Amana AVPTC31C14, AVPTC25B14, AVPTC49C14, AVPTC37B14, AVPTC37C14 Installation & Operating Instructions Manual

...
Page 1
AVPTC**14**
AIR HANDLERS INSTALLATION & OPERATING INSTRUCTIONS
Contents
1 Important Safety Instructions ............................................... 2
2 Shipping Inspection .............................................................. 3
3 Codes & Regulations ............................................................. 3
4 Replacement Parts ............................................................... 3
5 Pre-Installation Considerations ............................................. 3
6 Installation Location ............................................................. 3
7 Refrigerant Lines .................................................................. 5
8 Condensate Drain Lines......................................................... 8
9 Ductwork ............................................................................. 9
10 Return Air Filters .................................................................. 9
11 Electric Heat ......................................................................... 9
12 Electrical and Control Wiring ............................................... 10
13 Achieving 1.4% and
2.0% Airflow Low Leakage Rate ........................................ 11
14 24 Volt Wiring .................................................................... 11
15 Auxiliary Alarm Switch ........................................................ 12
16 AVPTC Motor Orientation................................................... 12
17 Circulator Blower ............................................................... 13
18 Heat Kit Selection ............................................................... 16
19 Troubleshooting ................................................................. 16
20 ComfortNet™ System ........................................................ 17
21 Start-Up Procedure ............................................................ 19
23 Communications Troubleshooting Chart ............................. 20
24 Air Handler Advanced Features Menu ................................ 21
25 Troubleshooting ................................................................. 22
26 Diagnostic Codes ................................................................ 26
27 Wiring Diagrams ................................................................. 27
© 2016-2017 Goodman Manufacturing Company, L.P.
5151 San Felipe, Suite 500, Houston, TX 77056
www.goodmanmfg.com - or - www.amana-hac.com P/N: IOA-4021D Date: December 2017
O
NLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL, ADJUST, SERVICE OR
REPAIR (HEREINAFTER
SHOULD SERVICE THE EQUIP MENT
FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR
SERVICE PROCED URES
FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT
JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES TO SERVICE THE EQUIPMENT
SPECIFIED IN THIS MANUAL, ONLY LICENSED PERSONNEL SHOULD SERVICE THE
EQUIPMENT
THE EQUIP MENT SPECIFIED IN THIS MANUAL, OR ATT EM PT ING TO INSTALL, ADJUST
SERVICE OR REPAIR THE EQUIP MENT SPECIFIED IN THIS MANUAL WITHOUT PROPER
TRAINING MAY RESULT IN PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH
, “
SERVICE
”)
THE EQUIPM ENT SPECIFIED IN THIS MANUAL
. THE
MANUFACTURER WILL NOT BE RESPONSIBLE
. IF
YOU SERVICE THIS UNIT, YOU ASSUME RESPONSIBILITY
. IN
ADDITION, IN
. I
MPROPER INSTALLATION, ADJUSTME NT, SERVICING OR REPAIR OF
.
,
RECOGNIZE THIS SYMBOL AS A
SAFETY PRECAUTION.
ATTENTION INSTALLING PERSONNEL
Prior to installation, thoroughly familiarize yourself with this Installa­tion Manual. Observe all safety warnings. During installation or repair, caution is to be observed. It is your responsibility to install the product safely and to educate the customer on its safe use.
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
Page 2
1 Important Safety Instructions
The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards. It is the owner’s and installer’s responsibility to read and comply with all safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of personal injury, property damage, and/or product damage.
To prevent the risk of property damage, personal injury, or death, do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this unit.
This product is factory-shipped for use with 208/240/1/60 electrical power supply. reconfigure this air handler to operate with any other power supply.
To avoid property damage, personal injury or death due to electrical shock, this unit MUST have an uninterrupted, unbroken
electrical ground. The electrical ground circuit may consist of an appropriately sized electrical wire connecting the ground lug in the unit control box to the building electrical service panel. Other methods of grounding are permitted if performed in accordance with the National Electric Code (NEC)/American National Standards Institute (ANSI)/National Fire Protection Association (NFPA) 70 and local/state codes. In Canada, electrical grounding is to be in accordance with the Canadian Electric Code (CSA) C22.1.
When installing or servicing this equipment, safety clothing, including hand and eye protection, is strongly recommended. If installing in an area that has special safety requirements (hard hats, etc.), bserve these requirements.
DO NOT
o
CO can cause serious illness including permanent brain dama ge or d eath.
Advertencia especial para la instalación de calentadores ó manejadoras de aire en áreas cerradas c omo estacionamientos ó c uartos de servi cio.
Las emisiones de monóxido de carbono pueden circular a través del aparato cuando se opera en cualquier modo.
El monóxido de carbono puede causar enfermedades severas como daño cerebral perma nente ó muerte.
RISQUE D'EMPOISONNEMENT AU
MONOXYDE DE CARBONE
Do not connect to or use any device that is not design­certified by the manufacturer for use with this unit. Serious property damage, personal injury, reduced unit performance and/or hazardous conditions may result from the use of such non-approved devices.
HIGH VOLTAGE!
Disconnect ALL power before servicing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
Cette ventilation est nécessaire pour éviter le danger d'intoxication au CO pouvant survenir si un appareil produisant du monoxyde de carbone con tinue de fonctionne r au sein de la zone confinée.
2
Page 3
2 Shipping Inspection
Always transport the unit upright; laying the unit on its side or top during transit may cause equipment damage. The installer should inspect the product upon receipt for shipping damage and subse­quent investigation is the responsibility of the carrier. The installer must verify the model number, specifications, electrical charac­teristics, and accessories are correct prior to installation. The dis­tributor or manufacturer will not accept claims from dealers for transportation damage or installation of incorrectly shipped units.
2.1 Parts
Also inspect the unit to verify all required components are present and intact. Report any missing components imme­diately to Goodman or to the distributor. Use only factory authorized replacement parts (see Section 5). Make sure to include the full product model number and serial number when reporting and/or obtaining service parts.
2.2 Handling
Use caution when transporting/carrying the unit. Do not move unit using shipping straps. Do not carry unit with hooks or sharp objects. The preferred method of carrying the unit after ar­rival at the job site is to carry via a two-wheel hand truck from the back or sides or via hand by carrying at the cabinet cor­ners.
3 Codes & Regulations
This product is designed and manufactured to comply with appli­cable national codes. Installation in accordance with such codes and/or prevailing local codes/regulations is the responsibility of the installer. The manufacturer assumes no responsibility for equip­ment installed in violation of any codes or regulations.
The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduction and disposal of refrigerants. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines.
Should you have any questions please contact the local office of the EPA and/or refer to EPA’s website www.epa.gov.
4 Replacement Parts
When reporting shortages or damages, or ordering repair parts, give the complete product model and serial numbers as stamped on the product. Replacement parts for this product are available through your contractor or local distributor. For the location of your nearest distributor consult the white business pages, the yel­low page section of the local telephone book or contact:
HOMEOWNER SUPPORT
GOODMAN MANUFACTURING COMPANY, L.P.
19001 KERMIER ROAD,
WALLER, TX 77484
(877) 254-4729
5 Pre-Installation Considerations
5.1 Preparation
Keep this document with the unit. Carefully read all instruc­tions for the installation prior to installing product. Make sure each step or procedure is understood and any special considerations are taken into account before starting instal­lation. Assemble all tools, hardware and supplies needed to complete the installation. Some items may need to be pur­chased locally. Make sure everything needed to install the product is on hand before starting.
5.2 System Matches
The entire system (combination of indoor and outdoor sec­tions) must be manufacturer approved and Air-Condition­ing, Heating, and Refrigeration Institute (AHRI) listed. NOTE: Installation of unmatched systems is not permitted. Damage or repairs due to installation of unmatched systems is not covered under the warranty.
5.3 Interconnecting Tubing
Give special consideration to minimize the length of refriger­ant tubing when installing air handlers. Refer to Remote Cool­ing/Heat Pump Service Manual RS6200006, and TP-107 Long Line Set Application R-410A for tubing guidelines. If possible, allow adequate length of tubing such that the coil may be removed (for inspection or cleaning services) from the cabi­net without disconnecting the tubing.
5.4 Clearances
The unit clearance from a combustible surface may be 0". However, service clearance must take precedence. A mini­mum of 24" in front of the unit for service clearance is re­quired. Additional clearance on one side or top will be re­quired for electrical wiring connections. Consult all appro­priate regulatory codes prior to determining final clearances. When installing this unit in an area that may become wet (such as crawl spaces), elevate the unit with a sturdy, non­porous material. In installations that may lead to physical damage (i.e. a garage) it is advised to install a protective barrier to prevent such damage. Always install units such that a positive slope in condensate line (1/4" per foot) is allowed.
5.5 Horizontal Applications
If installed above a finished living space, a secondary drain pan (as required by many building codes), must be installed under the entire unit and its condensate drain line must be routed to a location such that the user will see the conden­sate discharge.
6 Installation Location
NOTE: These air handlers are designed for indoor installation
only. The AVPTC**14** product line may be installed in one of the
upflow, downflow, horizontal left or horizontal right orientations as shown in Figures 2, 3, 4 and 5. The unit may be installed in upflow or horizontal left orientation as shipped (refer to specific sections for more information).
3
Page 4
Minor field modifications are necessary to convert to downflow or horizontal right as indicated in below sections.
6.1 Upflow Installation
No field modifications are mandatory; however, to obtain maximum efficiency, the horizontal drip shield, side drain pan and drain pan extension can be removed.
Side Drain Pan and Extension Removal: Refer to Figure 1, re­move the two (2) screws that secure the drip shield support brackets to the condensate collectors (front and back). Un­snap the side drain pan from the main drain pan using a screw driver or any small lever. The side drain pan, drip shield brack­ets and the drain pan extension may now be removed. From Figure 1, drain port labeled (A) is the primary drain for this application and condensate drain line must be attached to this drain port. Drain port (a) is for the secondary drain line (if used).
Drip Pan Extension
Side Drain Pan
Screw
b
B
Drip Shield Bracket
Drip Shield
CMK0008
Condensate
Kit
AVPTC25B14 AVPTC29B14 AVPTC31C14 AVPTC49D14 AVPTC33C14 AVPTC49C14
CMK0009
Condensate
Kit
AVPTC37B14 AVPTC37C14 AVPTC61D14 AVPTC39C14
CMK0010
Condensate
Kit
AVPTC 37D 14
AVPTC59C14
AVPTC 59D 14
CMK0012
Condensate
Kit
CMK0013
Condensa te
Kit
CMK0014
Condensate
Kit
CONDENSATE KIT
TABLE 1
6.3 Downflow/Horizontal Right Installation
IMPORTANT NOTE: In the downflow application, to prevent coil pan “sweating”, a downflow kit (DFK) is available through your local Goodman distributor. The DFK is not supplied with the air handler and is required by Goodman on all downflow installations. See Table 2 for the correct DFK and follow the instructions provided for installation.
MODEL LIST FOR DOWNFLOW KITS
DFK-B
Downflow Kit
DFK-C
Downflow Kit
DFK-D
Downflow Kit
AVPTC25B14** AVPTC31C14** AVPTC37D14**
AVPTC29B14** AVPTC37C14** AVPTC49D14**
AVPTC35B14** AVPTC59C14** AVPTC59D14**
AVPTC37B14** AVPTC33C14** AVPTC61D14**
AVPTC39C14**
AVPTC49C14**
DOWNFLOW KIT
TABLE 2
Pna
A
Main Drain Pan
SIDE DRAIN PAN REMOVAL
Figure 1
6.2 Horizontal Left Installation
No field modifications are permissible for this application.
The bottom right drain connection is the primary drain for this application and condensate drain line must be attached to this drain connection. The top connection of the three drain connections on the drain pan must remain plugged for this application. The bottom left drain connection is for the sec­ondary drain line (if used).
In applications where the air handler is installed in the hori­zontal left position, and the return air environment see hu­midity levels above 65% relative humidity coupled with total external static levels above 0.5” e.s.p., a condensate kit is available for field application. Kit nomenclature can be found in Table 1.
Refer to Figure 6 and 7 for the location of the components referenced in the following steps.
1. Before inverting the air handler, remove blower access panel and coil access panel. The coil access panel and tubing panel may remain screwed together during this procedure. Re­move and retain the seven (7) screws securing the coil ac­cess panel to the cabinet and the six (6) screws securing the blower access panel to the cabinet.
2. Slide the coil assembly out using the drain pan to pull the assembly from the cabinet.
NOTE: DO NOT USE MANIFOLDS OR FLOWRATOR TO PULL THE COIL ASSEMBLY OUT. FAILURE TO DO SO MAY RESULT IN BRAZE JOINT DAMAGE AND LEAKS.
3. Removal of the center support is required on units with 21" wide cabinet. Remove and retain the two (2) screws that secure the center support to the cabinet. Remove the cen­ter support.
4. Using the drain pan to hold the coil assembly, slide the coil assembly back into the cabinet on the downflow brackets as shown in Figure 8.
5. Re-install the center support (if removed) using the two (2) screws removed in Step 4.
6. Re-install the access panels removed in Step 1 as shown in Figure 9.
4
Page 5
7. The bottom left drain connection is the primary drain for this application and condensate drain line must be attached to this drain connection. The top connection of the three drain connections on the drain pan must remain plugged for this application. The bottom left drain connection is for the secondary drain line (if used).
HORIZONTAL RIGHT
Figure 5
7 Refrigerant Lines
NOTE: Refrigerant tubing must be routed to allow adequate ac-
cess for servicing and maintenance of the unit.
7.1 Tubing Size
For the correct tubing size, follow the specification for the condenser/heat pump.
7.2 Tubing Preparation
All cut ends are to be round, burr free, and clean. Failure to follow this practice increases the chances for refrigerant leaks. The suction line is spun closed and requires tubing cutters to remove the closed end.
UPFLOW DOWFLOW
Figure 2 Figure 3
NOTE: If removing only the coil access panel from the unit, the filter access panel must be removed first. Failure to do so may result in panel damage.
Do not install the air handler in a location that violates the instructions provided with the condenser. If the unit is located in an unconditioned area with high ambient temperature and/or high humidity, the air handler may be subject to nuisance sweating of the casing. On these installations, a wrap of 2" fiberglass insulation with a vapor barrier is recommended.
NOTE: To prevent possible damage to the tubing joints, do not handle coil assembly with manifold or flowrator tubes. Always use clean gloves when handling coil assemblies.
NOTE: The use of a heat shield is strongly recommended when brazing to avoid burning the serial plate or the finish of the unit. Heat trap or wet rags must be used to protect heat sen­sitive components such as service valves and TXV valves sens­ing bulb.
This product is factory-shipped with R410A and dry nitrogen mixture gas under pressure. Use appropriate service tools and follow these instructions to prevent injury.
A quenching cloth is strongly recommended to prevent scorching or marring of the equipment finish when brazing close to the painted surfaces. Use brazing alloy of 5% minimum silver content.
CAUTION
Applying too much heat to any tube can melt the tube. Torch heat required to braze tubes of various sizes must be proportional to the size of the tube. Service personnel must use the appropriate heat level for the size of the tube being brazed.
HORIZONTAL LEFT
Figure 4
5
Page 6
Upper Tie Plate
Control
Deck
Blower
Access
Panel
Downflow
Bracket
Center
Support
Filter
Bracket
Filter
Access
Panel
INTERNAL PART TERMINOLOGY
Figure 6
Coil Slides on the downflow bracket
Access
Remove side drain pan extension for downflow application
Coil
Panel
Tubing Panel
UV Knockout
EXTERNAL PART TERMINOLOGY
Figure 7
IMPORTANT NOTE:
Ensure coil slides on the rails along the groove provided on the drain pan side walls. Failure to do so will result in improper condensate drainage.
COIL INSTALLATION FOR DOWNFLOW
Figure 8
ACCESS PANEL CONFIGURAATION
FOR DOWNFLOW
OR HORIZONTAL RGHT
Figure 9
6
Page 7
7.3 Tubing Connections for TXV Models
TXV models come with factory installed TXV with the bulb
pre-installed on the vapor tube.
1. Remove refrigerant tubing panel or coil (lower) access panel.
2. Remove access valve fitting cap and depress the valve stem in access fitting to release pressure. No pressure indicates possible leak.
3. Replace the refrigerant tubing panel.
4. Remove the spin closure on both the liquid and suction tubes using a tubing cutter.
5. Insert liquid line set into liquid tube expansion and slide grom­met about 18" away from braze joint.
6. Insert suction line set into suction tube expansion and slide insulation and grommet about 18" away from braze joint.
7. Braze joints. Quench all brazed joints with water or a wet rag upon completion of brazing.
NOTE: The sensing bulb must be permanently located. A heat shield, heat trap, or wet rag must be used during brazing to pre­vent damage to the TXV valve.
a. If subcooling and superheat are low, adjust TXV to 7 to 9°F, and then check subcooling.
NOTE: To adjust superheat, turn the valve stem clockwise to in­crease and counter clockwise to decrease.
b. If subcooling is low and superheat is high, add charge to
raise subcooling to 7 to 9°F, and then check superheat.
c. If subcooling and superheat are high, adjust TXV valve to
7 to 9° superheat, then check subcooling.
d. If subcooling is high and superheat is low, adjust TXV valve
to 7 to 9° superheat and remove charge to lower the subcooling to 7 to 9°F.
NOTE: Do NOT adjust the charge based on suction pressure un­less there is a gross undercharge.
4. Disconnect manifold set, and installation is complete
NOTE: Check the Schrader ports for leaks and tighten valve cores if necessary. Install caps finger-tight.
SUBCOOL FORMULA= SAT. LIQUID LINE TEMP - LIQUID LINE TEMP SUPERHEAT FORMULA= SUCT. LINE TEMP - SAT. SUCT. TEMP
SATURATED SUCTION PRESSURE
TEMPERATURE CHART
8. Replace access panels, suction line grommet, insulation and all screws.
SUCTION LINE WITH SPIN CLOSURE
RUBBER GROMMET
Suction Line Grommet
Figure 11
7.4 Thermal Expansion Valve System Adjustment
Run the system at Cooling for 10 minutes until refrigerant pressures stabilize. Use the following guidelines and meth­ods to check unit operation and ensure that the refrigerant charge is within limits. Charge the unit on low stage.
1. Purge gauge lines. Connect service gauge manifold to base­valve service ports.
2. Temporarily install a thermometer on the liquid line at the liquid line service valve and 4-6’’ from the compressor on the suction line. Ensure the thermometer makes adequate contact and is insulated for best possible readings. Use liq­uid line temperatice to determine subcooling and vapor tem­perature to determine superheat.
3. Check subcooling and superheat. Systems with TXV applica­tion should have a subcooling of 7 to 9°F and superheat of 7 to 9°F
SUCTION PRESSURE
PSIG R-22 R-410A
50 26 1
52 28 3
54 29 4
56 31 6
58 32 7
60 34 8
62 35 10
64 37 11
66 38 13
68 40 14
70 41 15
72 42 16
74 44 17
76 45 19
78 46 20
80 48 21
85 50 24
90 53 26
95 56 29
100 59 31
110 64 36
120 69 41
130 73 45
140 78 49
150 83 53
160 86 56
170 90 60
SATURATED SUCTION
TEMPERATURE ºF
7
Page 8
SATURATED LIQUID PRESSURE
TEMPERATURE CHART
CAUTION
LIQUID PRESSURE
PSIG R-22 R-410A
200 101 70
210 105 73
220 108 76
225 110 78
235 113 80
245 116 83
255 119 85
265 121 88
275 124 90
285 127 92
295 130 95
305 133 97
325 137 101
355 144 108
375 148 112
405 155 118
415 157 119
425 n/a 121
435 n/a 123
445 n/a 125
475 n/a 130
500 n/a 134
525 n/a 138
550 n/a 142
575 n/a 145
600 n/a 149
625 n/a 152
SATURATED LIQUID
TEMPERATURE ºF
8 Condensate Drain Lines
The coil drain pan has a primary and a secondary drain with 3/4" NPT female connections. The connectors required are 3/4" NPT male, either PVC or metal pipe, and should be hand tightened to a torque of no more than 37 in-lbs. to prevent damage to the drain pan connection. An insertion depth of approximately 3/8” to 1/2” (3-5 turns) should be expected at this torque.
1. Ensure drain pan hole is not obstructed.
2. To prevent potential sweating and dripping on to finished space, it may be necessary to insulate the condensate drain line located inside the building. Use Armaflex® or similar material.
A secondary condensate drain connection has been provided for areas where the building codes require it. Pitch all drain lines a minimum of 1/4" per foot to provide free drainage. Provide re­quired support to the drain line to prevent bowing. If the second­ary drain line is required, run the line separately from the pri­mary drain and end it where condensate discharge can be easily seen.
NOTE: Water coming from secondary line means the coil primary drain is plugged and needs immediate attention.
If secondary drain is not installed, the secondary access must be plugged.
Insulate drain lines located inside the building or above a fin­ished living space to prevent sweating. Install a condensate trap to ensure proper drainage.
NOTE: When units are installed above ceilings, or in other locations where damage from condensate overflow may occur, it is MANDATORY to install a field fabricated auxiliary drain pan under the coil cabinet enclosure.
The installation must include a “P” style trap that is located as close as is practical to the evaporator coil. See Figure 12 for details of a typical condensate line “P” trap.
NOTE: Units operating in high static pressure applications may require a deeper field constructed “P” style trap than is shown in Figure 12 to allow proper drainage and prevent condensate over­flow.
Drain
Connection
Air Handler
POSITIVE LIQUID SEAL REQUIRED
AT T R AP
2" MIN.
3" MIN.
Figure 12
NOTE: Trapped lines are required by many local codes. In the
absence of any prevailing local codes, please refer to the require­ments listed in the Uniform Mechanical Building Code.
A drain trap in a draw-through application prevents air from being drawn back through the drain line during fan operation thus preventing condensate from draining, and if connected to a sewer line to prevent sewer gases from being drawn into the air­stream during blower operation.
Use of a condensate removal pump is permitted when necessary. This condensate pump should have provisions for shutting off the control voltage should a blocked drain occur. A trap must be installed between the unit and the condensate pump.
IMPORTANT NOTE: The evaporator coil is fabricated with oils that may dissolve styrofoam and certain types of plastics. Therefore, a removal pump or float switch must not contain any of these materials. Tip: Priming the “P” trap may avoid improper draining at the ini­tial installation and at the beginning of the cooling season.
8
Page 9
9 Ductwork
This air handler is designed for a complete supply and return ductwork system.
To ensure correct system performance, the ductwork is to be sized to accommodate 350-450 CFM per ton of cooling with the static pressure not to exceed 0.5" in w.c. Refer to ACCA Manual D, Manual S and Manual RS for information on duct sizing and appli­cation. Flame retardant ductwork is to be used and sealed to the unit in a manner that will prevent leakage.
NOTE: A downflow application with electric heat must have an L­shaped sheet metal supply duct without any outlets or registers located directly below the heater.
9.1 Return Ductwork
DO NOT LOCATE THE RETURN DUCTWORK IN AN AREA THAT CAN INTRODUCE TOXIC, OR OBJECTIONABLE FUMES/ ODORS INTO THE DUCTWORK. The return ductwork is to be connected to the air handler bottom (upflow configura­tion).
10 Return Air Filters
Each installation must include a return air filter. This filtering may be performed at the air handler using the factory filter rails or externally such as a return air filter grille. When using the factory filter rails, a nominal 16x20x1”, 20x20x1” or 24x20x1” (actual di­mension must be less than 23-½”x20”) filter can be installed on a B, C and D cabinet respectively (the cabinet size is the seventh letter of the model number).
11 Electric Heat
Do not operate this product without all the ductwork attached.
Refer to the installation manual provided with the electric heat kit for the correct installation procedure. All electric heat must be field installed. If installing this option, the ONLY heat kits that are permitted to be used are the HKS series. Refer to the air handler unit’s Serial and Rating plate or the HKS specification sheets to determine the heat kits compatible with a given air handler. No other accessory heat kit besides the HKS series may be installed in these air handlers.
The heating mode temperature rise is dependent upon the sys­tem airflow, the supply voltage, and the heat kit size (kW) selected. Use data provided in Tables 3, 4 and 5 to determine the tempera­ture rise (°F).
CFM
800 121923313756 1000 9 1519253044 1200 8 12152125374962 1400 7 11131821324253 1600 6 9 12 15 19 28 37 46 1800 5 8 10 14 16 25 33 41 2000 5 7 9 1215223037
3 5 6 8 10 15 19/20 25
230/1/60 SUPPLY VOLTAGE - TEMP. RISE °F
HEAT KIT NOMINAL kW
Table 2
CFM
800 111822303554 1000 9 1418242842 1200 7 12152024354759 1400 6 10131720304051 1600 6 9 11 15 18 27 35 44 1800 5 8 10 13 16 24 31 39 2000 4 7 9 12 14 21 28 35
3568101519/2025
HEAT KIT NOMINAL kW
220/1/60 SUPPLY VOLTAGE - TEMP. RISE °F
Table 3
CFM
800 1017212833
1000 8 1317222740 1200 7 11141922334556 1400 6 10121619293848 1600 5 8 10 14 17 25 33 42 1800 5 7 9 12 15 22 30 37 2000 4 7 8 11 13 20 27 33
3568101519/2025
HEAT KIT NOMINAL k W
208/1/60 SUPPLY VOLTAGE - TEMP. RISE °F
Table 4
Model
3 5 6 8 10 15 19 20 25
AVPTC25B14 550 650 700 800 850 875
AVPTC29B14 550 650 700 800 875 875
AVPTC35B14 550 650 700 800 875 1050
AVPTC37B14 550 650 700 800 875 1050
AVPTC33C14 600 700 750 875 950 950
AVPTC39C14 850 900 1000 1170 1345
AVPTC49C14 1170 1170 1170 1170 1345 1345
AVPTC31C14 600 850 900 1000 1170 1345 1345
AVPTC37C14 850 900 1000 1170 1345 1345
AVPTC59C14 1170 1170 1170 1170 1345 1345
AVPTC37D14 1240 1240 1240 1240 1520 1520 AVPTC59D14 1240 1240 1240 1240 1520 1520 AVPTC49D14 1250 1300 1500 1550 1720 AVPTC61D14 1250 1300 1500 1550 1780 1850 1850
HEATER (kW)
1345
MINIMUM CFM REQUIREMENTS FOR HEATER KITS
Table 5
NOTE: For installations not indicated above the following formula is to be used:
TR = (kW x 3412) x (Voltage Correction) / (1.08 x CFM)
Where: TR = Temperature Rise
kW = Heater Kit Actual kW 3412 = Btu per kW VC* = .96 (230 Supply Volts)
= .92 (220 Supply Volts) = .87 (208 Supply Volts)
1.08 = Constant CFM = Measured Airflow
VC* (Voltage Correction)
NOTE: The Temperature Rise Tables can also be used to estimate the air handler airflow delivery. When using these tables for this purpose set the room thermostat to maximum heat and allow the system to reach steady state conditions. Insert two thermometers, one in the return air and one in the supply air. The temperature rise is the supply air temperature minus the return air temperature. Using the temperature rise calculated, CFM can be estimated from the TR formula above. See Spec Sheets and/or Service Manual for more information.
9
Page 10
12 Electrical and Control Wiring
IMPORTANT: All routing of electrical wiring must be made through
provided electrical knockouts. Do not cut, puncture or alter the cabinet for electrical wiring.
12.1 Building Electrical Service Inspection
This unit is designed for single-phase electrical supply only.
DO NOT OPERATE ON A THREE-PHASE POWER SUPPLY. Mea­sure the power supply to the unit. The supply voltage must be measured and be in agreement with the unit nameplate power requirements and within the range shown.
Nominal Input Minimum Voltage Maximum Voltage
208-240 197 253
ELECTRICAL VOLTAGE
Table 6
Wire must be sized to allow no more than a 2% voltage
drop from the building breaker/fuse panel to the unit.
Wires with different insulation temperature rating have varying ampacities - be sure to check the temperature rat­ing used.
Refer to the latest edition of the National Electric Code or in Canada the Canadian Electric Code when determining the correct wire size.
12.3 Maximum Overcurrent Protection (MOP)
Every installation must include an NEC (USA) or CEC (Canada) approved overcurrent protection device. Also, check with local or state codes for any special regional re­quirements.
Protection can be in the form of fusing or HACR style circuit breakers. The Series and Rating Plate provides the maxi­mum overcurrent device permissible.
12.2 Wire Sizing
Wire size is important to the operation of your equipment. Use the following check list when selecting the appropriate wire size for your unit.
FIRE HAZARD! To avoid the risk of property damage, personal injury or fire, use only copper conductors.
HIGH VOLTAGE!
Disconnect ALL power before servicing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
HIGH VOLTAGE! To avoid property damage, personal injury or death due to electrical shock, this unit MUST have an uninterrupted, unbroken electrical ground circuit may consist of an appropriately sized electrical wire connecting the ground lug in the unit control box to the building electrical service panel. Other methods of grounding are permitted if performed in accordance with the National Electric Code (NEC)/American National Standards Institute (ANSI)/National Fire Protection Association (NFPA) 70 and local/state codes. In Canada, electrical grounding is to be in accordance with the Canadian Electric Code (CSA) C22.1.
electrical ground. The
Wire used must carry the Minimum Circuit Ampacity (MCA) listed on the unit’s Series and Rating Plate.
Refer to the NEC (USA) or CSA (Canada) for wire sizing. The unit MCA for the air handler and the optional electric heat kit can be found on the unit Series and Rating Plate.
NOTE: Fuses or circuit breakers are to be sized larger than the equipment MCA but not to exceed the MOP.
12.4 Electrical Connections – Supply Voltage
IMPORTANT NOTE: USE COPPER CONDUCTORS ONLY.
Knockouts are provided on the air handler top panel and sides of the cabinet to allow for the entry of the supply voltage conductors, as shown in Figure 13. If the knockouts on the cabinet sides are used for electrical conduit, an adapter ring must be used in order to meet UL1995 safety requirements. An NEC or CEC approved strain relief is to be used at this entry point. Some codes/municipalities re­quire the supply wire to be enclosed in conduit. Consult your local codes.
Top of
Cabinet
Side of
Cabinet
KNOCK-OUT FOR ELECTRICAL CONNECTIONS
Figure 13
12.4.1 Air Handler Only (Non-Heat Kit Models)
The building supply connects to the stripped black and red wires contained in the air handler electrical compartment cavity. A ground screw is also contained in this area. Attach the Supply wires to the air handler conductors as shown in the unit wiring diagram using appropriately sized solderless connectors or other NEC or CEC approved means.
10
Page 11
12.4.2 Air Handler - Non-Circuit Breaker Heat Kits
A
A terminal block is provided with the HKS kit to attach the power supply and air handler connections. Follow the HKS Installation Manual and wiring diagram for complete wir­ing details.
12.4.3 Air Handler With Circuit Breaker Heat Kit
The air handler has a plastic cover on the upper access panel that will require either one or both sections to be removed to allow the heat kit circuit breaker(s) to be installed. The circuit breakers have lugs for power supply connection. See the HKS Installation Instructions for further details.
12.5 Low Voltage Connections
Several combinations of low voltage schemes are possible, depending on the presence of a heat kit and whether the heat kit is single-stage or multi-stage, whether the outdoor section is an air conditioner or heat pump, and whether the system is setup with a communicating or traditional thermostat. The 24V-control voltage connects the air han­dler to the room thermostat and condenser. Low voltage wiring must be copper conductors. A minimum of 18 AWG must be used for installations up to 100 feet. Low voltage wiring must be connected through the top of the cabinet or either side. See the “Thermostat Wiring” section of this manual for typical low voltage wiring connections.
COOLING HEAT PUMP HEATING ELECTRIC HEATING
1-STAGE ------ 1- or 2-STAGE 2-STAGE ------ 1- or 2-STAGE 1-STAGE 1-STAGE -----­2-STAGE 2-STAGE -----­1-STAGE 1-STAGE 1- or 2-STAGE
2-STAGE 2-STAGE 1- or 2-STAGE
Table 7
Typical Single-Stage Cool,
Single-Stage Heat Thermostat
RCG
12RCG
RC
W1 Y1
W1 Y1 Y2
W2
Y
Remote Condensing Unit
(Single-Stage AC)
Typical Single-Stage Cooling with Single-Stage Heating
Figure 14
Place Jumper Between Y1
and O for Proper
Dehumidification Operation
and Proper Ramping
Profile Operation
Air Handler Integrated
DEHUM
O
NEU
HOT
Control Module
Dehumidistat
[Optional]
13 Achieving 1.4% and 2.0% Airflow Low Leakage Rate
Ensure all the gaskets remain intact on all surfaces as shipped with the unit. These surfaces are areas between the upper tie plate and coil access panel, blower access and coil access panels, and between the coil access and filter access panels. Ensure upon in­stallation, that the plastic breaker cover is sitting flush on the blower access panel and all access panels are flush with each other and the cabinet. With these requirements satisfied, the unit achieves less than 1.4% airflow leakage @ 0.5 inch wc static pres­sure and less than 2% airflow leakage @1inch wc static pressure when tested in accordance with ASHRAE Standard 193.
14 24 Volt Wiring
14.1 24 Volt Thermostat Wiring - Non-Communicating Thermostat Connections
NOTE: Wire routing must not interfere with the circulator blower operation or routine maintenance. The air handler’s integrated control module provides terminals for “Y1” and “Y2” and “W1” and “W2” thermostat connections. This allows the air handler to support the systems shown in the following table. Refer to the following figures for typical connec­tions to the integrated control module. Thermostat wiring entrance holes are located in the top of the blower. Wire routing must not interfere with circulator blower operation or routine maintenance.
NOTE: A removable plug connector is provided with the control to make thermostat wire connections. This plug may be removed, wire connections made to the plug, and replaced. It is STRONGLY recommended that you do not connect multiple wires into a single terminal. Wire nuts are recommended to ensure one wire is used for each terminal. Failure to do so may result in intermittent operation.
12RCG
12RC
11
Typical Two-Stage Cool,
Two-Stage Heat Thermostat
RCG
RC
W1 W2 Y1 Y2
W1 W2 Y1 Y2
Y1 Y2
Remote Condensing Unit
(Two-Stage AC)
Place Jumper Between Y1
and O for Proper
Dehumidification Operation
and Proper Ramping
Profile Operation
Air Handler Integrated
DEHUM
O
NEU
HOT
Control Module
Dehumidistat
[Optional]
Typical Two-Stage Cooling with Two-Stage Heating
Figure 15
RCG
RC
W/E
W1 W2 Y1 Y2
G
W1 Y
Remote Condensing Unit
(Single-Stage HP)
Y1
Typical Single-Stage Cool,
O
O
O
Single-Stage Heat
Heat Pump Thermostat
DEHUM
ir Handler
Integrated Control Module
NEU
Dehumidistat
HOT
[Optional]
Typical Single-Stage Heat Pum
with Auxiliary/Emergency Heating
Figure 16
Page 12
A
A
A
RCG
12RC
RC
Remote Condensing Unit
W/E
W2 Y1 Y2
W1 W2 Y1 Y2
G
W1 Y1 Y2
(Two-Stage HP)
Typical Two-Stage Cool,
O
O
O
Two-Stage Heat
Heat Pump Thermostat
DEHUM
Integrated Control Module
NEU
HOT
ir Handler
Dehumidistat
[Optional]
Typical Two Stage Heat Pump Heating
and Auxiliary/Emergency Heating
Figure 17
14.2 24 Volt Dehumidistat Wiring - Non-Communicating Thermostat Connections
The optional usage of a dehumidistat allows the air handler’s cir­culator blower to operate at a slightly lower speed during a com­bined thermostat call for cooling and dehumidistat call for dehu­midification. This lower blower speed enhances dehumidification of the conditioned air as it passes through the AC coil. For proper function, a dehumidistat applied to this air handler must operate on 24 VAC and utilize a switch which opens on humidity rise.
To install/connect a dehumidistat:
15 Auxiliary Alarm Switch
The control is equipped with two Auxiliary Alarm terminals la­beled CAS which can be utilized with communicating mode setups (typically used for condensate switch wiring but could be used with compatible C02 sensors or fire alarms).
Legacy mode use In a legacy system (Non-communicating), this feature is not op-
erational. Any auxiliary alarm switch must be used to interrupt the Y1 signal either to the indoor or outdoor unit.
Communication mode use
This feature can be activated or deactivated through the ther­mostat user menus. An auxiliary alarm switch must be normally closed and open when the base pan’s water level in the evapo­rator coil reaches a particular level. The control will respond by turning off the outdoor compressor and display the proper fault codes. If the switch is detected closed for 30 seconds, normal operation resumes and the error message will be removed.
SWITCH
CAS
1. Turn OFF power to air handler.
2. Secure the dehumidistat neutral wire (typically the white lead) to the screw terminal marked “DEHUM” on the air handler’s integrated control module.
3. Secure the dehumidistat hot wire (typically the black lead) to the screw terminal marked “R” on the air handler’s inte­grated control module.
4. Secure the dehumidistat ground wire (typically the green lead) to the ground screw on the air handler. NOTE: Ground wire may not be present on all dehumidistats.
5. To enable the dehumidification function, move the dehu­midification dip switch (S7) from OFF to ON. See following figure.
S5 S6 S7 S8
ON
OFF
Dip Switches -
Dehumidification Enable
Figure 18
Move to the ON position
to enable
dehumidification
Figure 19
16 AVPTC Motor Orientation
If the unit is in the upflow position, there is no need to rotate the motor. If the unit is in the downflow position, loosen motor mount and rotate motor as shown in the AVPTC Motor Orientation figure below. Be sure motor is oriented with the female connections on the casing down. If the motor is not oriented with the connec­tions down, water could collect in the motor and may cause pre­mature failure.
FRONT VIEW
FEMALE CONNECTIONS
AVPTC Motor Orientation
Figure 20
SIDE VIEW
W
RNING
SOFTW
RE VER.
TOP
6. Turn ON power to air handler.
12
Page 13
2
Seven Segment
LED
Green CFM LED
W1W2
C
ST1
3
ST4
24VAC
TH
TR
COM
FUSE 3A
ST3
CAS
DE
HUM
Y2
Y1
W2
W1
G
C
R
2
ST2
Auxiliary
Alarms
O
1
C 2 1 R
Dip Switches
Communicating Board
17 Circulator Blower
This air handler is equipped with a multi-speed circulator blower. This blower provides ease in adjusting blower speeds. The Speci­fication Sheet applicable to your model provides an airflow table, showing the relationship between airflow (CFM) and external static pressure (E.S.P.), for the proper selection of heating and cooling speeds. The heating blower speed shipped is set at 21kW or 25kW, and the cooling blower speed is set at “D”. These blower speeds should be adjusted by the installer to match the installation re­quirements so as to provide the correct electric heating CFM and correct cooling CFM.
Use the CFM LED (green) to obtain an approximate airflow quan­tity. The green CFM LED blinks once for each 100 CFM of airflow.
1. Determine the tonnage of the cooling system installed with the air handler. If the cooling capacity is in BTU/hr divide it by 12,000 to convert capacity to TONs.
Example: Cooling Capacity of 30,000 BTU/hr.
30,000/12,000 = 2.5 Tons
2. Determine the proper airflow for the cooling system. Most cooling systems are designed to work with airflows between 350 and 450 CFM per ton. Most manufacturers recommend an airflow of about 400 CFM per ton.
Example: 2.5 tons X 400 CFM per ton = 1000 CFM
Figure 21
The cooling system manufacturer’s instructions must be checked for required airflow. Any electronic air cleaners or other devices may require a specific airflow; consult installation instructions of those devices for requirements.
3. Knowing the air handler model, locate the high stage cool­ing airflow charts in the Specification Sheet applicable to your model. Look up the cooling airflow determined in step 2 and find the required cooling speed and adjustment setting.
Example: An AVPTC31C14 air handler installed with a 2.5
ton air conditioning system. The airflow needed is 1000 CFM. Looking at the cooling speed chart for AVPTC31C14, find the airflow closest to 1000 CFM. A cooling airflow of 1000 CFM can be attained by setting the cooling speed to “C” and the adjustment to “0” (no adjustment).
4. Locate the blower speed selection DIP switches on the inte­grated control module. Select the desired “cooling” speed tap by positioning switches 1 and 2 appropriately. If airflow adjustment is required, set dip switch S8 (trim enable) to ON (trim enable default is off). Then select the desired “adjust” tap by positioning switches S3 and S4 appropriately. Refer to the following Airflow Adjust Taps figure for switch posi­tions and their corresponding taps. Verify CFM by counting the number of times the green CFM LED blinks, see page 13 for LED locations.
13
Page 14
SPEED SELECTION DIP SWITCHES
COOL
SELECTION
SWITCHES
TAPS1S2S3S4S5S6S12S13
A OFF OFF OFF OFF OFF OFF OFF OFF
B ON OFF ON OFF ON OFF ON OFF
C OFF ON OFF ON OFF ON OFF ON
D ONONONONONONON ON
PROF ILES PRE-RU N SHOR T-RUN OFF DELAY
A
B
C
D
TO SET AIRFLOW
AIRFLOW. Determine the corresponding TAP (A, B, C, D). Set DIP switches S1 and S2 to the appropriate ON / OFF positions. (2) Select model and installed electric heater size. Set DIP switches S9, S10 and S11 to the appropriate ON / OFF positions. (3) If airflow adjustment is required, set TRIM ENABLE SWITCH S8 to ON (OFF = 0% Trim) and set S3 and S4 to appropriate ON / OFF positions. TAP A is +5%, TAP B is -5%, TAP C is +10%. TAP D is - 10%.
TO SET COMFORT MODE:
profiles above). Set DIP switc hes S5 and S6 to appropriate ON / OFF positions.
DEHUMIDIFICATION:
be reduced to 85% of nominal value during cool call when DEHUM command is present. To disable, set S7 to OFF.
CONTINUOUS FAN S PEED
the 4 continuous fan speeds, TAP A is 25%, TAP B is 50%, TAP C is 75%, TAP D is 100%.
NOTES:
1. Airflow data shown applies to legacy mode operation only. For a fully communica ting system, please see the outdoo r un it's insta llation instruc tions fo r cooling and heat pump airflow data. See ComfortNet System-Airflow Consideration section for details.
2. Airflow blink codes are approximations of actual airflow.
ADJUST
SELECTION
SWITCHES
PROFILE
SELECTION
SWITCHES
CONTINUOUS
FAN
SPEED
---- ---- 60 SEC. / 100%
---- 30 SEC. / 50% 60 SEC. / 100%
---- 7.5 MIN. / 82% 60 SEC. / 100%
30 SEC. / 50% 7.5 MIN. / 82% 30 SEC. / 50%
: (1) Select model and desired HIGH STAGE COOLING
Select desired Comfort Mode Profile. (see
To enable, set DIP switc h S7 to ON. Cooling airflow will
: Use DIP switches S12 and S13 to select one of
Cooling/Heat Pump Airflow Table
MODEL
Tap Low S tage High Sta ge
A 410 610 AV PTC25 B14 AVPTC35B14
B 565 840
C 650 970
D 685 1020
A 375 610 AVPTC29B14 AVPTC37B14
B 545 795
C 630 930
D 740 1085
A 450 675
AVPTC33C14
B 520 780
C 660 985
D 750 1115
A 665 990
AVPTC39C14
B 770 1150
C 815 1215
D 910 1360
A 710 875
AVPTC49C14
B 745 1225
C 880 1410
D 975 1595
A 595 870 AVPTC31C14 AVPTC37C14
B 705 1050
C 835 1260
D 870 1315
A 610 875
AVPTC59C14
B 810 1225
C 940 140
D 1070 1595
A 590 865
AVPTC37D14
B 700 1055
C 770 1210
D 885 1375
A 1040 1445
AVPTC59D14
B 1260 1790
C 16330 1890
D 1395 1990
A 820 1195
AVPTC49D14
B 895 1320
C 995 1460
D 1056 1530
A 1080 1630
AVPTC61D14
B 1210 1820
C 1280 1925
D 1350 2025
NOTE: Airflow blink codes are approximations of actual airflow. Airflows provided are at 0.3 static.
DIP SWITCH SETTING & AIRFLOW TABLE FOR ELECTRIC HEAT
HTR KW S9 S10 S11 AVPTC25B14 AVPTC29B14
3ONONON
5ONONOFF
6ONOFFON
8ONOFFOFF
10 OFF ON ON
15 OFF ON OFF
19* OFF OFF ON 1345 1345
20 OFF OFF ON 21 OFF OFF O FF
25* OFF OFF OFF 1850
Note: Airflow data shown applies to the electric heat only in either legacy mode or communicating mode operation * Within thermostat user menu CTK0* communicating thermostat will display 20KW for OFF- OFF- ON dip switch selection, 21kW for OFF -OFF-OFF dip swi th s ele cti on.
NR - Not ra ted †† For match up with a 3 ton outdoor unit Airflow for 5kW up to 15kW heater kits s hall be set to 1300 cfm speed ta p of ON-OFF-ON
††† For match up with a 3.5 ton outdoor unit: Heater kit appli caƟon shall not exceed 20kW Airflow for 5 kW up to 20kW heater kits s hall be s et to 1500 cfm speed ta p of ON-OFF-OFF
550 550 550
650 650 650
700 700 700
800 800 800
850 875 875
875 875 1050
AVPTC35B14 AVPTC37B14
AVPTC33C14 AVPTC39C14 AVPTC49C14 AVPTC37C14 AVPTC59C14 AVPTC37D14 AVPTC59D14 AVPTC49D14 II
600
700 850 11 70
750 900 11 70
875 100 0 1170
950 117 0 1170
950 134 5 1345
850 1170 1240 1240 1250 1250 850
900 1170 1240 1240 1300 1300 900
1000 1170 1240 1240 1500 1500 1000
1170 1170 1240 1240 1550 1550 1170
1345 1345 1520 1520 1720 1780 1345
1345 1345 1345
1520 1 520 1850
14
AVPTC61D14 III AV PTC31C14
600
Page 15
5. Continuous fan speeds that provide 25, 50, 75, and 100% of the air handler’s maximum airflow capability are selectable via dip switches S12 and S13.
If the air handler’s maximum airflow capability is 2000 CFM and 25% continuous fan speed is selected, the continuous fan speed will be 0.25 x 2000 CFM = 500 CFM.
6. The multi-circulator blower also offers several custom ON/ OFF ramping profiles. These profiles may be used to enhance cooling performance and increase comfort level. The ramp­ing profiles are selected using DIP switches 5 and 6. Refer to the following Dip Switches - Cooling Airflow Ramping Pro- files figure for switch positions and their corresponding taps. Refer to the bullet points below for a description of each ramping profile. Verify profile selection by counting the green CFM LED blinks and timing each step of the ramping profile.
Ta p A Ta p B
OFF OFF OFF OFFON ON ON ON
S1
S2
S1
S2
Tap C Tap D*
S1
S2
S1
S2
25% 50%*
OFF
OFF
S12
S13
12
13
S12
S13
Fan Only Selection (*indicates factory setting)
Fan Only Selection (*indicates factory setting)
ON
ON
OFF
OFF
12
13
75% 100%
OFF
OFF
ON ON
ON ON
12
S12
13
S13 S13
OFFON
OFFON
12
13
Figure 24
• Profile A provides only an OFF delay of one (1) minute at 100% of the cooling demand airflow.
OFF
100% CFM 100% CFM
1 min
Figure 26
OFF
• Profile B ramps up to full cooling demand airflow by first stepping up to 50% of the full demand for 30 seconds. The motor then ramps to 100% of the required airflow. A one (1) minute OFF delay at 100% of the cooling airflow.
Cooling Airflow Speed Tap (*indicates factory setting)
Figure 22
+5% -5%
OFF OFF OFF OFFON ON ON ON
S3
S4
S3
S4
Airflow Adjust Taps (*indicates factory setting)
+10% -10%
S3
S4
S3
S4
Dip Switches -
Cooling Airflow and Airflow Adjust Taps
Figure 23
21 kW* or
25 kW*
OFF OFF OFF OFFON ON ON ON
S9
S10
S11
19 kW or
20 kW
S9
S10
S11
15 kW 10 kW
S9
S10
S11
S10
S11
S9
OFF
50% CFM
1/2 min
100% CFM
100% CFM
OFF
1 min
Figure 27
• Profile C ramps up to 82% of the full cooling demand air­flow and operates there for approximately 7 1/2 minutes. The motor then steps up to the full demand airflow. Profile C also has a one (1) minute 100% OFF delay.
OFF
100% CFM
Figure 28
OFF
8 kW 6 kW 5 kW 3 kW
OFF OFF OFF OFFON ON ON ON
S9
S10
S11
S9
S10
S11
S9
S10
S11
S9
S10
S11
NOTE: Upon start up in communicating mode the circuit board may display an “Ec” error. This is an indication that the dip switches on the control board need to be configured in accordance with the Electric Heating Airflow Table. Configuring the dip switches and resetting power to the unit will clear the error code.
Within the thermostat user menu, CTK0* communicating thermostat will display 20 kW for OFF-OFF-ON dip switch selection and 21 kW for OFF-OFF-OFF dip switch selection.
Electric Heating Airflow (*indicates factory setting)
Figure 25
15
Page 16
• Profile D ramps up to 50% of the demand for 1/2 minute, then ramps to 82% of the full cooling demand airflow and operates there for approximately 7 1/2 minutes. The mo­tor then steps up to the full demand airflow. Profile D has a 1/2 minute at 50% airflow OFF delay.
18 Heat Kit Selection
For heat kit selection, see the Specification Sheet for each
specific Air Handler.
19 Troubleshooting
OFF
Figure 29
Tap A* Tap B Tap C Tap D
OFF OFF OFF OFFON ON ON ON
S5
S6
Dip Switches - Cooling Airflow Ramping Profiles
S5
S6
S5
S6
Figure 30
S5
S6
OFF
7. If an electric heater kit has been installed, determine the heater kilowatt (kW) rating. Using the Electric Heat Airflow table on page 14, set dip switches 9, 10, and 11 for the in­stalled heater. The adjust setting (already established by the cooling speed selection) also applies to the electric heater kit airflow. Thus, the electric heater airflow is adjusted by the same amount. This does not apply to systems setup with a communicating thermostat. See Set-Up section in the AIR HANDLER ADVANCED FEATURES MENU on page 21. Verify selected CFM by counting the green CFM LED blinks.
If an electric heater kit has not been installed, set dip switches 9, 10, and 11 to any valid heater kit setting (see airflow table for valid settings). This will prevent an Ec Error code from being displayed.
NOTE: For installations not indicated in the preceding Temperature Rise Tables, the following formula is to be used:
TR = (kW x 3412) x (Voltage Correction) / (1.08 x CFM)
Where: TR = Temperature Rise kW = Heater Kit Actual kW 3412 = Btu per kW Voltage Correction =.96 (230 Supply Volts)
=.92 (220 Supply Volts) =.87 (208 Supply Volts)
1.08 = Constant CFM = Measured Airflow
NOTE: The Temperature Rise Tables can also be used to determine the air handler airflow delivery. When using these tables for this purpose set the room thermostat to maximum heat and allow the system to reach steady state conditions. Insert two thermometers, one in the return air and one in the supply air. The temperature rise is the supply air temperature minus the room air temperature. Use HKR specification sheets to determine the HKR available for a given air handler.
19.1 Electrostatic Discharge (ESD) Precautions
NOTE: Discharge body’s static electricity before touching unit. An electrostatic discharge can adversely affect electrical components. Use the following precautions during air handler installation and servicing to protect the integrated control module from dam­age. By putting the air handler, the control, and the person at the same electrostatic potential, these steps will help avoid ex­posing the integrated control module to electrostatic discharge. This procedure is applicable to both installed and uninstalled (un­grounded) blowers.
WARNING
HIGH VOLTAGE!
TO
AVOID PERSONAL INJURY OR DEATH DUE TO
ELECTRICAL SHOCK, DISCONNECT ELECTRICAL POWER
BEFORE PERFORMING ANY SERVICE OR MAINTENANCE
1. Disconnect all power to the blower. Do not touch the inte­grated control module or any wire connected to the con­trol prior to discharging your body’s electrostatic charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the air handler blower near the control. Any tools held in a person’s hand during grounding will be discharged.
3. Service integrated control module or connecting wiring fol­lowing the discharge process in step 2. Use caution not to recharge your body with static electricity; (i.e., do not move or shuffle your feet, do not touch ungrounded objects, etc.). If you come in contact with an ungrounded object, repeat step 2 before touching control or wires.
4. Discharge your body to ground before removing a new con­trol from its container. Follow steps 1 through 3 if install­ing the control on a blower. Return any old or new con­trols to their containers before touching any ungrounded object.
19.2 Diagnostic Chart
Refer to the Troubleshooting Chart at the end of this manual for assistance in determining the source of unit operational prob­lems. The 7 segment LED display will provide any active fault codes. An arrow printed next to the display indicates proper orientation (arrow points to top of display). See Figure 31.
7 Segment Diagnostic Display
Figure 31
.
16
Page 17
19.3 Fault Recall
The integrated control module is equipped with a momentary push-button switch that can be used to display the last six faults on the 7 segment LED display. The control must be in Standby Mode (no thermostat inputs) to use the feature. Depress the push-button for approximately two seconds and less than five sec­onds. The LED display will then display the six most recent faults beginning with the most recent fault and decrementing to the least recent fault. The faults may be cleared by depressing the button for greater than five seconds.
NOTE: Consecutively repeated faults are displayed a maximum of three times. Example: A clogged return air filter causes the air handler’s motor to repeatedly enter a limiting condition. The control will only store this fault the first three consecutive times the fault occurs.
20 ComfortNet™ System
20.1 Overview
The ComfortNet system is a system that includes a ComfortNet compatible air handler and air conditioner or heat pump with a CTK0* thermostat. Any other system configurations are consid­ered invalid ComfortNet systems and must be connected as a tra­ditional (or non-communicating) system (see the 24 VOLT THERMO-
STAT WIRING - NON-COMMUNICATING THERMOSTAT CONNECTIONS section for
details). A ComfortNet heating/air conditioning system differs from a non-
communicating/traditional system in the manner in which the in­door unit, outdoor unit and thermostat interact with one another. In a traditional system, the thermostat sends commands to the indoor and outdoor units via analog 24 VAC signals. It is a one­way communication path in that the indoor and outdoor units typically do not return information to the thermostat.
On the other hand, the indoor unit, outdoor unit, and thermostat comprising a ComfortNet system “communicate” digitally with one another. It is now a two-way communications path. The thermostat still sends commands to the indoor and outdoor units. However, the thermostat may also request and receive informa­tion from both the indoor and outdoor units. This information may be displayed on the ComfortNet thermostat. The indoor and outdoor units also interact with one another. The outdoor unit may send commands to or request information from the indoor unit. This two-way digital communications between the thermo­stat and subsystems (indoor/outdoor unit) and between sub­systems is the key to unlocking the benefits and features of the ComfortNet system.
Two-way digital communications is accomplished using only two wires. The thermostat and subsystem controls are powered with 24 VAC Thus, a maximum of 4 wires between the equipment and thermostat is all that is required to operate the system.
20.1 Airflow Consideration
Airflow demands are managed differently in a fully communicat­ing system than they are in a non-communicating wired system. The system operating mode (as determined by the thermostat) determines which unit calculates the system airflow demand. If the indoor unit is responsible for determining the airflow de­mand, it calculates the demand and sends it to the ECM motor. If the outdoor unit or thermostat is responsible for determining the demand, it calculates the demand and transmits the demand along with a fan request to the indoor unit. The indoor unit then sends the demand to the ECM motor. The table below lists the various ComfortNet systems, the operating mode, and airflow de­mand source.
For example, assume the system is a heat pump matched with an air handler. With a call for low stage cooling, the heat pump will calculate the system’s low stage cooling airflow demand. The heat pump will then send a fan request along with the low stage cool­ing airflow demand to the air handler. Once received, the air han­dler will send the low stage cooling airflow demand to the ECM motor. The ECM motor then delivers the low stage cooling air­flow. See the applicable ComfortNet air conditioner or heat pump installation manual for the airflow delivered during cooling or heat pump heating.
In continuous fan mode, the CTK0* thermostat provides the airflow demand. Depending on which CTK0* thermostat has been installed three or four continuous fan speeds may be available. If the thermostat provides three speeds (low, medium, high) they correspond to 25%, 50% and 75%, respectively, of the air handlers’ maximum airflow capability. If the thermostat provides four continuous fan speeds then a 100% airflow option is added. During continuous fan operation, the thermostat sends a fan request along with the continuous fan demand to the air handler. The air handler, in turn, sends the demand to the ECM motor. The ECM motor delivers the requested continuous fan airflow.
Sys tem
Air Conditioner +
Air Handler
Hea t Pump + A ir
Handler
Sys tem
Operating Mode
Cooling A ir Conditioner
Heating A ir Handler
Continuous Fan Thermostat
Cooling Heat Pump
Heat Pump Heating
Only
HP + Electric Heat
Strips
Electric Heat Strips
Only
Airflow Dem and
Source
Heat Pump
> of Heat Pump or Air
Han dl er Demand
Air Handler
Continuous Fan Thermostat
Figure 32
17
Page 18
20.2 Control Wiring
NOTE: Refer to section Electrical Connections for 208/230 volt line connections to the air handler.
NOTE: A removable plug connector is provided with the control to make thermostat wire connections. This plug may be removed, wire connections made to the plug, and replaced. It is STRONGLY
recommended that you do not connect multiple wires into a single terminal. Wire nuts are recommended to ensure one wire is used for each terminal. Failure to do so may result in
intermittent operation.
Typical 18 AWG thermostat wire may be used to wire the system components. One hundred and fifty (150) feet is the maximum length of wire recommended between indoor unit and outdoor unit, or between indoor unit and thermostat.
Only the data lines 1 and 2 are required between the indoor and outdoor units. A 40VA, 208/230 VAC to 24 VAC transformer must be installed in the outdoor unit to provide 24 VAC power to the outdoor unit’s electronic control. See kit instructions for mount­ing and wiring instructions.
CTK04
1
2
R
C
1
2
R
C
1
2
R
C
20.5 Diagnostics
Accessing the air handler’s diagnostics menu provides ready access to the last six faults detected by the air handler. Faults are stored most recent to least recent. Any consecutively re­peated fault is stored a maximum of three times. Example: A clogged return air filter causes the air handler’s motor to repeat­edly entera limiting condition. The control will only store this fault the first three consecutive times the fault occurs.
NOTE: It is highly recommended that the fault history be cleared after performing maintenance or servicing the air handler.
20.6 Network Troubleshooting
The ComfortNet system is a fully communicating system, and thus, constitutes a network. Occasionally the need to trouble­shoot the network may arise. The integrated air handler control has some on-board tools that may be used to troubleshoot the network. These tools are: red communications LED, green re­ceive (Rx) LED, and learn button. Refer to the Communications Troubleshooting Chart at the end of this manual for error codes, possible causes and corrective actions.
Red communications LED – Indicates the status of the net­work. The table below indicates the LED status and the corresponding potential problem.
Green receive LED – Indicates network traffic. The
COMMUNICATIONS TROUBLESHOOTING CHART indicates
the LED status and the corresponding potential problem.
Learn button – Used to reset the network. Depress the button for approximately 2 seconds to reset the network.
20.4 ComfortNet™ System Advanced Features
The ComfortNet system permits access to additional system in­formation, advanced set-up features, and advanced diagnostic/ troubleshooting features. These advanced features are organized into a menu structure. See the AIR HANDLER ADVANCED FEA­TURES MENU section for layout of menu shortcuts.
20.7 System Troubleshooting
NOTE: Refer to the instructions accompanying the ComfortNet compatible outdoor AC/HP unit for troubleshooting information. Refer to the Troubleshooting Chart at the end of this manual for a listing of possible air handler error codes, possible causes and corrective actions.
18
Page 19
21 Start-Up Procedure
Prior to start-up, ensure that all electrical connections are properly sized and tightened.
All panels must be in place and secured. For Air Tight appli­cation, neoprene gasket must be positioned at prescribed locations to achieve low airflow as stated in section 13.
Tubing must be leak free.
Unit should be elevated, trapped and pitched to allow for drainage.
Low voltage wiring is connected.
Auxiliary drain is installed when necessary and pitched to allow for drainage.
Drain pan and drain tubing has been leak checked.
Return and supply ducts are sealed.
Unit is elevated when installed in a garage or where flam­mable vapors may be present.
Unit is protected from vehicular or other physical damage.
Return air is not obtained from any areas where there may be objectionable odors, flammable vapors or products of combustion such as carbon monoxide (CO), which may cause serious personal injury or death.
22 Regular Maintenance
HIGH VOLTAGE!
Disconnect ALL power before servicing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
The only item to be maintained on a regular basis by the user is the circulating air filter(s). Filter should be cleaned or replaced regularly. A certified service technician must perform all other services.
NOTE: THESE INSTRUCTIONS ARE SPECIFICALLY FOR AVPTC MODELS. DO NOT USE THESE DIAGRAMS FOR ANY OTHER MODELS. SEE SEPARATE INSTALLATION AND OPERATING INSTRUCTIONS FOR ATUF, ARUF, ARPT, ADPF, AND ASPF MODELS.
NOTICE: THIS PRODUCT CONTAINS ELECTRONIC COMPONENTS WHICH REQUIRE A DEFINITE GROUND. PROVISIONS ARE MADE FOR CONNECTION OF THE GROUND. A DEDICATED GROUND FROM THE MAIN POWER SUPPLY OR AN EARTH GROUND MUST BE PROVIDED.
19
Page 20
23 Communications Troubleshooting Chart
LED LED
Status
1 Flash
Red
Communications
LED
2 Flashes
1 Steady
Flash
Green Receive
LED
Rapid
Flashing On Solid
Off
Off
Indication Possible Causes Corrective Action(s) Notes & Cautions
Normal condition • None • None • None
Communications
Failure
Out-of-box reset • Control power up
No power
Communications
error
No network found Broken/ disconnected
Normal network
traffic
Data 1/ Data 2 miss-wire
Communications Failure
Learn button depressed
No power to air handler
Open fuse
Communications error
data wire(s)
Air handler is installed as a legacy/ traditional system
Control is “talking” on network as expected
Data 1 and data 2 wires reversed at air handler, thermostat, or CT™ compatible outdoor AC/HP
Short between data 1 and data 2 wires
Short between data 1 or data 2 wires and R (24VAC) or C (24VAC common)
Depress Learn Button
Verify that bus BIAS
and TERM dipswitches are in the ON position.
None None
Check fuses and
circuit breakers; replace/reset
Replace blown fuse
Check for shorts in
low voltage wiring in air handler/system
Reset network by depressing learn button
Check data 1/ data 2 voltages
Check communications wiring (data 1/ data 2 wires)
Check wire connections at terminal block
Verify air handler installation type (legacy/ traditional or communicating)
Check data 1/ data 2 voltages
None None
Check
communications wiring (data 1/ data 2 wires)
Check wire connections at terminal block
Check data 1/ data 2 voltages
Depress once quickly for a power­up reset
Depress and hold for 2 seconds for an out-of-box reset
Turn power OFF prior to repair
Turn power OFF prior to repair
Verify wires at terminal blocks are securely twisted together prior to inserting into terminal block
Verify data1 and data voltages as described above
Turn power OFF prior to repair
Verify wires at terminal blocks are securely twisted together prior to inserting into terminal block
Verify data1 and data voltages as described above
20
Page 21
24 Air Handler Advanced Features Menu
CONFIGURATION
Submenu Item
Electric Heat Size (HTR KW)
Motor HP (1/2, 3/4, or 1 MTR HP)
Heat ON Delay (HT ON) Displays the electric heat indoor blower ON delay.
Heat OFF Delay (HT OFF) Dis plays the elec tric heat indoor blower OFF delay.
Submenu Item Indication/User Modifiable Options Comments
Fault 1 (FAULT #1) Most recent modular fault For display only
Fault 2 (FAULT #2) Next most recent modular fault For display only
Fault 3 (FAULT #3) Next most recent modular fault For display only
Fault 4 (FAULT #4) Next most recent modular fault For display only
Fault 5 (FAULT #5) Next most recent modular fault For display only
Fault 6 (FAULT #6) Least recent modular fault For display only
Clear Fault History (CLEAR) NO or YES Selecting “YES” clears t he fault history
Consecutively repeated faults are shown a maximum of 3 times
NOTE:
Displays t he size in kW of the selected elec tric heaters.
Displays t he air handler indoor blower motor horsepower.
Indication (for Display Only; not Use r Modifiable)
DIAGNOSTICS
IDENTIFICATION
Submenu Item
Model Number (MOD NUM) Displays t he modular blower model number
Serial Number (SER NUM) Displays the modular blower serial number (Optional)
Software (SOFTWARE) Displays the application software revision
Submenu Item Use r Modifia ble Options Comments
Heat Airflow Trim (HT TRM) -10% to +10% in 2% increments, default is 0%
Submenu Item
Mode (MODE) Displays t he current air handler operating mode
CFM (CFM) Displays the airflow for the current operating mode
Indication (for Display Only; not Use r Modifiable)
SET-UP
STATUS
Indication (for Display Only; not Use r Modifiable)
Trims the heating airflow by the selected amount.
21
Page 22
25 Troubleshooting
Notes & Cautions
Corrective Actions
Possible Causes
x Normal operation x None x Normal operation
x Turn power OFF prior to
x Verify electric heat dipswitch
x Heater kit selected via
EC
repair.
x Use memory card for
settings
x Verify the installed electric
dipswitches is too large for
heater kits in shared data set
the specific model.
heater is valid for the air
BEFORE turning power
x Insert memory card
handler blower. Check
nameplate or Specification
ON. Memory card may
Sheet applicable to your
be removed after data is
loaded.
model* for allowable heater
kit(s).
x Turn power off before
x Verify shared data set is
repair.
the specific model.
BEFORE turning power
ON. Memory card may
be removed after data is
removing memory card.
x Turn power OFF prior to
x Use memory card for
x Insert memory card
correct for the specific model.
Re-populate data using
correct memory card if
required.
settings
heater is valid for the air
dipswitches is too small for
x Verify the installed electric
heater kits in shared data set
handler blower. Check
x Verify electric heat dipswitch
x Heater kit selected via
EC
loaded.
removing memory card.
x Turn power off before
nameplate or Specification
Sheet applicable to your
model* for allowable heater
kit(s).
correct for the specific model.
Re-populate data using
x Verify shared data set is
repair.
the specific model.
BEFORE turning power
ON. Memory card may
be removed after data is
loaded.
removing memory card.
x Turn power OFF prior to
x Use memory card for
x Insert memory card
settings
heater is valid for the air
handler blower. Check
nameplate or Specification
Sheet applicable to your
correct memory card if
required.
x Verify electric heat dipswitch
x Verify the installed electric
dipswitches is doesn’t match
heater kits in shared data set
x Heater kit selected via
EC
model* for allowable heater
x Turn power off before
kit(s).
correct for the specific model.
Re-populate data using
x Verify shared data set is
correct memory card if
required.
service.
x Turn power OFF prior to
service
x Check overflow pan and
evaporation coil.
x High water level in the
EF
ComfortNet™
None None
Thermostat Only
Message Code
HTR TOO
Fault Description
x Heater kit selected via
x Normal operation
EC
ON
Codes
Characters
Will Alternate
7-Segment LED
LARGE
dipswitches is too
large for heater kits
specified in shared
SMALL
HTR TOO
data set
x Heater kit selected via
EC
dipswitches is too
small for heater kits
specified in shared
data set
MATCH
NO HTR
dipswitches does not
heater kits specified in
x Heater kit selected via
EC
shared data set
Fault
Aux Alarm
x Aux switch open
EF
Symptoms of Abnormal Operation
(Legacy & ComfortNet™ Thermostat)
call for W1 or Auxiliary/Emergency
heat
provides the indicated error code.
Service” icon illuminated
x LED display is ON continuously
x Electric heaters fail to energize on a
x Integrated control module LED display
“Check Air Handler” message
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls
x Electric heat airflow is higher than
expected on a call for W1 or
Auxiliary/Emergency heat
x Integrated control module LED display
provides the indicated error code.
expected on a call for W1 or
Auxiliary/Emergency heat
x Electric heat airflow is higher than
provides the indicated error code.
x Integrated control module LED display
x Integrated control module LED display
EF error code.
x ComfortNet™ thermostat “Call for
Service”.
22
Page 23
25 Troubleshooting (Sheet 2 of 4)
repair.
control module fuse with
3A automotive fuse.
control module with
correct replacement part
x Turn power OFF prior to
x Replace integrated
x Replace integrated
volt power to air handler
blower and integrated control
module.
x Assure 208/230 volt and 24
Possible Causes Corrective Actions Notes & Cautions
or 24 volt wire improperly
x Manual disconnect switch OFF
EE
module fuse (3A). Replace if
x Check integrated control
connected or loose
an internal fault
x Blown fuse or circuit breaker
x Integrated control module has
“Electrostatic Discharge”
x Read precautions in
necessary.
208/230 volt and 24 volt
circuits. Repair as necessary.
x Check for possible shorts in
section of manual.
x Replace bad integrated
control module.
repair
the specific model.
x Turn power OFF prior to
x Use memory card for
using memory card.
x Populate shared data set
contain any shared data.
x Air handler blower does not
d0
repair
BEFORE turning power
ON. Memory card may
be removed after data is
loaded.
cleared once data is
loaded.
x Insert memory card
x Error code will be
x Turn power off before
removing memory card
the specific model.
x Turn power OFF prior to
x Use memory card for
set using memory card.
x Populate correct shared data
contain an appropriate shared
data set.
x Air handler blower does not
d1
BEFORE turning power
ON. Memory card may
be removed after data is
x Insert memory card
loaded.
x Error code will be
cleared once data is
loaded.
x Turn power OFF prior to
x Verify shared data set is
x Shared data set on memory
d4
repair
x Use memory card for
correct for the specific model.
Re-populate data using
card has been rejected by
integrated control module
the specific model.
BEFORE turning power
ON. Memory card may
be removed after data is
loaded.
cleared once data is
loaded.
x Insert memory card
correct memory card if
required.
x Error code will be
x Turn power off before
removing memory card
ComfortNet™
Thermostat Only
Codes
7-Segment LED
FAULT
Message Code
INTERNAL
Fault Description
to air handler blower
x No 208/230 volt power
No Display
Characters
Will Alternate
or no 24 volt power to
integrated control
module
breaker
x Blown fuse or circuit
DATA
NO NET
module has an internal
fault.
x Integrated control
x Data not yet on
d0
network.
INVALID
x Invalid data on
d1
DATA
network.
INVALID
x Invalid memory card
d4
MC DATA
data.
Symptoms of Abnormal Operation
(Legacy & ComfortNet™ Thermostat)
provides no signal.
Service” icon illuminated
x ComfortNet™ thermostat “Call for
“Check Air Handler” message
x ComfortNet™ thermostat scrolls
x Air handler blower fails to operate
x Integrated control module LED display
provides indicated error code.
x Air handler blower fails to operate.
x Integrated control module LED display
Service” icon illuminated.
“Check Air Handler” message.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls
provides indicated error code.
Service” icon illuminated.
x Air handler blower fails to operate.
x Integrated control module LED display
“Check Air Handler” message.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls
operation.
provides indicated error code.
Service” icon illuminated.
x Operation different than expected or no
x Integrated control module LED display
“Check Air Handler” message.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls
23
Page 24
25 Troubleshooting (Sheet 3 of 4)
Notes & Cautions
Corrective Actions
Possible Causes
x Turn power OFF prior to
x Tighten or correct wiring
x Loose wiring connection at
b0
repair
x Replace circulator motor
connection.
x Check circulator blower
circulator motor power leads
or circulator motor power
with correct
replacement part.
motor. Replace if necessary.
leads disconnected.
x Failed circulator blower motor.
repair
x Turn power OFF prior to
connection.
x Tighten or correct wiring
circulator motor control leads.
x Loose wiring connection at
b1
with correct
replacement part.
x Replace circulator motor
motor. Replace if necessary.
x Check circulator blower
x Check integrated control
module.
x Failed circulator blower motor.
x Failed integrated control
control module with
x Replace integrated
module. Replace if
necessary.
correct replacement
part.
x Turn power OFF prior to
x Verify circulator blower motor
x Incorrect circulator blower
b2
repair
x Replace motor with
horse power is the same
specified for the specific air
motor in air handler blower.
x Incorrect shared data set in
correct replacement
part.
x Use memory card for
handler blower model.
Replace is necessary.
x Verify shared data set is
integrated control module.
the specific model
x Insert memory card
correct for the specific model.
Re-populate data using
for installation requirements.
x See "Installation Instructions"
x Turn power OFF prior to
x Check filters, filter
x Abnormal motor loading,
b4
repair.
grills/registers, duct system,
and air handler blower/coil air
sudden change in speed or
torque, sudden blockage of air
inlet/outlet for blockages.
handler blower/coil air inlet or
outlet.
x High loading conditions,
blocked filters, very restrictive
ductwork, blockage of air
handler blower/coil air inlet or
outlet.
BEFORE turning power
ON. Memory card may
be removed after data is
loaded.
cleared once shared
data and motor horse
power match.
removing memory card
x Error code will be
correct memory card if
required.
x Turn power off before
x Turn power OFF prior to
x Check filters for blockage.
x Blocked filters.
b3
repair.
Clean filters or remove
obstruction.
x Restrictive ductwork.
x Undersized ductwork.
x Check ductwork for blockage.
x High ambient temperatures.
Remove obstruction. Verify
all registers are fully open.
x Verify ductwork is
appropriately sized for
system. Resize/replace
ductwork if necessary.
ComfortNet™
Thermostat Only
MOTOR
Message Code
NOT RUN
Fault Description
motor is not running
x Circulator blower
b0
Codes
Characters
Will Alternate
7-Segment LED
when it should be
running.
MOTOR
x Integrated control
b1
COMM
module has lost
MOTOR
MISMATCH
communications with
circulator blower
motor.
x Circulator blower
b2
motor horse power in
shared data set does
not match circulator
blower motor horse
power.
MOTOR
x Circulator blower
b3
LIMITS
motor is operating in a
power, temperature, or
speed limiting
condition.
MOTOR
x Circulator blower
b4
TRIPS
motor senses a loss
rotor control.
x Circulator blower
motor senses high
current.
Symptoms of Abnormal Operation
(Legacy & ComfortNet™ Thermostat)
provides indicated error code.
Service” icon illuminated.
“Check Air Handler” message.
provides indicated error code.
Service” icon illuminated.
x Air handler blower fails to operate.
x Integrated control module LED display
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls
x Air handler blower fails to operate.
x Integrated control module LED display
“Check Air Handler” message.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls
provides indicated error code.
Service” icon illuminated.
x Air handler blower fails to operate.
x Integrated control module LED display
“Check Air Handler” message.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls
performance.
x Air handler blower operates at reduced
provides b3 error code.
x Airflow delivered is less than expected.
x Integrated control module LED display
provides indicated error code.
Service” icon illuminated.
x Air handler blower fails to operate.
x Integrated control module LED display
“Check Air Handler” message.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls
24
Page 25
25 Troubleshooting (Sheet 4 of 4)
Notes & Cautions
Corrective Actions
Possible Causes
repair
x Turn power OFF prior to
obstructions. Remove and
x Check circulator blower for
blower housing.
x Obstruction in circulator
b5
correct replacement
part.
x Replace motor with
repair/replace wheel/motor if
necessary.
x Check circulator blower motor
bearings.
x Seized circulator blower motor
x Failed circulator blower motor.
repair.
correct replacement
part.
x Turn power OFF prior to
x Replace wheel with
blower. Verify line voltage to
blower is within the range
specified on the air handler
blower rating plate.
hander blower.
x High ambient temperatures.
for installation requirements.
x See "Installation Instructions"
shaft rotation and motor.
Replace motor if necessary.
x Check power to air handler
handler blower.
x High AC line voltage to air
x Low AC line voltage to air
b6
repair.
x Turn power OFF prior to
module. Verify control is
x Check integrated control
module.
x Error with integrated control
b7
x Replace with correct
populated with correct shared
x Motor has a locked rotor
replacement part(s).
x Use memory card for
data set. See data errors
above for details.
condition.
the specific model.
x Check for locked rotor
BEFORE turning power
ON.
removed after data is
x Memory card may be
loaded
x Insert memory card
condition (see error code
above for details).
x Turn power off before
repair.
removing memory card.
x Turn power OFF prior to
Clean filters or remove
obstruction.
Remove obstruction. Verify
all registers are fully open.
appropriately sized for
system. Resize/replace
x Check filters for blockage.
x Blocked filters.
b9
x Restrictive ductwork.
x Check ductwork for blockage.
x Undersized ductwork.
ductwork if necessary.
x Verify ductwork is
ComfortNet™
MTR
Thermostat Only
LCKD
Message Code
Fault Description
motor fails to start 10
x Circulator blower
b5
Codes
Characters
Will Alternate
7-Segment LED
ROTOR
consecutive times.
MOTOR
x Circulator blower
b6
VOLTS
motor shuts down for
over or under voltage
condition.
x Circulator blower
motor shuts down due
to over temperature
condition on power
module.
MOTOR
x Circulator blower
b7
PARAMS
motor does not have
enough information to
LOW ID
AIRFLOW
operate properly.
Motor fails to start 40
consecutive times.
demanded.
x Airflow is lower than
b9
Symptoms of Abnormal Operation
(Legacy & ComfortNet™ Thermostat)
provides indicated error code.
Service” icon illuminated.
x Air handler blower fails to operate.
x Integrated control module LED display
“Check Air Handler” message.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls
provides indicated error code.
Service” icon illuminated.
x Air handler blower fails to operate.
x Integrated control module LED display
“Check Air Handler” message.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls
provides indicated error code.
Service” icon illuminated.
x Air handler blower fails to operate.
x Integrated control module LED display
“Check Air Handler” message.
x ComfortNet™ thermostat “Call for
x ComfortNet™ thermostat scrolls
x Air handler blower operates at reduced
performance or operates on low stage
when high stage is expected.
provides indicated error code.
x Integrated control module LED display
25
Page 26
26 Diagnostic Codes
7 SEGMENT LED
(characters will
alternate)
(no di s play) INTE RNAL CONTROL F AULT / NO POW E R
DESCRIPTION OF CONDITION
On STANDBY, WAITING FOR INPUTS
Ed HEATER KIT DIP SWITCHES NOT SET PROPERLY Eb NO HTR KIT INSTALLED - SYSTEM CALLING FOR AUXILIARY HEAT E5 FUSE OPEN
EF AUXILIARY SWITCH OPEN
d0 DATA NOT ON NETWORK d1 INVALID DATA ON NETWORK d4 INV ALID ME MORY CA RD DATA b0 BLOWER MOTOR NOT RUNNING b1 BL OW ER MOTOR COMM UNICATION ERROR b2 BLOWER MOTOR HP MISMATCH b3 BLOWER MOTOR OPERATING IN POWER, TEMP., OR SPEED LIMIT b4 BLOWER MOTOR CURRENT TRIP OR LOST ROTOR b5 BLOWER MOTOR ROTOR LOCKED b6 OVER/UNDER VOLTAGE TRIP OR OVER TEMPERATURE TRIP
b7 INCOMPL ETE PARAMETER S E NT TO MOTO R
b9 LOW INDOOR AIRFLOW C1 LOW STAGE COOL - LEGACY MODE ONLY C2 HIGH STAGE COOL - LEGACY MODE ONLY P1 LOW STAGE HEAT PUMP HEAT - LEGACY MODE ONLY P2 HIGH STAGE HEAT PUMP HEAT - LEGACY MODE ONLY
h1 EMERGENCY HEAT LOW - COMMUNICATING MODE ONLY
h2 EMERGENCY HEAT HIGH - COMMUNICATING MODE ONLY
FC FA N CO OL - COMM UNICATING MODE ONLY FH FAN HEAT - COMMUNICATING MODE ONLY
FFAN ONLY H1 ELECTRIC HEAT LOW H2 ELECTRIC HEAT HIGH
dF
DEFROST - COMMUNICATING MODE ONLY
(note: defrost is di splayed as H1 in a legacy setup)
GREEN CFM LED - EACH FLASH REPRESENTS 100CFM (USE FOR AIRFLOW
AP PROXIMATION ONLY) - EXA MPLE : 8 FLASHES = 800CFM
0140A00079-A
26
Page 27
27 Wiring Diagrams
WARNING
HIGH VOLTAGE!
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO
DISCONNECT ALL POWER BEFORE SERVICING.
MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
PL1
PL2
2
2
3
3
1
1
6
6 5
5
4
4
7
7
8
8
9
9
SEE
NOTE 7
BK
RD
BL
GY
BK
RD
40 VA TRANSFORMER, SEE NOTE 1
230 VAC
RD
RD
208 VAC
BK
BK
WH
BR
BL
4
4 CIRCUIT HEATER
CONNECTOR
SEE NOTE 5
SEE NOTE 6
CONNECTOR
4
3
2
1
ECM MOTOR
HARNESS
SEE NOTE 6
COOL AF PROFILE
S5 S6 S7 S8
DIP SWITCHES
RD
24 VAC
BL
7 SEGMENT
DIAGNOSTIC
DISPLAY
TRIM ENABLE
DEHUM ENABLE
S9
SEE NOTE 6
HTR KIT(KW)
S10
C
3
4 CIRCUIT MOTOR
COM
S1
W2
2
STATUS
LED
CFM LED
AF SELECT
S2 S3 S4
3
2
1
W1
1
FAULT
RECALL
TRIM %
TWO-STAGE INTEGRATED CONTROL MODULE
CIRCULATOR BLOWER
3
2
4
1
1 2
3 4
5
RX LED
S11
RD
TH
24 V 3 A
SEE NOTE 8
DEHUM
CONT FAN
S13
S12
BK
GN
GRND
W2
W1
RD
Y2
Y1
COM
FUSE
CAS
O
G
C
R
2
1
BL
TR
GRND
GN
DISCONNECT
L1
24 V THERMOSTAT CONNECTIONS
FUSE 3 A
R
24V THERMOSTAT CONNECTIONS
W1
W2
Y1
TO
Y2
MICRO
G
O
DEHUM
C
L1
GRND
INDOOR
AIR
CIRCULATOR
BLWRLEARN
208/230 VAC
TH
W1 (1)
W2 (2)
CAS (1)
CAS (2)
+VDC (1)
RX (2)
TX (3)
GRND (4)
TR
COM
INTEGRATED CONTROL MODULE
24 VAC
HEAT 1 COIL/R1
HEAT 2 COIL/ R2
CONDENSATE SWITCH
L2
GRND
40 VA TRANSFORMER
INDOOR
CIRCULATOR
L2
AIR
BLWR
GRND
NOTES:
1. PLACE RED WIRES ON TRANSFORMER TERMINAL 2 FOR 208 VAC OPERATION.
2. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING.
3. IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH THIS UNIT MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105°C. USE COPPER CONDUCTORS ONLY.
4. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C AND LOCAL CODES.
5. TO RECALL THE LAST 6 FAULTS, MOST RECENT TO LEAST RECENT, DEPRESS SWITCH FOR MORE THAN 2 SECONDS WHILE IN STANDBY (NO THERMOSTAT INPUTS)
6. RED STATUS LED PROVIDES NETWORK STATUS. GREEN RX LED INDICATES NETWORK TRAFFIC. USE LEARN BUTTON TO RESET NETWORK.
7. DISCARD CONNECTOR PL1 WHEN INSTALLING OPTIONAL HEAT KIT.
8. THE CONDENSATE ALARM SWITCH (CAS) TERMINALS CAN ONLY BE UTILIZED WITH COMMUNICATING MODE SETUPS AND MUST BE ENABLED WITH A COMMUNICATING THERMOSTAT. THIS FEATURE IS NOT OPERATIONAL WITH LEGACY SYSTEMS.
USE N.E.C CLASS 2 WIRE.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
27
INTEGRATED CONTROL
LOW VOLTAGE (24V)
LOW VOLTAGE FIELD
HI VOLTAGE (230V)
HI VOLTAGE FIELD
JUNCTION
TERMINAL
INTERNAL TO
EQUIPMENT GRND
FIELD GRND
FIELD SPLICE
RESISTOR
OVERCURRENT
PROT. DEVICE
PLUG CONNECTION
COLOR CODES: PK ---- PINK
BR ---- BROWN WH ---- WHITE BL ---- BLUE
GY ---- GRAY
RD ---- RED
YL ---- YELLOW OR ---- ORANGE
PU ---- PURPLE
GN ---- GREEN
BK ---- BLACK
0140A00244-B
Page 28
27 Wiring Diagrams
3-Phase Heat Kit
WARNING
HIGH VOLTAGE!
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
DISCONNECT ALL POWER BEFORE SERVICING.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
28
Page 29
AIR HANDLER
AIR HANDLER HOMEOWNER’S ROUTINE MAINTENANCE RECOMMENDATIONS
We strongly recommend a bi-annual maintenance checkup be performed before the heating and cooling seasons begin by a qualified servicer.
REPLACE OR CLEAN FILTER
IMPORTANT NOTE: Never operate unit without a filter installed as dust and lint will build up on internal parts resulting in loss of
efficiency, equipment damage and possible fire. An indoor air filter must be used with your comfort system. A properly maintained filter will keep the indoor coil of your comfort
system clean. A dirty coil could cause poor operation and/or severe equipment damage. Your air filter or filters could be located in your furnace, in a blower unit, or in “filter grilles” in your ceiling or walls. The installer of your
air conditioner or heat pump can tell you where your filter(s) are, and how to clean or replace them. Check your filter(s) at least once a month. When they are dirty, replace or clean as required. Disposable type filters should be replaced.
Reusable type filters may be cleaned. You may want to ask your dealer about high efficiency filters. High efficiency filters are available in both electronic and non-electronic
types. These filters can do a better job of catching small airborne particles.
MOTORS
Indoor and outdoor fan motors are permanently lubricated and do not require additional oiling.
ALUMINUM INDOOR COIL CLEANING (QUALIFIED SERVICER ONLY)
This unit is equipped with an aluminum tube evaporator coil. The safest way to clean the evaporator coil is to simply flush the coil with water. This cleaning practice remains as the recommended cleaning method for both copper tube and aluminum tube residential evaporator coils.
It has been determined that many coil cleaners and drain pan tablets contain corrosive chemicals that can be harmful to aluminum tube and fin evaporator coils. Even a one-time application of these corrosive chemicals can cause premature aluminum evaporator coil failure. Any cleaners that contain corrosive chemicals including, but not limited to, chlorine and hydroxides, should not be used.
An alternate cleaning method is to use one of the products listed in TP-109* to clean the coils. The cleaners listed are the only agents deemed safe and approved for use to clean round tube aluminum coils. TP-109 is also available on the web site in Partner Link > Service Toolkit.
NOTE: Ensure coils are rinsed well after use of any chemical cleaners.
BEFORE YOU CALL YOUR SERVICER
Check the thermostat to confirm that it is properly set.
Wait 15 minutes. Some devices in the outdoor unit or in programmable thermostats will prevent compressor op­eration for awhile, and then reset automatically. Also, some power companies will install devices which shut off air con­ditioners for several minutes on hot days. If you wait sev­eral minutes, the unit may begin operation on its own.
Check the electrical panel for tripped circuit breakers or failed fuses. Reset the circuit breakers or replace fuses as necessary.
Check the disconnect switch near the indoor furnace or blower to confirm that it is closed.
Check for obstructions on the outdoor unit . Confirm that it has not been covered on the sides or the top. Remove any obstruc­tion that can be safely removed. If the unit is covered with dirt or debris, call a qualified servicer to clean it.
Check for blockage of the indoor air inlets and outlets. Confirm that they are open and have not been blocked by objects (rugs, curtains or furniture).
Check the filter. If it is dirty, clean or replace it.
Listen for any unusual noise(s), other than normal operating noise, that might be coming from the outdoor unit. If you hear unusual noise(s) coming from the unit, call a qualified servicer.
29
Page 30
THIS PAGE WAS LEFT BLANK INTENTIONALLY
30
Page 31
THIS PAGE WAS LEFT BLANK INTENTIONALLY
31
Page 32
CUSTOMER FEEDBACK
We are very interested in all product comments. Please fill out the feedback form on one of the following links:
Goodman® Brand Products: (http://www.goodmanmfg.com/about/contact-us). Amana® Brand Products: (http://www.amana-hac.com/about-us/contact-us). You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page.
PRODUCT REGISTRATION
Thank you for your recent purchase. Though not required to get the protection of the standard warranty, registering your product is a relatively short process, and entitles you to additional warranty protection, except that failure by California and Quebec residents to register their product does not diminish their warranty
rights.
For Product Registration, please register as follows: Goodman® Brand products: (https://www.goodmanmfg.com/product-registration). Amana® Brand products: (http://www.amana-hac.com/product-registration) You can also scan the QR code on the right for the product brand you purchased to be directed to the Product Registration page.
GOODMAN® BRAND
GOODMAN® BRAND
AMANA® BRAND
AMANA® BRAND
© 2016-2017 Goodman Manufacturing Company, L.P.
5151 San Felipe, Suite 500, Houston, TX 77056
www.goodmanmfg.com - or - www.amana-hac.com
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
32
Loading...