CCTV Isolated Rack Mount
Power Supplies
Installation Guide
Models Include:
Vertiline8i Vertiline8Di
- 24VAC or 28VAC @ 8A - 24VAC or 28VAC @ 8A
- Eight (8) fuse protected electronically - Eight (8) PTC protected electronically
isolated outputs isolated outputs
Vertiline16i Vertiline16Di
- 24VAC or 28VAC @ 16A - 24VAC or 28VAC @ 16A
- Sixteen (16) fuse protected electronically - Sixteen (16) PTC protected electronically
isolated outputs isolated outputs
More than just power.
Rev. 031808
TM
Overview:
Altronix Vertiline AC Isolated CCTV Rack Mount Power Supplies provide 8 or 16 camera channels in a space saving 1U
EIA 19” rack mount chassis which may be rack, wall or shelf mounted. The units feature individually selectable 24VAC
and/or 28VAC power outputs.
Specifications:
Input:
• Selectable 115VAC 60 Hz or 230VAC 50/60 Hz input.
Output:
• Eight (8) or sixteen (16) individually selectable
24VAC or 28VAC power outputs with OFF position.
• Maximum 1A per output.
• Individual electronically isolated outputs.
• Eight (8) or sixteen (16) power LED indicators.
• External automotive blade fuses or PTC protected outputs.
• Surge suppression.
Features:
• Illuminated power disconnect circuit breaker with
manual reset.
• Removable terminal blocks with locking screw flange.
• Ease of installation saves time and eliminates costly labor.
Mechanical:
• Units can be rack, wall or shelf mounted.
• Modular 1U standard EIA 19” rack mount chassis
• Enclosure Dimensions (H x W x D approx.):
1.625” x 19.125” x 8.5” (41.3mm x 486mm x 216mm).
Eight (8) and Sixteen (16) Output Rack Mount Configuration Reference Chart:
Altronix
Model
Output
Voltage (VAC)
Total Output
Current (Power)
Number of Outputs
Output Protection
Class 2 Rated
Power- Limited
Output Protection
Current
(max. per output)
Fuse Rating
115VAC 60Hz Input
Current
230VAC 50/60Hz
Input Current
Number
Vertiline8i
Vertiline8Di
Vertiline16i
Vertiline16Di
24VAC or
28VAC
24VAC or
28VAC
24VAC or
28VAC
24VAC or
28VAC
8A 8
8A 8
16A 16
16A 16
Fused -- 3A 3A
-- PTC 2.5A --
Fused -- 3A 3A
-- PTC 2.5A --
2.5A 1.5A
5A 2.5A
Agency Listings
UL Listed for Commercial
CCTV Equipment (UL 2044).
CUL Listed - CSA Standard
C22.2 No.1-04,
Audio, Video and Similar
UL Listings and
File Numbers
Equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to the National
Electrical Code and all local codes.
Installation Instructions:
1. Set the input voltage selector switch located on the left side of the Vertiline unit for 115VAC or
230VAC operation (Fig. 1c, pg. 4).
2. Attach mounting brackets to Vertiline unit for rack or wall mount installation (Figs. 4-5, pg. 7). Affix rubber pads to
Vertiline for shelf installation (Fig. 6, pg. 7).
3. Secure the unit in a rack, mount unit to a wall or place unit on a shelf as desired (unit should be spaced at least
3” from any video monitors).When installing the unit in a rack, allow for one half of a U spacing above the unit
for ventilation.
4. Plug the grounded AC line cord (included) into the IEC 320 connector of the Vertiline unit (Fig. 1f, pg. 4).
Insert the plug end of the line cord into a grounded AC receptacle.
5. Set illuminated master power disconnect circuit breaker to the (ON) position (Fig. 3, pg. 6).
6. Select 24VAC or 28VAC power output for cameras 1-8 for Vertiline8i and Vertiline8Di or cameras 1-16 for
Vertiline16i and Vertiline16Di with the corresponding voltage adjustment switches (Fig. 1b, pg. 4).
7. Measure output voltage before connecting cameras. This helps avoiding potential damage.
All terminals with common suffix (P) “1P, 2P ...” are the same polarity.
8. Set illuminated master power disconnect circuit breaker to the (OFF) position (Fig. 3, pg. 6).
- 2 - Vertiline8i/Vertiline16i
9. Connect the power outputs of the terminals marked [1P & 1N] to the power inputs of camera 1 (Fig. 2, pg. 5).
Repeat this step for each additional camera (Outputs 2-16). After wiring is completed, insert terminal block into the
corresponding connector and secure by tightening the screws.
10. Upon completion of wiring, set illuminated master power disconnect circuit breaker to the
ON (RESET) position (Fig. 3, pg. 6).
11. The power LEDs (Green) on the faceplate for Outputs 1-8 for Vertiline8i and Vertiline8Di or Outputs 1-16 for
Vertiline16i and Vertiline16Di will illuminate when AC power is present (Fig. 1a, pg. 4). If all of the LEDs are OFF,
there may be a complete loss of supply power to the Vertiline unit or the illuminated master power disconnect circuit
breaker is in the OFF position.
To restore the power output for Vertiline8i or Vertiline16i:
1- Switch corresponding output voltage switch to the OFF position (Fig. 1b, pg. 4).
2- Eliminate the trouble condition.
3- Replace the corresponding automotive blade fuse.
Automotive
Blade Fuse
Replace fuses with same type and rating:
Output fuses are rated @ 3A for all models.
4- Switch output voltage switch to the 24VAC or 28VAC position as desired (Fig. 1b, pg. 4).
To restore the power output for Vertiline8Di or Vertiline16Di:
1- Switch corresponding output voltage switch to the OFF position (Fig. 1b, pg. 4).
2- Eliminate the trouble condition.
3- Allow 1 minute for PTC to cool off.
4- Switch output voltage switch to the 24VAC or 28VAC position as desired (Fig. 1b, pg. 4).
Vertiline8i/Vertiline16i - 3 -