Altronix VertiLine8C, VertiLine83CD, VertiLine83C Installation Guide

CCTV Rack Mount Power Supplies
Installation Guide
Models Include:
Vertiline8C Vertiline8CD
- 24VAC or 28VAC @ 5A - 24VAC or 28VAC @ 5A
Vertiline83C Vertiline83CD
- 24VAC or 28VAC @ 10A - 24VAC or 28VAC @ 10A
Rev. 031808
More than just power.
TM
Overview:
Altronix Vertiline CCTV Rack Mount Power Supplies provide 8 power outputs in a space saving 1U EIA 19” rack mount chassis which may be rack, wall or shelf mounted. The units feature individually selectable 24VAC and/or 28VAC power outputs with surge suppression. Vertiline CCTV Rack Mount Power Supplies are also available in sixteen (16) and twenty­four (24) output models with various power ratings.
Specifications:
Input:
• 115VAC 60 Hz.
Output:
• Eight (8) individually selectable 24VAC or 28VAC power outputs with OFF position.
• 24VAC or 28VAC @ 5A max. total
(0.625A per device, 3A max.).
• Eight (8) external blade fuse or PTC protected outputs.
• Surge suppression.
Features:
• Eight (8) power LED indicators.
• Illuminated master power disconnect circuit breaker with manual reset.
• IEC 320 - 3-wire grounded line cord (detachable).
• Removable terminal blocks with locking screw flange.
Mechanical:
• Units can be rack, wall or shelf mounted.
• Modular 1U standard EIA 19” rack mount chassis.
• Enclosure Dimensions (H x W x D approx.):
1.625” x 19.125” x 8.5” (41.3mm x 486mm x 216mm).
Eight (8) Output Rack Mount Configuration Reference Chart:
Altronix Model
Output
Voltage (VAC)
Total Output
Current (Power)
Number of Outputs
Output Protection
Class 2 Rated
Power-Limited
Output Protection
Current
(max. per output)
Fuse Rating
Main Fuse Rating
115VAC 60Hz
Input Current
230VAC 50/60Hz
Number
Vertiline8C
Vertiline8CD
Vertiline83C
Vertiline83CD
24VAC or
28VAC
24VAC or
28VAC
24VAC or
28VAC
24VAC or
28VAC
5A 8
5A 8
10A 8
10A 8
Input Current
Fused -- 3A 3A
10A 1.5A 0.8A
-- PTC 2.5A --
Fused -- 3A 3A
15A 3A 1.5A
-- PTC 2.5A --
Agency Listings
UL Listed for
Commercial
CCTV Equipment
(UL 2044).
CUL Listed - CSA
Standard
C22.2 No.1-04,
Audio, Video and
Similar Equipment.
UL Listings and
File Numbers
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to the National Electrical Code and all local codes.
Installation Instructions:
1. Attach mounting brackets to Vertiline unit for rack or wall mount installation (Figs. 4-5, pg. 7). Affix rubber pads to Vertiline for shelf installation (Fig. 6, pg. 7).
2. Secure the unit in a rack, mount unit to a wall or place unit on a shelf as desired (unit should be spaced at least 3” from any video monitors). When installing the unit in a rack allow for one half of a U spacing above the unit for ventilation.
3. Plug the grounded AC line cord (included) into the IEC 320 connector of the Vertiline unit (Fig. 1f, pg. 4). Insert the plug end of the line cord into a grounded AC receptacle.
4. Set illuminated master power disconnect circuit breaker to the (ON) position (Fig. 3, pg. 6).
5. Select 24VAC or 28VAC power output for cameras 1-8 with the corresponding voltage adjustment switches (Fig. 1b, pg. 4).
6. Measure output voltage before connecting cameras. This helps avoiding potential damage. All terminals with common suffix (P) “1P, 2P ...” are the same polarity.
7. Set illuminated master power disconnect circuit breaker to the (OFF) position (Fig. 3, pg. 6).
- 2 - Vertiline8C
8. Connect the power outputs of terminals marked [1P & 1N] to the power inputs of camera 1 (Fig. 2, pg. 5). Repeat this step for each additional camera (Outputs 2-8). After wiring is completed insert terminal block into the corresponding connector and secure by tightening the screws.
9. Upon completion of wiring, set illuminated master power disconnect circuit breaker to the ON (RESET) position (Fig. 3, pg. 6).
10. The power LEDs (Green) on the faceplate for Outputs 1-8 will illuminate when AC power is present (Fig. 1a, pg. 4). If any of these LEDs are off, a loss of AC power output may be due to a blown fuse or a tripped PTC caused by a short circuit or overload condition. If all of the LEDs are OFF there may be a complete loss of supply power to the Vertiline unit or the illuminated master power disconnect circuit breaker is in the OFF position or the main fuse 1-8 is blown (Fig. 1c, pg. 4).* To restore the power output for Vertiline8C or Vertiline83C: 1- Switch corresponding output voltage switch to the OFF position (Fig. 1b, pg. 4). 2- Eliminate the trouble condition. 3- Replace the corresponding automotive blade fuse.* 4- Switch output voltage switch to the 24VAC or 28VAC position as desired (Fig. 1b, pg. 4). To restore the power output for Vertiline8CD or Vertiline83CD: 1- Switch corresponding output voltage switch to the OFF position (Fig. 1b, pg. 4). 2- Eliminate the trouble condition. 3- Allow 1 minute for PTC to cool off. 4- Switch output voltage switch to the 24VAC or 28VAC position as desired (Fig. 1b, pg. 4).
*Note: Replace fuses with same type and rating:
Output fuses are rated @ 3A for all models. Main fuse ratings: 10A for Vertiline8C and Vertiline8CD.
Automotive Blade Fuse
15A for Vertiline83C and Vertiline83CD.
Vertiline8C - 3 -
AC POWER
1f - IEC 320
Connector:
115VAC 60Hz
(grounded line
cord included).
AC POWER
1b - Output voltage switches:
Selects 24VAC or 28VAC
or OFF for each output.
1a - LED(s) 1-8:
Power LED indicators.
78
6
OFF
28VAC
34 5
2
1
12345678
24VAC
P
N P
N P
N P
N
P
N P
N P
N P
N
1-8
Main Fuse
1e - Output Fuses:
Automotive
blade fuses.
1d - Power
Outputs:
1c - Main Fuse:
Protects the
transformer
24VAC or
28VAC.
against overload.
P
12345678
N P
N P
N P
N
P
N P
N P
N P
N
1-8
Main Fuse
RESET
Vertiline8C, Vertiline8CD,
Vertiline83C or Vertiline83CD (front)
OFF
Vertiline8C or Vertiline83C (rear)
Vertiline8CD or Vertiline83CD (rear)
Vertiline8CD and Vertiline83CD do not have output fuses on the rear of the rack mount
Fig. 1
- 4 - Vertiline8C
chassis. The output PTCs are located on the inside of the rack mount chassis.
AC POWER
78
6
Typical Hookup:
34 5
12345678
OFF
28VAC
24VAC
P
N P
N P
N P
N
P
N P
N P
N P
N
1-8
Main Fuse
2
1
Fig. 2
RESET
OFF
Vertiline8C - 5 -
The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure. There are no user serviceable parts inside. Refer servicing to qualified service personnel.
1U EIA 19” Rack Mount Chassis Mechanical Drawing & Dimensions (H x W x D):
1.625” x 19.125” x 8.5” (41.3mm x 486mm x 216mm)
REAR
5678 1234
P
NPNPNPN
P
1.625"
41.3mm
Main Fuse
1-8
NPNPNPN
TOP & BOTTOM
17.625"
447.7mm
AC POWER
8.5"
216mm
0.75"
19.05mm
RESET
OFF
(ON)
FRONT
1
34 5
2
28VAC
OFF
24VAC
Fig. 3
Power switch with built-in circuit breaker: OFF position - Switch not Illuminated. Outputs not powered. RESET (ON) position - Switch illuminated. Outputs powered. Circuit breaker tripped - Switch not Illuminated. Power LEDs on faceplate are not illuminated. Outputs not powered. To reset circuit breaker set power switch to the ON (RESET) position (Fig. 3, pg. 6).
6
78
19.125" 486mm
- 6 - Vertiline8C
Mounting Options:
Rack Mount Installation
1- Remove factory installed screws from both sides of rack chassis (Fig. 4a). 2- Install mounting brackets (A) on the left and right side of rack chassis using the two (2) flat head screws (B) (included) (Fig. 4b). 3- Place unit into desired EIA 19” rack position and secure with mounting screws (not included) (Fig. 4c).
Fig. 4
Fig. 4a
Top
Fig. 4b
Top
Fig. 4c
Top
Front
Front Left
B
Left
Front Left
Remove
A
Wall Mount Installation
1- Install mounting brackets (A) on the left and right side of rack chassis using two (2) flat head screws (B) (included) (Fig. 5a). 2- Place unit at desired location and secure with mounting screws (not included) (Fig. 5b).
Caution: It is necessary to make sure mounting screws are securely fastened to a beam when installing.
Fig. 5
Fig. 5a
Fig. 5b
B
A
Shelf Installation
1- Position and affix rubber pads (C) (included) at each corner on the bottom of the unit (Fig. 6). 2- Place unit in desired location.
Fig. 6
Left Side
C
Vertiline8C - 7 -
Rubber Pad
Mounting Hardware (Included):
A
Two (2) mounting brackets
Six (6) flat head screws
B
for mounting brackets.
C
Four (4) rubber pads.
Notes:
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com. Lifetime Warranty, Made in U.S.A.
- 8 - Vertiline8C