 1320
3.4 1360
3.5 1400
Airflow
Tonnage
Selection
3.5 1400
3.6 1440
3.7 1480
3.8 1520
3.9 1560
4.0 1600
4.1 1640
4.2 1680
4.3 1720
4.4 1760
4.5 1800
4.6 1840
4.7 1880
4.8 1920
4.9 1960
5.0 2000
5.1 2040
5.2 2080
5.3 2120
5.4 2160
5.5 2200
5.6 2240
5.7 2280
5.8 2320
5.9 2360
6.0 2400
Maximum Airflow Output
AVPTC2 5B14 AVPTC2 9B14 AVPTC3 5B14 AVPTC3 7B14
*If
airflow is set above the model's maximum value, the output will be the
maximum value
AVPTC37C14
AVPTC39C14
600 700 750 850 920 950
NR NR NR NR
EHt
NR 700 770 880 970
1090 1280
NR
NR
NR
) to select heater kit size. See "Menu Navigation and Selection Instructions"
AVPTC3 3C14
12001300 1600 1800 1900 2100
AVPTC49C14
AVPTC59C14
NR 800 800
950 1090 1290 1345
NR NR NR
EHt
) menu.
AVPTC3 1C14 AVPTC3 7C14 AVPTC3 9C14
AVPTC37D14
NR 870 970
1060 1120 1220
NR
1250
NR
NR
AVPTC3 7D14 AVPTC4 9C14
AVPTC49D14
++
NR NR
950 1060 1150 1220 1520
NR NR NR NR
AVPTC4 9D14 AVPTC5 9C14
AVPTC59D14
990 1110 1200 1240 1520
NR
1520
NR NR
22
Airflow
AVPTC5 9D14 AVPTC6 1D14
AVPTC61D14
++
NR 1030 1150 1250 1320 1650
NR 1690
NR 1750
0140A00615-A
Page 23
A
A
29 Wiring Diagrams
HIGH VOLTAGE!
WARNING
(SEE NOTE 4) GROUND LUG
8456321
7
9
RD
BK
INSTALLING
WH
AUX ALARM
BR
(ALARM) (SEE NOTE 7)
BL
HEATE R KIT
OUTPUT
AUX
~
~
OUT
AUX IN
~
~
RELAY OUT
RELAY OUT
(EAC-OUT)
RELAY IN
RELAY IN
(EAC-IN)
NOTES:
1. PLACE RED WIRES ON 208 V TERMINAL OF 2 TRANSFORMERS (TR1/TR2) FOR 208 VAC OPERATION.
2. MAN UFACTURER’S SPEC IFIED REPLA CEMENT PARTS MUST BE US ED
WHEN SERVIC ING.
3. IF ANY OF THE ORI GINAL WIRES AS SUPPL IED WITH THIS UNIT MU ST BE REPLAC ED, IT MUST BE R EPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105°C. USE COPPER CONDUCTORS ONLY.
4. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C AND LOCAL CODES.
6. DISCARD CONNECTOR Pl1 WHEN INSTALLING OPTIONAL HEAT KIT.
7. REM OVE JUMPER TAB AND PUT AUX ALARM SWITCH W HEN
INSTALLING AUX ALARM SWITCH.
9. USE N.E.C CLASS
2 WIRE.
10. SEE M ANUAL FOR PUSH BU TTON OPERATION.
11. SEE MANUAL FOR 7-SEGMENT DIS PLAY DIAGNOSTIC C ODES AND
MENU CODES .
12. SEE MANUAL FOR LED FUNCTIONALITY.
13. R AND C TERMINALS (USED FOR 24VAC OUTDOOR CONTROL
VOLTAGE) ARE OPTIONAL FOR 2 STAGE COMMUNICATING AIR CONDITIONERS. R AND C TERMINALS ARE NOT TO BE USED FOR 2 STAGE COMMUNICATING HEAT PUMP APPLICATIONS.
FOR COMMUN ICATING HEAT PUMPS OR IF ONLY TWO THERMOSTAT WIRES ARE AVAILABLE, A SEPARATE TRANSF ORMER MUST BE INSTALLED IN TH E OUTDOOR UNIT FOR CONTRO L BOARD POWER.
1 AND 2 WIR ES ARE REQUIR ED FOR ALL APPLICATIONS. SEE INSTALLATION MANU AL FOR FULL SYST EM WIRING EXAM PLES.
208/230 VAC
TO
L2
BL
3
24
1
L1
RD BK
PL1
PL2
208
230
VAC
VAC
TR1
24VAC
(SEE NOTE 1)
RD
598710 11 12
6
AUX AL ARM
AUX AL ARM (ALARM)
R
AUX
AUX
OUT
IN
EAC-OUT
TB6
COM
EAC-IN
Tb7
TB5
Th2
TR
Tb3
TB4
F2U
K1R
K2R
GND
NC
J4
(SEE NOTE 11)
J6
EEV COIL
THERMISTOR
(HEAT EXCHANGER 1,2)
INTEGRAT ION TYPE
HEATER KIT
BK
RD
~
~
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
(SEE N OTE 6)
BK
BK
RD
J19
TH1Tr1
B1
SEG3
SEG2
SEG1
J7
TS
F1U
PS
PS
TC
PU YL
TB2
S
208 VAC
24VAC
(SEE NOTE 10)
Pb3
PB2
PB1
J20
DATA AC
TEMPERATURE)
VAC
TR2
(SEE
DH/Y2
FLASH WRITER
(RETURN AIR
RD
30
NOTE 1)
PL3
PL4
RD
THERMOSTAT
WH GR BL
PUGY
YGWCRC
LEGACY INPUT
J11
U A R T 5
I
J13
J12
S
D
H
A
A
T
R
A
E
J8
RAT
BK
J14
J15
J T A G
OUTDOOR UNIT
SEE NOTE 13)
GY BK
BL RD
RD
R21
CT COMM
J3
R
M
A
O
M
N I
T O R
J5
MPU
LED
(SEE NOTE 12)
U10
J18
J9
SAT
PRESSURE
(SUPPLY AIR
SENSOR
TEM PERAT URE)
INTEGRATED CONTROL:
LOW VOLTAGE
LOW VOLTAGE FIELD
HIGH VOLTAGE
HIGH VOLTAGE FIELD
JUNCT ION
TERMINAL
INTERNAL TO
RESISTOR
OVERCURRENT
PROT. DEVICE
PLUG CONNECTION
EQUIPM ENT GND
FIELD GROUND
DISCONNECT ALL POWER BEFORE SERVICING.
L1
GRND
ECM MOTOR
DISCONNECT
FAN
MOTOR
INDOOR
IR
CIRCULATOR
BLWR
208/23 0 VAC
24 VAC
HEAT 1 COIL/R 1
HEAT 2 COIL/ R2
CONDENSATE AUX SWITCH
POWER/HEATER CONNECTOR
TL
THERMAL LIMIT
TRANSFORMER
FUSE LINK
TRANSFORMER
CONNECTOR
J2J1
D
A
A
C
T A
RD
INDO OR U NIT PCB
BK
BL
GY
L1
FUSE 3 A
R
2 4 V
W
T h e r
m o
Y
s t
a t C
o n n e c t
i
o n s
DH/Y2
TO
MICRO
C
TH2
W1 (1)
W2 (2)
CAS (1)
CAS (2)
+VDC (1)
RX (2)
TX (3)
GRND (4)
TR2
COM
INTEGRATED CONTROL MODULE
COLOR CODES:
BL - BLUE
- RED
RD
YL - YELLOW
OR - ORANGE
BK - BL ACK
COMPONENT CODES:
PL1, PL2
TR
F1U, F2U
PL3, P L4
GY - GREY
BR - BROWN
GR - GREEN
PU - PURPLE
WH - WHITE
L2
GRND
40 VA TRANSFORMER
INDOOR
IR
CIRCULATOR
BLWR
GRND
0140 A00613- A
L2
23
Page 24
29 Wiring Diagrams
3-Phase Heat Kit
WARNING
HIGH VOLTAGE!
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
DISCONNECT ALL POWER BEFORE SERVICING.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
24
Page 25
AIR HANDLER
AIR HANDLER HOMEOWNER’S ROUTINE MAINTENANCE RECOMMENDATIONS
We strongly recommend a bi-annual maintenance checkup be performed before the heating and cooling seasons begin by a qualified servicer.
REPLACE OR CLEAN FILTER
IMPORTANT NOTE: Never operate unit without a filter installed as dust and lint will build up on internal parts resulting in loss of
efficiency, equipment damage and possible fire. An indoor air filter must be used with your comfort system. A properly maintained filter will keep the indoor coil of your comfort
system clean. A dirty coil could cause poor operation and/or severe equipment damage. Your air filter or filters could be located in your furnace, in a blower unit, or in “filter grilles” in your ceiling or walls. The installer of your
air conditioner or heat pump can tell you where your filter(s) are, and how to clean or replace them. Check your filter(s) at least once a month. When they are dirty, replace or clean as required. Disposable type filters should be replaced.
Reusable type filters may be cleaned. You may want to ask your dealer about high efficiency filters. High efficiency filters are available in both electronic and non-electronic
types. These filters can do a better job of catching small airborne particles.
MOTORS
Indoor and outdoor fan motors are permanently lubricated and do not require additional oiling.
ALUMINUM INDOOR COIL CLEANING (QUALIFIED SERVICER ONLY)
This unit is equipped with an aluminum tube evaporator coil. The safest way to clean the evaporator coil is to simply flush the coil with water. This cleaning practice remains as the recommended cleaning method for both copper tube and aluminum tube residential evaporator coils.
It has been determined that many coil cleaners and drain pan tablets contain corrosive chemicals that can be harmful to aluminum tube and fin evaporator coils. Even a one-time application of these corrosive chemicals can cause premature aluminum evaporator coil failure. Any cleaners that contain corrosive chemicals including, but not limited to, chlorine and hydroxides, should not be used.
An alternate cleaning method is to use one of the products listed in TP-109* to clean the coils. The cleaners listed are the only agents deemed safe and approved for use to clean round tube aluminum coils. TP-109 is also available on the web site in Partner Link > Service Toolkit.
NOTE: Ensure coils are rinsed well after use of any chemical cleaners.
BEFORE YOU CALL YOUR SERVICER
Check the thermostat to confirm that it is properly set.
Wait 15 minutes. Some devices in the outdoor unit or in programmable thermostats will prevent compressor op­eration for awhile, and then reset automatically. Also, some power companies will install devices which shut off air con­ditioners for several minutes on hot days. If you wait sev­eral minutes, the unit may begin operation on its own.
Check the electrical panel for tripped circuit breakers or failed fuses. Reset the circuit breakers or replace fuses as necessary.
Check the disconnect switch near the indoor furnace or blower to confirm that it is closed.
Check for obstructions on the outdoor unit . Confirm that it has not been covered on the sides or the top. Remove any obstruc­tion that can be safely removed. If the unit is covered with dirt or debris, call a qualified servicer to clean it.
Check for blockage of the indoor air inlets and outlets. Confirm that they are open and have not been blocked by objects (rugs, curtains or furniture).
Check the filter. If it is dirty, clean or replace it.
Listen for any unusual noise(s), other than normal operating noise, that might be coming from the outdoor unit. If you hear unusual noise(s) coming from the unit, call a qualified servicer.
25
Page 26
THIS PAGE WAS LEFT BLANK INTENTIONALLY
26
Page 27
THIS PAGE WAS LEFT BLANK INTENTIONALLY
27
Page 28
CUSTOMER FEEDBACK
We are very interested in all product comments. Please fill out the feedback form on one of the following links:
Goodman® Brand Products: (http://www.goodmanmfg.com/about/contact-us). Amana® Brand Products: (http://www.amana-hac.com/about-us/contact-us). You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page.
PRODUCT REGISTRATION
Thank you for your recent purchase. Though not required to get the protection of the standard warranty, registering your product is a relatively short process, and entitles you to additional warranty protection, except that failure by California and Quebec residents to register their product does not diminish their warranty
rights.
For Product Registration, please register as follows: Goodman® Brand products: (https://www.goodmanmfg.com/product-registration). Amana® Brand products: (http://www.amana-hac.com/product-registration) You can also scan the QR code on the right for the product brand you purchased to be directed to the Product Registration page.
GOODMAN® BRAND
GOODMAN® BRAND
AMANA® BRAND
AMANA® BRAND
© 2018 Goodman Manufacturing Company, L.P.
5151 San Felipe, Suite 500, Houston, TX 77056
www.goodmanmfg.com - or - www.amana-hac.com
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
28
Loading...