Altronix WayPoint102 DC Outdoor Power Supply/Charger provides 12VDC and is designed to be conveniently
LGN
NC C NO NC C NO
BAT FAILAC FAIL
--- DC +
AC
AC1
DC
--- BAT +
+ AUX –
enable
disable
1 min.
2 hr.
AC DELAY SHUTDOWN
TRIGGER EOL
SUPERVISED
NO GND
RESET
O
N
5A 250V
located where power is required.
Specifications:
Overview:
Input:
• Input: 120VAC, 60Hz, 3.5A.
• Input fuse rating: 5A/250V.
Output:
• 12VDC @ 10A maximum supply current.
• Auxiliary power-limited output rated @ 1A
(unswitched).
• Filtered and electronically regulated output.
• Thermal overload and short circuit protection.
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• Maximum charge current 1.54A.
• Automatic switch over to stand-by battery.
Output Disconnect:
• Supervised output disconnect (latching or non latching) 10K EOL resistor. Operates on a normally
open (NO) or normally closed (NC) trigger.
Supervision:
• AC fail supervision (form “C” contacts).
• Battery fail & presence supervision
(form “C” contacts).
• Low power shutdown. Shuts down DC output
terminals if battery voltage drops below 71-73%.
Prevents deep battery discharge.
Visual Indicators:
• Green AC Power LED indicates 120VAC present.
• AC input and DC output LED indicators.
Environmental:
• Operating Ambient Temperature:
– 40°C to 60°C (– 40°F to 140ºF).
• Relative Humidity: 85%, +/– 5%
• Storage Temperature:
– 40ºC to 75ºC (– 40ºF to 167ºF).
• Operating Altitude: – 304.8 to 2,000m.
Optional Accessories:
• PMK1 Pole Mount Kit
simplifies installation of outdoor units.
• LINQ2 Network Communication Module
provides remote supervision, control,
and monitoring over LAN/WAN.
Enclosure:
• NEMA 4/4X, IP66-11 Rated enclosure for
outdoor use.
• Enclosure Dimensions (H x W x D approx.):
13.31” x 11.31” x 5.59”
(338.1 mm x 287.3 mm x 142 mm).
• Enclosure accommodates up to two (2)
12VDC/7AH batteries.
Unit shall be installed in accordance with The National Electrical Code and all applicable Local Regulations.
Installation Instructions:
1. Remove backplane from enclosure prior to mounting (do not discard hardware).
2. Mark and drill desired inlets on the enclosure to facilitate wiring (Fig. 2, pg. 4).
Note: Inlets for conduit fittings should only be made on the bottom of the enclosure.
UL Listed NEMA type 4X rated conduit connector/hubs shall be used for the appropriate size inlets.
3. Mount unit in the desired location. For wall mounting refer to Fig. 4, pg. 7.
For pole mounting installation refer to pg. 7 - Pole Mounting Using Optional Pole Mount Kit PMK1.
4. Mount backplane to enclosure with hardware.
5. To facilitate wire entry utilize weather-tight NEMA 4 rated connectors, bushings, and cable.
6. Connect unswitched AC power (120VAC, 60 Hz) to terminals marked [L, N] (Fig. 3, pg. 5).
Green branch wire connects to earth (safety) ground lug .
Wire gauge range of connectors is 14 AWG to 11 AWG (1.6mm to 2.5mm diameter).
7. Measure output voltage before connecting devices. This helps avoiding potential damage.
8. Connect devices to be powered to terminals marked [– DC +] (Fig. 1h, pg. 4).
For auxiliary device connection this output will not be affected by Low Power Disconnect or
Output Disconnect. Connect device to terminals marked [+ AUX –] (Fig. 1f, pg. 4).
9. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result
in the loss of the output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel
type. Connect battery to terminals marked [– BAT +] (Fig. 1g, pg. 4). Use batteries - Casil CL1270 (12V/7AH)
batteries or UL recognized BAZR2 batteries of an appropriate rating.
10. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1b, pg. 4) supervisory
relay outputs.
11. To delay AC reporting for 2 hrs. set DIP switch [AC Delay] to OFF position (Fig. 1c, pg. 4).
To delay AC reporting for 1 min. set DIP switch [AC Delay] to ON position (Fig. 1c, pg. 4).
12. To enable Output Disconnect set DIP switch [Shutdown] to ON position (Fig. 1c, pg. 4).
To disable Output Disconnect set DIP switch [Shutdown] to OFF position (Fig. 1c, pg. 4).
13. Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger terminals
will cause [DC] output to shutdown (Fig. 1d, pg. 4).
- 2 - WayPoint102

14. Place a jumper for non-latching output. A momentary short on these terminals resets output latching
[Trigger EOL Shutdown] (Fig. 1e, pg. 4).
15. Upon completion of wiring secure enclosure door with latches and optional lock.
WARNING: When installing in a non-restricted service area use lock or other fastened means on door
latches. This installation should be made by qualified service personnel and should conform to the
National Electrical Code and all local codes.
LED Diagnostics:
Red (DC) Green (AC/AC1) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery supplying power.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Terminal Identification:
Terminal
Legend
L, G, N
– DC +
(Fig. 1h, pg. 4)
Trigger EOL
Supervised
NO, GND
RESET
+ AUX –
AC Fail
NC, C, NO
Function/Description
Connect 120VAC 60Hz to these terminals: L to hot, N to neutral(non power-limited)
(Fig. 1a, pg. 4).
12VDC @ 10A continuous output (Non power-limited output).
Trigger inputs can be normally open, normally closed from an output circuit
(power-limited input) (Fig. 1d, pg. 4).
Trigger input latching or non-latching (power-limited) (Fig. 1c, pg. 4).
Auxiliary power-limited output rated @ 1A (unswitched) (power-limited output)
(Fig. 1f, pg. 4).
Indicates loss of AC power, e.g. connect to audible device or alarm panel.
Relay normally energized when AC power is present.
Contact rating 1A @ 30VDC (power-limited) (Fig. 1b, pg. 4).
Bat Fail
NC, C, NO
– BAT +
WayPoint102 - 3 -
Indicates low battery condition, e.g. connect to alarm panel.
Relay normally energized when DC power is present. Contact rating 1A @ 30VDC.
A removed battery is reported within 5 minutes.
Battery reconnection is reported within 1 minute (power-limited) (Fig. 1b, pg. 4).
Stand-by battery connections. Maximum charge current 1.54A (non power-limited)
(Fig. 1g, pg. 4).

Fig. 3 - WayPoint102
5A 250V
LGN
CAUTION
HIGH VOLTAGE
AC1
NC C NO NC C NO
--- DC +
--- BAT +
AC DELAY SHUTDOWN
BAT FAILAC FAIL
O
N
AC
DC
enable
1 min.
NO GND
TRIGGER EOL
disable
2 hr.
SUPERVISED
+ AUX –
RESET
The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user
to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may
be of sufficient magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of
important operating and maintenance (servicing) instructions in the literature accompanying the
appliance.
CAUTION: To reduce the risk of electric shock do not open
enclosure. There are no user serviceable parts inside.
Refer servicing to qualified service personnel.
WayPoint102 - 5 -

Wall Mount Installation
1- Place unit at desired location and secure with mounting
screws (not included) (Fig. 4, pg. 7).
Fig. 4
Pole Mounting Using Optional Pole Mount Kit PMK1 (not included):
This installation should be made by qualified service personnel. This product contains no serviceable parts.
PMK1 is intended for use with Altronix outdoor rated power supplies or accessories housed in WP1, WP2, WP3
and WP4 enclosures. Brackets are designed for use with the Wormgear Quick Release Straps (two included).
1. Thread one (1) wormgear quick release strap through the slots on the back of a mounting bracket (Fig. 5, pg. 7).
2. Once the desired height of the top Pole Mount bracket is achieved, tighten the straps down by sliding open
end of the strap through the locking mechanism on the strap, then tighten the screw with
flat head screwdriver or 5/16” hex socket driver (Fig. 6, pg. 7 and Fig. 8, pg. 7).
Fig. 7
Fig. 9a
5” (127mm) square pole
Fig. 8
Fig. 6
Fig. 9
2” to 8”(50.8mm to 203.2mm)
diameter round pole
Fig. 5
3. Attach the bottom bracket to the enclosure by inserting bolts through the flange of the enclosure and into the
bracket, tightening bolts with a 7/16” hex socket (Fig. 7, pg. 7).
4. Thread the second wormgear quick release strap through the slots on the back of the bottom mounting bracket
(Fig. 5, pg. 7).
5. Mount enclosure onto the top bracket by inserting bolts through flange of the enclosure and into the bracket,
tightening bolts with a 7/16” hex socket (Fig. 7, pg. 7).
6. Tighten the straps of the bottom bracket down by sliding the open end of the strap through the locking
mechanism on the strap, then tighten screw with flat head screwdriver or 5/16” hex socket driver
(Fig. 5, pg. 7).
7. Clip excess straps.
WayPoint102 - 7 -

8.25” (209.6mm)
10.75” (273.1mm)
3.96”
(100.6mm)
Enclosure Dimensions (H x W x D approx.):
13.31” x 11.31” x 5.59” (338.1mm x 287.3mm x 142mm)
10.25”
(260.4mm)
10-32 X 0.25” (6.4mm)
BRASS INSERT (X2)
10.00”
(254mm)
12.00”
(304.8mm)
13.50”
(342.9mm)
12.75”
(323.9mm)
10-32 X 0.375” (9.6mm)
BRASS INSERT (X4)
PADLOCK LATCH ATTACHED WITH RIVETS
1.61”
(40.9mm)
11.31”
13.31”
(338.1mm)
(287.3mm)
STAINLESS STEEL PIANO HINGE
(Ø 0.375” (9.5mm) PADLOCK EYE).
5.59”
(142mm)
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty | Made in U.S.A.
IIWayPoint102 H30R
- 8 - WayPoint102
Ø 0.32 (8.1mm) MOUNTING HOLE
TYP. 4 PLACES
8.00” (203.2mm)
MEMBER