Altronix VertiLine6D Installation Instructions

Rack Mount Power Supplies
Installation Guide
Models Include:
Vertiline3D
- 12VDC @ 8 amp
- Eight (8) PTC protected outputs
Vertiline6D
- 24VDC @ 8 amp
- Eight (8) PTC protected outputs
Rev. 051909
More than just power.
Overview:
Altronix Vertiline Rack Mount Power Supplies provide eight (8) filtered and electronically regulated power outputs in a space saving 1U EIA 19” rack mount chassis. The units are available with either 12VDC or 24VDC power outputs. Vertiline Rack Mount Power Supplies are also available in sixteen (16) outputs.
VertiLine Specifications:
VertiLine3D:
• Eight (8) 12VDC power outputs.
VertiLine6D:
• Eight (8) 24VDC power outputs.
Common Specifications:
• 115V
AC 60 Hz input.
• Eight (8) power LED indicators.
• PTC protected outputs.
• Filtered and electronically regulated.
• Illuminated power disconnect circuit breaker with manual reset.
• IEC 320 - 3-wire grounded line cord (detachable).
• Removable terminal blocks with locking screw flange.
• Ease of installation saves time and eliminates costly labor.
• Compact 1U rack mount chassis.
• Fits standard EIA 19” rack.
• Units can be rack, wall or shelf mounted.
Eight (8) Output Rack Mount Configuration Reference Chart:
Altronix Model Number
Vertiline3D
Vertiline6D
Output Voltage (VAC)
12VDC 8 amp 8
24VDC 8 amp 8
Total Output Current (Power)
PTC Output Protection
Number of Outputs
PTC 2.5 amp 1.5 amp
PTC 2.5 amp 3 amp
(max. per output)
Current
Input Current
115VAC 60Hz
Agency Listings
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to all local codes and in accordance with the National Electrical Code.
Installation Instructions:
1. Attach mounting brackets to Vertiline unit for desired rack or wall mount installation (Figs. 3-4, pg. 7).
Affix rubber pads to Vertiline for shelf installation (Fig. 5, pg. 7).
2.
Secure the unit into rack, mount unit to wall or place unit on a shelf as desired (unit should be spaced at least 3” from any video monitors). When installing the unit in a rack allow for one half U spacing above the unit for ventilation.
3. Insert and secure removable terminal blocks to unit (Fig. 1e, pg. 4).
4.
Plug the grounded AC line cord (included) into the IEC 320 connector of the Vertiline unit (Fig. 1d, pg. 4). Inser
t the plug end of the line cord into a grounded AC, receptacle.
5. Set illuminated master power disconnect circuit breaker to the (ON) position (Fig. 1c, pg
6. Measure output voltage before connecting devices. This helps avoid potential damage.
7. Set illuminated master power disconnect circuit breaker to the (OFF) position (Fig. 1c, pg. 4).
8.
Connect the power output of terminals marked [+ 1 --- ] to the power input of device (Fig. 1b, pg. 4). Repeat this step for each additional de
9. Upon completion of wiring, set illuminated master power disconnect circuit breaker to the
ON (RESET) position (Fig. 1c, pg. 4).
- 2 - Vertiline3D/VertiLine6D
vice (Outputs 2-8).
. 4).
10. The power LEDs on the faceplate for Outputs 1-8 will illuminate when AC power is present (Fig. 1a, pg. 4).
Note: If an
y of the power LEDs are not illuminated the cause may be due to the following: a. AC mains fail. b. Illuminated master power disconnect circuit breaker is OFF or tripped. c. One (1) or more power output PTCs are tripped due to a short circuit or overload condition.
To reset the PTC:
1. Set illuminated master power disconnect circuit breaker to the (OFF) position (Fig. 1d, pg. 4).
2.
Eliminate the trouble condition (short circuit or overload).
3. Allow 1 minute for PTC to cool off (reset).
4. Set illuminated master power disconnect circuit breaker to the (ON) position (Fig. 1d, pg. 4).
5.
All power LEDs will illuminate indicating power has been restored to all outputs (Fig. 1a, pg. 4).
Vertiline3D/VertiLine6D - 3 -
1e
Block
Removable Terminal
1a 1b 1c
1d
• OFF position Circuit breaker tripped Switch not illuminated.
• RESET (ON) position Switch illuminated.
Fig. 1
Vertiline3D and Vertiline6D (front)
- 4 - Vertiline3D/VertiLine6D
Vertiline3D and Vertiline6D (rear)
1a LED(s) 1-8: Power LED indicators.
1b Power Outputs: 12VDC or 24VDC.
1c Illuminated master power disconnect circuit breaker (switch):
1d IEC 320 Connector: 115VAC 60Hz (grounded line cord included).
1e Removable Terminal Block.
Typical Application Drawing:
12VDC (VertiLine3D)
or 24VDC (VertiLine6D)
Power Outputs to Devices
Fig. 2
Vertiline3D/VertiLine6D - 5 -
1.625"
8.5"
.75"
19.125"
17.625"
(ON)
The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the presence of an insulated “DANGEROUS VOLTAGE” within the products enclosure that may be of sufficient magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.
1U EIA 19” Rack Mount Chassis Mechanical Drawing & Dimensions:
1.625”H x 19.125”W x 8.5”D
CAUTION: To reduce the risk of electric shock do not open enclosure. There are no user ser
viceable parts inside. Refer servicing to qualified service personnel.
REAR
TOP & BOTTOM
FRONT
Illuminated master power disconnect circuit breaker:
OFF position - Switch not Illuminated. Outputs not powered. RESET (ON) position - Switch illuminated. Outputs powered. Circuit breaker tripped - Switch not Illuminated. Power LEDs on faceplate are not illuminated. Outputs not powered. To reset circuit breaker set power switch to the ON (RESET) position.
- 6 - Vertiline3D/VertiLine6D
Chassis Mounting Options:
B
A
C
A
B
C
A
B
Rack Mount Installation
1- Remove factory installed screws from both sides of rack chassis (Fig. 3a). 2- Attach mounting brackets (A) on the left and right side of rack chassis using the
two (2) flat head screws (B) (included) (Fig. 3b).
3-
Install unit into desired EIA 19” rack position and secure with mounting screws (not included) (Fig. 3c).
Fig. 3
Fig. 3a
Top Top
Fig. 3b
Fig. 3c
To
Front
Front Left
Left
Front Left
Remove
Wall Mount Installation
1- Attach mounting brackets (A) on the left and right side of rack chassis using
two (2) flat head screws (B) (included) (Fig. 4a).
2-
Secure unit to wall with appropriate screws/hardware (not included) (Fig. 4b). Caution: It is necessary to make sure mounting screws are securely fastened to a beam when installing.
Fig. 4
Fig. 4a
Fig. 4b
p
Shelf Installation
1- Position and affix rubber pads (C) (included) at each
corner on the bottom of the unit (Fig. 5).
2-
Place unit in desired location.
F
ig. 5
Left Side
Hardware (Included):
Two (2) mounting brackets
Six (6) flat head screws for mounting brackets.
Four (4) rubber pads.
Rubber Pad
Vertiline3D/VertiLine6D - 7 -
Notes:
Altronix is not responsible for any typographical errors.
Altronix Corp. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A. IIVertiline3DSeries E19I
- 8 - Vertiline3D/VertiLine6D
MEMBER
Loading...