The following symbols and labels are used throughout this
manual to indicate immediate or potential safety hazards.
It is the owner’s and installer’s responsibility to read and
comply with all safety information and instructions accompanying these symbols. Failure to heed safety information
increases the risk of personal injury, property damage, and/
or product damage.
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION.
Keep this literature in a safe place for future reference.
ATTENTION INSTALLING PERSONNEL
IO-901
2/2015
It is your responsibility to install the product safely and to educate the customer on its safe use.
Prior to installation, thoroughly familiarize yourself with this Installation Manual.
Observe all safety warnings. During installation or repair, caution is to be observed.
Page 2
HIGH VOLTAGE!
Disconnect ALL power before ser vicing.
Multiple power sources may be present.
Failure to do so may cause p roperty damage,
personal injury or death.
Install ati on an d re pair of t his u ni t sho uld b e p erf orm ed
by indiv id uals me et ing t he requi re men ts of an
ONLY
“entry level technician” as specified by
, at a minimum,
the Ai r-Co ndi ti on in g, H eati ng a nd Re fri g erati on I nst i tu te
(AHRI). Attempting to install or repair this unit without
such ba ck grou nd may re sul t i n p r od uct damag e,
personal inju ry or death.
This product is factory-shipped for use with
208/240/1/60 electrical power supply.
DO NOT
reconfigure this air handler to operate with any other
power supply.
To avoid property damage, personal injury or death
due to electrical shock, this unit MUST have an
uninterrupted, unbroken
electrical ground. The
electrical ground circuit may consist of an
appropriately sized electrical wire connecting the
ground lug in the unit control box to the building
electrical service panel.
Other meth ods of gro unding ar e p ermit te d i f pe rfo rmed
in accordance with the National Electric Code
(NEC) /Amer ican National Stan dards I nsti tute
(ANSI)/ Nati onal Fire P rotec tion A ssocia tion (NFP A) 70
and local /s ta te c ode s. I n Canada, e le ctr ica l gro undi ng
is to be in accordance wit h the C ana dian Electric Code
(CSA) C22.1.
When installing or servicing this equipment, safety
clothing, including hand and eye protection, is
strongly recommended. If installing in an area that has
special safety requirements (hard hats, etc.), bserve
o
these requirements.
Do not connect to or use any device that is not designcertified by the manufacturer for use with this unit.
Serious property damage, personal injury, reduced
unit performance and/or hazardous conditions may
result from the use of such non-approved devices.
To prevent the risk of property damage, personal
injury , or dea th, do not store comb ustible m aterials or
use gasoline or other flammable liquids or vapors in
the vicin ity of this unit.
CO can ca u se serious il lness includ in g permanent b r ai n
damage or death.
Advertencia especial para la instalación de calentadores ó manejadoras
de aire en áreas cerradas como estacionamientos ó cuartos de servicio.
Las emisiones de monóxido de carbono pueden circular a través
del aparato cuando se o pe ra en cua lqu i e r mo do .
El mo nó xido de carbo no puede ca usar enferme da des severas
como daño cerebral permanente ó muerte.
RISQUE D'EMPOISONNEME NT AU
Cette ven t ilation est nécess aire po ur éviter le danger d'intoxicati on
au CO pouvant survenir si un appareil produisant du monoxyde
de carbone contin ue de fonctionner au sein d e la zone confinée.
MONOXYDE DE CARBONE
2
Page 3
2Shipping Inspection
Always transport the unit upright; laying the unit on its side or top during transit may cause equipment damage. The
installer should inspect the product upon receipt for shipping damage and subsequent investigation is the responsibility of
the carrier. The installer must verify the model number, specifications, electrical characteristics, and accessories are
correct prior to installation. The distributor or manufacturer will not accept claims from dealers for transportation
damage or installation of incorrectly shipped units.
2.1 Parts
Also inspect the unit to verify all required components are present and intact. Report any missing components
immediately to the manufacturer or to the distributor. Use only factory authorized replacement parts (see Section
5). Make sure to include the full product model number and serial number when reporting and/or obtaining service
parts.
2.2 Handling
Use caution when transporting/carrying the unit. Do not move unit using shipping straps. Do not carry unit with hooks
or sharp objects. The preferred method of carrying the unit after arrival at the job site is to carry via a two-wheel
hand truck from the back or sides or via hand by carrying at the cabinet corners.
3Codes & Regulations
This product is designed and manufactured to comply with applicable national codes. Installation in accordance with such
codes and/or prevailing local codes/regulations is the responsibility of the installer. The manufacturer assumes no
responsibility for equipment installed in violation of any codes or regulations.
The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduction
and disposal of refrigerants. Failure to follow these regulations may harm the environment and can lead to the
imposition of substantial fines. Should you have any questions please contact the local office of the EPA and/or refer to
EPA’s website www.epa.gov.
4Replacement Parts
When reporting shortages or damages, or ordering repair parts, give the complete product model and serial numbers as
stamped on the product. Replacement parts for this product are available through your contractor or local distributor.
For the location of your nearest distributor consult the white business pages, the yellow page section of the local telephone book or contact:
CONSUMER AFFAIRS
GOODMAN MANUFACTURING COMPANY, L.P.
7401 SECURITY WAY
HOUSTON, TEXAS 77040
(877) 254-4729
5 Pre-Installation Considerations
5.1 Preparation
Keep this document with the unit. Carefully read all instructions for the installation prior to installing product. Make
sure each step or procedure is understood and any special considerations are taken into account before starting
installation. Assemble all tools, hardware and supplies needed to complete the installation. Some items may need to
be purchased locally. Make sure everything needed to install the product is on hand before starting.
5.2 System Matches
The entire system (combination of indoor and outdoor sections) must be manufacturer approved and Air-Conditioning, Heating, and Refrigeration Institute (AHRI) listed. NOTE: Installation of unmatched systems is not permitted and
will void the product warranty.
5.3 Interconnecting Tubing
Give special consideration to minimize the length of refrigerant tubing when installing air handlers. Refer to Remote
Cooling/Heat Pump Service Manual RS6200006, and TP-107 Long Line Set Application R-410A for tubing guidelines. If
possible, allow adequate length of tubing such that the coil may be removed (for inspection or cleaning services) from
the cabinet without disconnecting the tubing.
3
Page 4
5.4 Clearances
The unit clearance from a combustible surface may be 0". However, service clearance must take precedence. A
minimum of 24" in front of the unit for service clearance is required. Additional clearance on one side or top will be
required for electrical wiring connections. Consult all appropriate regulatory codes prior to determining final clearances. When installing this unit in an area that may become wet (such as crawl spaces), elevate the unit with a
sturdy, non-porous material. In installations that may lead to physical damage (i.e. a garage) it is advised to install
a protective barrier to prevent such damage. Always install units such that a positive slope in condensate line (1/4"
per foot) is allowed.
5.5 Horizontal Applications
If installed above a finished living space, a secondary drain pan (as required by many building codes), must be
installed under the entire unit and its condensate drain line must be routed to a location such that the user will see
the condensate discharge.
6 Installation Location
NOTE: These air handlers are designed for indoor installation
only.
The ARUF**14** and ASPT**14** product lines may be installed in
one of the upflow, downflow, horizontal left or horizontal right
orientations as shown in Figures 2, 3, 4 and 5. The unit may be
installed in upflow or horizontal left orientation as shipped (refer to specific sections for more information).
Minor field modifications are necessary to convert to downflow
or horizontal right as indicated in below sections.
Side Drain Pan Removal: Refer to Figure 1, remove the two (2)
screws that secure the drip shield support brackets to the
condensate collectors (front and back). Unsnap the side drain
pan from vertical (bottom) drain pan using a screw driver or any
small lever. The side drain pan and drip shield brackets may now
be removed. The bottom left drain connection is the primary
drain for this application and condensate drain line must be
attached to this drain connection. The bottom right drain
connection is for the secondary drain line (if used).
6.1 Upflow Installation
No field modifications are mandatory however to obtain maximum efficiency, the horizontal side drain pan & extension must
be removed.
DRIP SHIELD REMOVAL
Figure 1
6.2 Horizontal Left Installation
No field modifications are permissible for this application.
The bottom left drain connection is the primary drain for this application and condensate drain line must be attached to
this drain connection. The bottom right drain connection is
for the secondary drain line (if used).
6.3 Downflow
No field modifications are mandatory however to obtain
maximum efficiency, the horizontal side drainpan & extension must be removed.
IMPORTANT NOTE: To prevent coil pan “sweating” in the
downflow application, a downflow kit (DFK) is available
through your local distributor. The DFK is not supplied with
the air handler and is required by the manufacturer on all
downflow installations. See Table 1 for the correct DFK and
follow the instructions provided for installation.
Side drainpan extension must be removed for all models except : ARUF47D14**, ARUF61D14**, ASPT61D14**.
Refer to Figure 6 and 7 for the location of the components referenced in the following steps.
1. Before inverting the air handler, remove blower access panel and coil access panel. The coil access panel and tubing
panel may remain screwed together during this procedure. Remove and retain the seven (7) screws securing the coil
access panel to the cabinet and the six (6) screws securing the blower access panel to the cabinet.
2. Slide the coil assembly out from the cabinet. Use the drain pan to pull the assembly from the cabinet.
NOTE: DO NOT USE MANIFOLDS OR FLOWRATOR TO PULL THE COIL ASSEMBLY OUT. FAILURE TO DO SO MAY
RESULT IN BRAZE JOINT DAMAGE AND LEAKS.
3. Removal of the center support is required on units
with 21" wide cabinet. Remove and retain the two
(2) screws that secure the center support to the cabinet. Remove the center support.
4. Using the drain pan to hold the coil assembly, slide
the coil assembly back into the cabinet on the
downflow brackets as shown in Figure 8.
5. Re-install the center support (if removed) using the
two (2) screws removed in Step 4.
6. Re-install the access panels removed in Step 1 as
shown in Figure 9.
7. The bottom right drain connection is the primary drain
for this application and condensate drain line must
be attached to this drain connection. The bottom left
drain connection is for the secondary drain line (if
used). Install the PVC plug that was removed from
the side drain pan primary connection and install it
on the vertical primary connection.
NOTE: If removing only the coil access panel from the
unit, the filter access panel must be removed first. Failure to do so will result in panel damage.
UPFLOW
Figure 2
DOWNFLOW
Figure 3
HORIZONTAL LEFT
Figure 4
HORIZONTAL RIGHT
Figure 5
5
Page 6
INTERNAL PART TERMINOLOGY
Figure 6
Coil Slides
on the down flow bracket
Secondary
Drain Port
for
Horizontal
Application
Blower
Access
Panel
Tubi ng
Panel
Secondary
Drain Port for
Upflow/DownflowApplication
EXTERNAL PART TERMINOLOGY
Figure 7
IMPORTANT NOTE:
Ensure coil slides on the rails along the groove provided on the drain pan side
walls. Failure to do so will result in improper condensate drainage.
COIL INSTALLATION FOR DOWNFLOW
Figure 8
ACCESS PANEL CONFIGURATION FOR DOWNFLOW
OR HORIZONTAL RIGHT
Figure 9
6
Page 7
7Refrigerant Lines
NOTE: Refrigerant tubing must be routed to allow adequate
access for servicing and maintenance of the unit.
Do not install the air handler in a location that violates
the instructions provided with the condenser. If the unit
is located in an unconditioned area with high ambient
temperature and/or high humidity, the air handler may
be subject to nuisance sweating of the casing. On these
installations, a wrap of 2" fiberglass insulation with a vapor
barrier is recommended.
7.1 Tubing Size
For the correct tubing size, follow the specification
for the condenser/heat pump.
7.2 Tubing Preparation
All cut ends are to be round, burr free, and clean.
Failure to follow this practice increases the chances
for refrigerant leaks. The suction line is spun closed
and requires tubing cutters to remove the closed end.
NOTE: To prevent possible damage to the tubing joints, do not handle coil assembly with manifold or flowrator tubes.
Always use clean gloves when handling coil assemblies.
7.3 Special Instructions
This product is factory-shipped with R410A and dry
nitrogen mixture gas under pressu re. Use appr opria te
service tools and follow these instructions to prevent
injury .
A quenching cloth is strongly recommended to prevent
scorching or marring of the equipment finish when
brazing close to the painted surfaces. Use brazing
alloy of 5% minimum silver content.
CAUTION
Applying too much heat to any tube can melt the tube. Torch
heat required to braze tubes of various sizes must be
proportiona l to the s ize of th e tub e. S erv ice p ersonn el m u st
use the appropriate heat level for the size of the tube being
brazed.
Units without a factory installed TXV come equipped with a flowrator piston for refrigerant expansion. For most
installations with matching applications, no change to the flowrator piston is required. However, in mix-matched
applications, a flowrator piston change may be required. See the piston kit chart (provided in the literature packet)
or consult your local distributor for details regarding mix-matched flowrator piston sizing. If the mix-match application requires a different flowrator piston size, change the flowrator piston in the flowrator body on the indoor
coil before installing the coil and use the procedure in section 8.4.
NOTE: The use of a heat shield is strongly recommended when brazing to avoid burning the serial plate or the finish
of the unit. Heat trap or wet rags must be used to protect heat sensitive components such as service valves and TXV
valves sensing bulb.
7.4 Tubing Connections for Flowrator Model
1. Loosen the 13/16 nut 1 TURN ONLY to allow high pressure tracer
SUCTION LINE
WITH SPIN CLOSURE
gas to escape. No gas indicates a possible leak.
2. After the gas has been expelled, remove the nut and discard the
black or brass cap plastic seal.
RUBBER
GROMMET
3. Remove the flowrator piston to verify it is the correct size for
the outdoor unit being installed and then replace the piston
(changing size, if needed). See piston kit chart in the literature
kit for appropriate piston size.
SUCTION SPUN END AND GROMMET
Figure 10
4. Remove the spin closure on the suction line using a tube cutter
and deburr the tube.
5. Insert the suction line into the connection, slide the insulation and the rubber grommet at least 18" away from the
braze joint.
6. Remove the tailpiece clamped to the exterior of the cabinet or in the literature kit packet and slide the 13/16 nut
into place.
7. Braze tailpiece to the line set liquid tube and braze suction line connection. Quench all brazed joints with a damp
rag upon completion of brazing. Do not allow water to enter the inside of the tubing.
7
Page 8
8. AFTER THE TAILPIECE HAS COOLED, confirm position of the white
Teflon® seal and hand tighten the 13/16 nut.
PLASTIC or BRASS CAP
9. Torque the 13/16 nut to 7-25 ft-lbs. or tighten 1/6 turn.
TAILPIECE
Excessive torque can cause orifices to stick. Use the
proper torque settings when tightening orifices.
13/16” NUT
WHITE
TEFLON SEAL
PISTON
TAILPIECE JOINT
7.5 Tubing Connections for TXV Models
TXV models come with factory installed TXV with the bulb pre-
Figure 11
installed on the vapor tube.
1. Remove refrigerant tubing panel or coil (lower) access panel.
2. Remove access valve fitting cap and depress the valve stem in access fitting to release pressure. No pressure indicates possible leak.
3. Replace the refrigerant tubing panel.
4. Remove the spin closure on both the liquid and suction tubes using a tubing cutter.
5. Insert liquid line set into liquid tube expansion and slide grommet about 18" away from braze joint.
6. Insert suction line set into suction tube expansion and slide insulation and grommet about 18" away from braze joint.
7. Braze joints. Quench all brazed joints with water or a wet rag upon completion of brazing.
8Condensate Drain Lines
The coil drain pan has a primary and a secondary drain with 3/4" NPT female connections. The connectors required are 3/
4" NPT male, either PVC or metal pipe, and should be hand tightened to a torque of no more than 37 in-lbs. to prevent
damage to the drain pan connection. An insertion depth of approximately 3/8” to 1/2” (3-5 turns) should be expected at
this torque.
1. Ensure drain pan hole is not obstructed.
2. To prevent potential sweating and dripping on to finished space, it may be necessary to insulate the condensate drain
line located inside the building. Use Armaflex® or similar material.
A secondary condensate drain connection has been provided for areas where the building codes require it. Pitch all drain
lines a minimum of 1/4" per foot to provide free drainage. Provide required support to the drain line to prevent bowing.
If the secondary drain line is required, run the line separately
from the primary drain and end it where condensate discharge
can be easily seen.
NOTE: Water coming from secondary line means the coil primary drain is plugged and needs immediate attention.
If secondary drain is not installed, the secondary
access must be plugged.
Insulate drain lines located inside the building or above a finished living space to prevent sweating. Install a condensate
trap to ensure proper drainage.
NOTE: When units are installed above ceilings, or in other locations
where damage from condensate overflow may occur, it is MANDATORY
to install a field fabricated auxiliary drain pan under the coil cabinet
enclosure.
The installation must include a “P” style trap that is located as close as
is practical to the evaporator coil. See Figure 12 for details of a typical
condensate line “P” trap.
NOTE: Trapped lines are required by many local codes. In the absence
of any prevailing local codes, please refer to the requirements listed in
the Uniform Mechanical Building Code.
CAUTION
Air Handler
POSITI VE LIQUID
SEAL REQUIRED
AT TRAP
Drain
Connection
2" MIN.
3" MIN.
Figure 12
8
Page 9
A drain trap in a draw-through application prevents air from being drawn back through the drain line during fan operation thus preventing condensate from draining, and if connected to a sewer line to prevent sewer gases from being drawn
into the airstream during blower operation.
Field experience has shown condensate drain traps with an open vertical Tee between the air handler and the condensate
drain trap can improve condensate drainage in some applications, but may cause excessive air discharge out of the open
Tee. The manufacturer does not prohibit this type of drain but we also do not recommend it due to the resulting air
leakage. Regardless of the condensate drain design used, it is the installer’s responsibility to ensure the condensate drain
system is of sufficient design to ensure proper condensate removal from the coil drain pan.
Use of a condensate removal pump is permitted when necessary. This condensate pump should have provisions for
shutting off the control voltage should a blocked drain occur. A trap must be installed between the unit and the condensate pump.
IMPORTANT NOTE: The evaporator coil is fabricated with oils that may dissolve styrofoam and certain types of plastics.
Therefore, a removal pump or float switch must not contain any of these materials.
Tip: Priming the “P” trap may avoid improper draining at the initial installation and at the beginning of the cooling
season.
9Ductwork
This air handler is designed for a complete supply and return ductwork system.
To ensure correct system performance, the ductwork is to
be sized to accommodate 350-450 CFM per ton of cooling
with the static pressure not to exceed 0.5" in w.c. Refer to
ACCA Manual D, Manual S and Manual RS for information on duct sizing and application. Flame retardant ductwork is to
be used and sealed to the unit in a manner that will prevent leakage.
NOTE: A downflow application with electric heat must have an L-shaped sheet metal supply duct without any outlets or
registers located directly below the heater.
9.1 Return Ductwork
Do not operate this product without all the ductwork
attached.
DO NOT LOCATE THE RETURN DUCTWORK IN AN AREA THAT CAN INTRODUCE TOXIC, OR OBJECTIONABLE FUMES/
ODORS INTO THE DUCTWORK. The return ductwork is to be connected to the air handler bottom (upflow configuration).
10Return Air Filters
Each installation must include a return air filter. This filtering may be performed at the air handler using the factory
filter rails or externally such as a return air filter grille. When using the factory filter rails, a nominal 16x20x1”, 20x20x1”
or 24x20x1” (actual dimension must be less than 23-½”x20”) filter can be installed on a B, C and D cabinet respectively
(the cabinet size is the seventh letter of the model number).
11Electric Heat
Refer to the installation manual provided with the electric heat kit for the correct installation procedure. All electric
heat must be field installed. If installing this option, the ONLY heat kits that are permitted to be used are the HKS series.
Refer to the air handler unit’s Serial and Rating plate or the HKS specification sheets to determine the heat kits compatible with a given air handler. No other accessory heat kit besides the HKS series may be installed in these air handlers.
The heating mode temperature rise is dependent upon the system airflow, the supply voltage, and the heat kit size (kW)
selected. Use data provided in Tables 2, 3 and 4 to determine the temperature rise (°F).
NOTE: For installations not indicated above the following formula is to be used:
TR = (kW x 3412) x (Voltage Correction) / (1.08XCFM)
Where:TR= Temperature Rise
kW= Heater Kit Actual kW
3412 = Btu per kW
VC*= .96 (230 Supply Volts)
= .92 (220 Supply Volts)
= .87 (208 Supply Volts)
1.08 = Constant
CFM = Measured Airflow
*VC (Voltage Correction)
9
Page 10
NOTE: The Temperature Rise Tables can also be used to estimate the air handler airflow delivery. When using these
tables for this purpose set the room thermostat to maximum heat and allow the system to reach steady state conditions.
Insert two thermometers, one in the return air and one in the supply air. The temperature rise is the supply air temperature
minus the room air temperature. Using the temperature rise calculated, CFM can be estimated from the TR formula
above. See Technical Manual and/or Service Manual for more information.
IMPORTANT: All routing of electrical wiring must be made
through provided electrical knockouts. Do not cut, puncture or alter the cabinet for electrical wiring.
12.1 Building Electrical Service Inspection
Nominal InputMinimum Voltag eM aximum Voltage
208-240197253
ELECTRICAL VOLTAGE
Table 6
This unit is designed for single-phase electrical supply only. DO NOT OPERATE ON A THREE-PHASE POWER SUPPLY.
Measure the power supply to the unit. The supply voltage must be measured and be in agreement with the unit
nameplate power requirements and within the range shown.
12.2 Wire Sizing
Wire size is important to the operation of your equipment. Use the following check list when selecting the
appropriate wire size for your unit.
•Wire used must carry the Minimum Circuit Ampac-
ity (MCA) listed on the unit’s Series and Rating Plate.
•Refer to the NEC (USA) or CSA (Canada) for wire sizing. The unit MCA for the air handler and the optional electric heat kit can be found on the unit Series and Rating Plate.
•Wire must be sized to allow no more than a 2% volt-
age drop from the building breaker/fuse panel to
the unit.
•Wires with different insulation temperature rating
have varying ampacities - be sure to check the temperature rating used.
Refer to the latest edition of the National Electric
Code or in Canada the Canadian Electric Code when
determining the correct wire size.
12.3 Maximum Overcurrent Protection (MOP)
Every installation must include an NEC (USA) or CEC
(Canada) approved overcurrent protection device.
Also, check with local or state codes for any special
regional requirements.
Protection can be in the form of fusing or HACR style
circuit breakers. The Series and Rating Plate provides the maximum overcurrent device permissible.
FIRE HAZARD!
To avoid the risk of property damage, personal injury
or fire, use only copper conductors.
HIGH VOLTAGE!
Disconnect ALL power before servicing.
Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death.
HIGH VOLTAGE!
T o avoid prope rty dama ge , persona l injury or death
due to el ect rical shock, this unit M U S T have an
uninterrupted, unbroken
electrical ground circuit may consist of an
appro pri at ely sized electrical wire connecting the
ground lug in the unit control box to the building
electrical service panel.
Other methods of grounding are permit ted if perform ed
in accordance with the National Electric Code
(NEC) /Americ an Nation al Standar ds Institut e
(ANSI)/National Fire Protection Association (NFP A) 70
and local/state codes. In Canada, electrical grounding
is to be in ac co rda nce w ith th e C ana dian Elec tric Cod e
(CSA) C22.1.
electrical ground. The
NOTE: Fuses or circuit breakers are to be sized larger than the equipment MCA but not to exceed the MOP.
11
Page 12
12.4 Electrical Connections – Supply Voltage
IMPORTANT NOTE: USE COPPER CONDUCTORS ONLY.
Knockouts are provided on the air handler top panel and
sides of the cabinet to allow for the entry of the supply
voltage conductors, as shown in Figure 13. If the knockouts
on the cabinet sides are used for electrical conduit, an
adapter ring must be used in order to meet UL1995 safety
requirements. An NEC or CEC approved strain relief is to be
used at this entry point. Some codes/municipalities require the supply wire to be enclosed in conduit. Consult
your local codes.
12.4.1 Air Handler Only (Non-Heat Kit Models)
The building supply connects to the stripped black and red
wires contained in the air handler electrical compartment
cavity. A ground screw is also contained in this area. Attach the Supply wires to the air handler conductors as shown in the unit wiring diagram using appropriately sized
solderless connectors or other NEC or CEC approved means.
12.4.2 Air Handler - Non-Circuit Breaker Heat Kits
A terminal block is provided with the HKS kit to attach the power supply and air handler connections. Follow the
HKS Installation Manual and wiring diagram for complete wiring details.
12.4.3 Air Handler With Circuit Breaker Heat Kit
Top of
Cabinet
KNOCK-OUT FOR ELECTRICAL CONNECTIONS
Figure 13
Side of
Cabinet
The air handler has a plastic cover on the upper access panel that will require either one or both sections to be
removed to allow the heat kit circuit breaker(s) to be installed. The circuit breakers have lugs for power supply
connection. See the HKS Installation Instructions for further details.
12.5 Low Voltage Connections
Several combinations of low voltage schemes are possible, depending on the presence of a heat kit and whether the
heat kit is single-stage or multi-stage, whether the outdoor section is an air conditioner or heat pump, and whether
the outdoor section is single-stage or two-stage. The 24V-control voltage connects the air handler to the room
thermostat and condenser. Low voltage wiring must be copper conductors. A minimum of 18AWG must be used for
installations up to 100 feet. Low voltage wiring must be connected through the top of the cabinet or either side.
See the “Thermostat Wiring” section of this manual for typical low voltage wiring connections.
12.5.1 Thermostats
Second-stage heat can be accomplished by a multi-stage heating thermostat or the addition of an outdoor thermostat as shown in wiring schematics on pages 14 and 15. Follow the thermostat manufacturer’s instructions for
installation.
12.6 Speed Tap Adjustment
ARUF**14** air handlers have multi-speed PSC motors. The color of the wire coming from the motor to the “COM”
terminal on the control board defines at which speed the motor will operate. Black wire is high speed, blue wire is
medium speed and red wire is low speed. To change speeds, remove the wire attached to the “COM” terminal on
the control board, and swap it with the wire (on terminal “M1” or “M2”) with the color that will give the desired
speed.
ASPT**14** air handlers feature energy efficient blower motors. The motors run at a constant torque with very low
power consumption and are energized by 24 VAC. Adjust the CFM by changing the 24 VAC leads to the desired speed
tap on the terminal block. The ASPT blower motor speeds are programmed to deliver adequate airflow at rated
external static pressure and with 60 second off time delay. For details, refer to the specification sheet applicable
to your model.
NOTE: In some models, not all speed taps are allowable for certain electric heat applications. Refer to Table 5 for
minimum speed.
12
Page 13
13Achieving 1.4% Low Leakage Rate
Ensure all the gaskets remain intact on all surfaces as shipped with the unit. These surfaces are areas between the upper
tie plate and blower access panel, blower access and coil access panels, and between the coil access and filter access
panels. Ensure upon installation, that the plastic breaker cover is sitting flush on the blower access panel and all access
panels are flush with each other and the cabinet. With these requirements satisfied, the unit achieves less than 1.4%
airflow leakage when tested in accordance with ASHRAE Standard 193.
14Start-Up Procedure
•Prior to start-up, ensure that all electrical wires are properly sized and all connections are properly tightened.
•All panels must be in place and secured. For Air Tight application, gasket must be positioned at prescribed locations to achieve 1.4% leakage.
•Tubing must be leak free.
•Condensate line must be trapped and pitched to allow for drainage.
•Low voltage wiring is properly connected.
•Auxiliary drain is installed when necessary and pitched to allow for drainage.
•Unit is protected from vehicular or other physical damage.
•Return air is not obtained from, nor are there any return air duct joints that are unsealed in, areas where there may
be objectionable odors, flammable vapors or products of combustion such as carbon monoxide (CO), which may
cause serious personal injury or death.
15Regular Maintenance
The only item required to be maintained on a regular basis
by the user is the circulating air filter(s). Filter should be
cleaned or replaced regularly, typically once per month. A
certified service technician must perform all other services.
IMPORTANT NOTE: If thumb screws are used to access the
filter, ensure the washer installed on the screw behind the
access panel remains in place after re-installation.
HIGH VOLTAGE!
Disconnect ALL power before servicing or
installing this unit. Multiple power sources may
be present. Failure to do so may cause property
damage, personal injury or death.
1. Airf low data indicated is at 230V without air filter in place.
2. The ch ar t i s f o r in form at io n o n ly . F o r satisfacto r y o pe r atio n , ext er n al stat ic pr essu r e m ust n ot ex ce ed value sho w n o n
3. Use the CFM adjustment factors of 0.98 for horizontal left and 0.96 f or horizontal rig ht & downflow orientations
2265222
AIRFLOW DATA (CFM)
Table 7
14
139
133512601180
172516701635
2045200019701935
218521652120
Page 15
Air Handler Low Voltage Connections
The following composite wiring diagrams detail various configurations in which the air handlers can be used. Examples
include single-stage cooling and heat pump with single or two-stage electric heating. All these configurations can be
applied with convenient connections to outdoor thermostat applications.
The following sections are detailed:
•Single-Stage Cooling
•Heat Pump
Each diagram details the connections between room thermostat and the air handlers, and the connections between the
air handlers and the Condensing Unit (or Heat Pump) with optional connections to Outdoor Thermostats. For each
configuration, refer to the explanation of the proper jumper(s) to remove for the corresponding blower speed that will
result in the programmed fixed speed ECM motor.
IMPORTANT: WHEN MATCHING THE ASPT AIR HANDLERS TO A SINGLE SPEED COOLING OR HEAT PUMP
UNIT, REMEMBER TO CONNECT “Y” FROM THE THERMOSTAT TO THE “Y2” ON THE LOW VOLTAGE
TERMINAL BOARD.
An equivalent thermostat can be used in place of the manufacturer’s thermostat part number.
NOTE: Some models feature low voltage wires and do not include a terminal block. For those applications use the
corresponding colored wires.
WARNING
HIGH VOLTAG E !
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO
MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
YL
BL
TO CONDENSING UNIT
24V CONNECTION
DISCO NNECT ALL POWER BEFORE SERVICING.
#18 GA. 4 WIRES WITH COOLING
3 WIRES WITHOUT
YW
GR
AIR HANDLER
RD
GR
WH
YL
YL
BL
C
R
G
W1
W2
Y1
Y2
O
TB
COOLING UNIT WITH OPTIONAL HEAT KITS OF 10 kW AND BELOW
NOTES:
1) OUTDOOR THERMOSTAT (OT-1) SHOULD BE THE FIRST
TO CLOSE AND THE LAST TO OPEN.
2) JUMPER W1 AND W2 TOGETHER IF OT-2 IS NOT USED.
3) REMOVE WIRE WHEN USING OUTDOOR THERMOSTAT.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
NOMENCLATURE:
OT - OUTDOOR THERMOSTAT (OPTIONAL)
EHR - EMERGENCY HEAT RELAY (OPTIONAL)
15
COLOR CODES
RD - RED
YL - YELLOW
BL - BLUE
BR - BROWN
OR - ORANGE
WH - WHITE
Page 16
WARNING
HIGH VOLTAG E !
DISCO NNECT ALL POWER BEFORE SERVICING.
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO
MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
#18 GA. 5 WIRES WITH COO LIN G
4 WIRES WITHOUT
W2
YGW
R
AIR HANDLER
C
YL
BL
BR
YL
CONDENSING UNIT
24V CONNE C TION
RD
GR
WH
BR
BR
YL
YL
BL
R
G
W1
W2
Y1
Y2
O
TB
COOLING UNIT WITH OPTIONAL HEAT KITS OF 15 kW AND ABOVE
AND ROOM THERMOSTAT WITH TWO STAGES OF HEAT
#18 GA. 7 WIRE
W2
YC
O
RYO
YL
RD
YL
OR
WH
BL
HEAT PUMP UNIT WITH OPTIONAL HEAT KITS OF 10 kW AND BELOW
NOTES:
1) OUTDOOR THERMOSTAT (OT-1) SHOULD BE THE FIRST
TO CLOSE AND THE LAST TO OPEN.
2) JUMPER W1 AND W2 TOGETHER IF OT-2 IS NOT USED.
3) REMOVE WIRE WHEN USING OUTDOOR THERMOSTAT.
W2
GCR
WH
WH
BL
NOMENCLATURE:
OT - OUTDOOR THERMOSTAT (OPTIONAL)
EHR - EMERGENCY HEAT RELAY (OPTIONAL)
GR
E
BR
BR
RD
WH
YL
OR
BL
BL
YL
AIR HANDLER
C
R
G
W1
W2
Y1
Y2
O
TB
COLOR CODES
RD - RED
YL - YELLOW
BL - BLUE
BR - BROWN
OR - ORANGE
WH - WHITE
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
16
Page 17
WARNING
HIGH VOLTAG E !
DISCO NNECT ALL POWER BEFORE SERVICING.
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO
MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
#18 GA. 7 WIRE
W2
YC
O
RYO
YL
OR
RD
YL
OR
WH
BL
OR
HEAT PUMP UNIT WITH OPTIONA L HEAT KITS O F 15 kW AND ABOVE
NOTES:
1) OUTDOOR THERMOSTAT (OT-1) SHOULD BE THE FIRST
TO CLOSE AND THE LAST TO OPEN.
2) JUMPER W1 AND W2 TOGETHER IF OT-2 IS NOT USED.
3) REMOVE WIRE WHEN USING OUTDOOR THERMOSTAT.
W2
GCR
GR
WH
BL
WH
OR
BR
NOMENCLATURE:
OT - OUTDOOR THERMOSTAT (OPTIONAL)
EHR - EMERGENCY HEAT RELAY (OPTIONAL)
E
BR
RD
GR
YL
RD
WH
RD
BL
OR
AIR HANDLER
C
R
G
WH
W1
W2
Y1
Y2
O
TB
COLOR CODES
RD - RED
YL - YELLOW
BL - BLUE
BR - BROWN
OR - ORANGE
WH - WHITE
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
17
Page 18
WARNING
C
T
P
R
C
P
C
R R
M
L
L
G
T
R
ELECTRONIC BLOWER TIME DELAY RELAY
HIGH VOLTAG E !
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO
MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
DISCO NNECT ALL POWER BEFORE SERVICING.
SYSTEM
TRANSFORME
24 VAC
OPTIONAL
SPEEDU
TSTA
XFMR-
K1
PARK TER M INA
M1
120/240VA
MOTO
B13707-35
XFMR-
WIRING DIAGRA
K1
FOR US E WITH
HEAT KI
SPEEDU
The Electronic Blower Time Delay Relay provides power to the blower motor with a delay of 7
seconds after 24VAC is applied to “G”. After 24VAC is removed from “G”, the blower motor
output is de-energized after a delay of 65 seconds.
Normal Time Delays60Hz50Hz
Turn On Delay7.0 SEC.±1%8.4 SEC. .±1%
Turn Off Delay65.0 SEC.±1% 78.0 SEC. .±1%
N E UTRA
Field test mode: Shorting the “speedup” quick connect to “C” decrease times as follows:
Speedup Time s60Hz50Hz
Turn On Delay3.0 SEC.±1%3.6 SEC. .±1%
Turn Off Delay5.0 SEC.±1%6.0 SEC. .±1%
Field test mode is cancelled when the “speedup” quick connect to “C” short is removed.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
18
Page 19
THIS PAGE LEFT INTENTIONALLY BLANK
19
Page 20
21 Wiring Diagrams
WARNING
ARUF**14**
IF REPLACEMENT OF THE ORIGINAL WIRES
SUPPLIED WITH THIS ASSEMBLY IS NECESSARY
USE WIRE THAT CONFORMS TO THE
NATIONAL ELECTRIC CODE.
NOTES:
1) RED WIRES TO BE ON TRANSFORMER TERMINAL "3" FOR 240 VOLTS
AND ON TERMINAL "2" FOR 208 VOLTS.
2) SEE COMPOSITE WIRING DIAGRAMS IN INSTALLATION INSTRUCTIONS
FOR PROPER LOW VOLTAGE WIRING CONNECTIONS.
3) CONFIRM SPEED TAP SELECTED IS APPROPRIATE FOR APPLICATION.
IF SPEED TAP NEEDS TO BE CHANGED, CONNECT APPROPRIATE
MOTOR WIRE (RED FOR LOW, BLUE FOR MEDIUM, AND BLACK FOR
HIGH SPEED) ON "COM" CONNECTION OF THE EBTDR.
INACTIVE MOTOR WIRES MUST BE CONNECTED TO "M1 OR M2"
ON EBTDR.
4) BROWN AND WHITE WIRES ARE USED WITH HEAT KITS ON LY.
5) EBTDR HAS A 7 SECOND ON DELAY WHEN "G" IS ENERGIZED
AND A 65 SECOND OFF DELAY WHEN "G" IS DE-ENERGIZED.
6) LOW VOLTAGE FIELD WIRING TO BE N.E.C CLASS 2 WIRES.
SEE NOTES 2 & 6
WH
BL
RD GR
BR
GR
RD
G
BL
COPPER POWER SUPPLY
USE MIN. 75C FIELD WIRE
R
XFMR-R
RD
XFMR-C
C
SPEEDUP
BL
(SEE RATING PLATE)
THREE SPEED MOTOR WIRING
(SELECT MODELS ONLY)
HIGH VOLTAG E !
DISCO NNECT ALL POWER BEFORE SERVICING.
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO
MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
TERMINAL BLOCK SHOWN
FOR 50HZ MODELS ONLY
SR
BR
WH
SEE NOTE 5
EBTDR
NO
K1
COM
K1
NC
M1
M2
BK
NOTE 3
SEE NOTE 3
SEE
PLF
PLM
RD
PU
(COM) RD
(M2)
(M1)
(TR 1)
PU
L1
L2
RD
BK
2
3
1
23
1
PU
BK
RD
BK
PU
RD
C
LOW
BL
MEDIUM
BK
HIGH
PU
BR
3 SPEED
RC
GRD
12
5
BL
EM
4
4
BL
24V
EQUIPMENT GROUND
USE COPPER WIRE
567
5WH67
BR
NOTE 4
RD
SEE NOTE 1
3
240
TR
4
BL
RD
RD
RC
BR
BR
SEE
89
89
PU
BK
EM
EBTDR
BK
RD
YL
BL
EM
RC
SR
R
EBTDR
CO
BLACK
RED
YELLOW
BLUE
COMPONENT
L1
PLF
1
PLM
1
RC
1
TR
R
RD
L
OR COD
EVAPORATOR MOTOR
RUN CAPACITOR
STRAIN RELIEF
RELAY
ELECTRONIC BLOWER
TIME DELAY RELAY
E
GR
PU
BR
CODE
4
24V
WH6BR
GREEN
PURPLE
BROWN
WHITEWH
2
EM
208/240
VOLTS
3
5
5
M1
HI
M2
LO
SEE NOTE 1
4
PLF
W
FACTORY WIRING
HIGH VOLTAGE
LOW VOLTAGE
FIELD WIRING
HIGH VOLTAGE
LOW VOLTAGE
TR
PLF
PLM
FL
TL
IRING
L2
2
PLF
2
PLM
3
NO
NC
EBTDR
COM
GC
EBTDR
BL
GR
CODE
TRANSFORMER
FEMALE PLUG CONNECTOR
MALE PLUG CONNECTOR
FUSE LINK
THERMAL LIMIT
0140A00242-A
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
20
Page 21
Wiring Diagrams
WARNING
ASPT**14**
&
6
S
E
T
E
2
E
O
S
N
2
4
5
3
H
D
1
2
O
Y
1
W
Y
2
W
G
1
C
R
D
R
R
G
L
B
r
K
B
D
R
o
H
W
IF REPLACEMENT OF THE ORIGINAL WIRES
SUPPLIED WITH THIS ASSEMBLY IS NECESSARY,
USE WIRE THAT CONFORMS TO THE NATIONAL
ELECTRIC CODE.
NOTES:
1. RED WIRES TO BE ON TRANSFORMER TERMINAL "3" FOR 240 VOLTS AND ON
TERMINAL "2" FOR 208 VOLTS.
2. SEE COMPLETE WIRING DIAGRAMS IN INSTALLATION INSTRUCTIONS FOR
PROPER LOW VOLTAGE WIRING CONNECTIONS.
3. CONFIRM SPEED TAP SELECTION IS APPROPRIATE FOR APPLICATION. IF
SPEED TAP NEEDS TO BE CHANGED, CONNECT PURPLE WIRE FROM TERMINAL
4 OF CR RELAY TO APPROPRIATE TAP AT TB
4. BROWN AND WHITE WIRES ARE USED FOR HEAT KITS ONLY.
5. FUSE: 3A, 250V, 3AG CARTRIDGE FUSE.
6. LOW VOLTAGE FIELD WIRING TO BE N.E.C CLASS 2 WIRES.
R
B
W
H
R
C
D
R
4
R
G
A
B
D
r
o
K
B
R
COPPER POWER SUPPLY
(USE RATING PLATE)
USE MIN. 75 C FIELD WIRE
7
1
B
L
HIGH VOLTAG E !
DISCO NNECT ALL POWER BEFORE SERVICING.
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO
MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
D
R
G
L
1
L
2
3
2
1
L
F
P
1
L
M
P
K
B
U
P
W
H
D
R
L
B
4
2
3
4
B
D
R
K
B
K
B
123
C
5
L
B
D
o
R
r
B
I
U
P
Q
E
E
S
U
6
5
6
5
W
H
R
B
L
D
R
SEE
NOTE 1
2
4
0
R
T
4
2
V
4
L
B
L
B
E
S
F
U
R
L
E
D
O
H
(
I
T
N
P
O
O
K
B
D
R
D
R
2
R
G
1
ALTERNATE HEAT RELAY
D
N
U
O
R
M
T
N
G
E
W
I
E
R
R
E
P
P
O
C
9
8
7
9
7
8
SEE
NOTE 4
U
P
W
H
)
L
A
B
K
L
Y
R
R
B
O
4
3
5
2
1
M
E
G
N
L
C
L
U
P
4
H
W
5
3
L
B
L
B
L1
1
1
FUSE
HOLDER
(OPTIONAL)
COMPONENT CODE
CR CONTROL RELAY
EM
FL
PLF
PLM
R
TB
TR
TL
PLF
PLM
EVAPORATOR MOTOR
FUSE LINK
FEMALE PLUG CONNECTOR
MALE PLUG CONNECTOR
RELAY
TERMINAL BOARD
TRANSFORMER
THERMAL LIMIT
208/240 VOLTS
EM
LGN
5
4
6
5
W2R
SEE NOTE 1
B
PLM
O
Y21DH 32
1
23
TR
4
24V
W1
C G
L2
2
PLF
2
PLM
1
4
A
5
4Y1
7
CR
1
2
EM
3
4
C
5
5
2
1
3
4
CR
ALTERNATE HEAT RELAY
WIRING CO
FACTORY WIRING
HIGH VOLTAGE
LOW VOLTAGE
FIELD WIRING
HIGH VOLTAGE
LOW VOLTAGE
DE
COLOR CODE
BK
BLACK
RD
RED
YELLOW
BLYLBLUE
GREEN
GR
PU
PURPLE
BR
BROWN
WHITE
WH
0140A00243-A
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
21
Page 22
WARNING
3-Phase Heat Kit
HIGH VOLTAG E !
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO
MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
DISCO NNECT ALL POWER BEFORE SERVICING.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
22
Page 23
AIR CONDITIONING AND HEAT PUMP HOMEOWNER’SROUTINE MAINTENANCE RECOMMENDATIONS
We strongly recommend a bi-annual maintenance checkup be performed before the heating and cooling seasons begin by a qualified servicer.
REPLACE OR CLEAN FILTER
IMPORTANT NOTE: Never operate unit without a filter installed as dust and lint will build up on internal parts resulting in loss of efficiency,
equipment damage and possible fire.
An indoor air filter must be used with your comfort system. A properly maintained filter will keep the indoor coil of your comfort system clean.
A dirty coil could cause poor operation and/or severe equipment damage.
Your air filter or filters could be located in your furnace, in a blower unit, or in “filter grilles” in your ceiling or walls. The installer of your air
conditioner or heat pump can tell you where your filter(s) are, and how to clean or replace them.
Check your filter(s) at least once a month. When they are dirty, replace or clean as required. Disposable type filters should be replaced.
Reusable type filters may be cleaned.
You may want to ask your dealer about high efficiency filters. High efficiency filters are available in both electronic and non-electronic types.
These filters can do a better job of catching small airborne particles.
COMPRESSOR
The compressor motor is hermetically sealed and does not require additional oiling.
MOTORS
Indoor and outdoor fan motors are permanently lubricated and do not
require additional oiling.
This unit is equipped with an aluminum tube evaporator coil. The safest
way to clean the evaporator coil is to simply flush the coil with water.
This cleaning practice remains as the recommended cleaning method for both copper tube and aluminum tube residential cooling coils.
An alternate cleaning method is to use one of the products listed below to clean the coils. The cleaners listed below are the only agents
deemed safe and approved for use to clean round tube aluminum coils.
Trade Name:Part/ProductManufacturer
EVAP-Green4191-08Nu-Calgon
Extreme Simply Green
Aircraft Precision Cleaner13406Sunshine Makers, Inc.
NOTE: Ensure coils are rinsed well after use of any chemical cleaners.
CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY)
Air must be able to flow through the outdoor unit of your comfort system.
Do not construct a fence near the unit or build a deck or patio over the
unit without first discussing your plans with your dealer or other qualified servicer. Restricted airflow could lead to poor operation and/or severe equipment damage.
Likewise, it is important to keep the outdoor coil clean. Dirt, leaves, or
debris could also restrict the airflow. If cleaning of the outdoor coil becomes necessary, hire a qualified servicer. Inexperienced people could
easily puncture the tubing in the coil. Even a small hole in the tubing
could eventually cause a large loss of refrigerant. Loss of refrigerant can
cause poor operation and/or severe equipment damage.
Do not use a condensing unit cover to “protect” the outdoor unit during
the winter, unless you first discuss it with your dealer. Any cover used must include “breathable” fabric to avoid moisture buildup.
BEFORE CALLING YOUR SERVICER
•
Check the thermostat to confirm that it is properly set.
Wait 15 minutes. Some devices in the outdoor unit or in programmable thermostats will prevent compressor operation for awhile, and
•
then reset automatically. Also, some power companies will install devices which shut off air conditioners for several minutes on hot
days. If you wait several minutes, the unit may begin operation on its own.
Check the electrical panel for tripped circuit breakers or failed fuses. Reset the circuit breakers or replace fuses as necessary.
•
Check the disconnect switch near the indoor furnace or blower to confirm that it is closed.
•
•
Check for obstructions on the outdoor unit . Confirm that it has not been covered on the sides or the top. Remove any obstruction that
can be safely removed. If the unit is covered with dirt or debris, call a qualified servicer to clean it.
Check for blockage of the indoor air inlets and outlets. Confirm that they are open and have not been blocked by objects (rugs, curtains
•
or furniture).
Check the filter. If it is dirty, clean or replace it.
•
Listen for any unusual noise(s), other than normal operating noise, that might be coming from the outdoor unit. If you hear unusual
•
noise(s) coming from the unit, call a qualified servicer.
SPLIT SYSTEMS
TO
AVOID THE RISK OF EQUIPMENT DAMAGE OR FIRE, INSTALL
THE
SAME AMPERAGE BREAKER OR FUSE AS YOU ARE
REPLACING
AGAIN
TO
CORRECT THE PROBLEM
F YOU REPEATEDLY RESET THE BREAKER OR REPLACE
I
THE
FUSE WITHOUT HAVING THE PROBLEM CORRECTED
YOU RUN THE RISK OF SEVERE EQUIPMENT DAMAGE
23
. IF
WITHIN THIRTY DAYS, CONTACT A QUALIFIED SERVICER
THE CIRCUIT BREAKER OR FUSE SHOULD OPEN
.
,
.
Page 24
NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE
Visit our website at www.daikincomfort.com, www.goodmanmfg.com or www.amana-hac.com for information on:
•Products
• Warranties
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.