Altronix VertiLine Rack Mount Power Supplies provide sixteen (16) filtered and electronically regulated power outputs
in a space saving 1U EIA 19” rack mount chassis. The units are available with either 12VDC or 24VDC power outputs.
Vertiline Rack Mount Power Supplies are also available with eight (8) outputs.
Specifica tions:
Agency Listing:
• CE European Conformity.
Input:
• 115VAC 60 Hz.
Output:
• Filtered and electronically regulated outputs.
VertiLine33D, VertiLine33TD:
• Sixteen (16) PTC protected 12VDC power outputs.
VertiLine63D, VertiLine63TD:
• Sixteen (16) PTC protected 24VDC power outputs.
Features:
• Sixteen (16) power LED indicators.
• Illuminated master power disconnect circuit breaker
with manual reset.
• IEC 320 - 3-wire grounded line cord (detachable).
• Removable terminal blocks with locking screw flange.
Mechanical:
• Units can be rack, wall or shelf mounted.
• Modular 1U standard EIA 19” rack mount chassis.
• Enclosure Dimensions (H x W x D approx.):
1.625” x 19.125” x 8.5” (41.3mm x 486mm x 216mm).
Sixteen (16) Output Rack Mount Configuration Reference Chart:
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This
installation should be made by qualified service personnel and should conform to the National Electrical
Code and all local codes.
Installation Instructions:
1. Attach mounting brackets to Vertiline unit for rack or wall mount installation (Figs. 3-4, pg. 7).
Affix rubber pads to Vertiline for shelf installation (Fig. 5, pg. 7).
2. Secure the unit into rack, mount unit to a wall or place unit on a shelf as desired (unit should be spaced at least 3”
from any video monitors). When installing the unit in a rack allow for one half U spacing above the unit
for ventilation.
3. Insert and secure removable terminal blocks to unit (Fig. 1e, pg. 4).
4. Plug the grounded AC line cord (included) into the IEC 320 connector of the Vertiline unit (Fig. 1d, pg. 4).
Insert the plug end of the line cord into a grounded AC receptacle.
5. Set illuminated master power disconnect circuit breaker to the (ON) position (Fig. 1c, pg. 4).
6. Measure output voltage before connecting cameras/devices. This helps avoiding potential damage.
7. Set illuminated master power disconnect circuit breaker to the (OFF) position (Fig. 1c, pg. 4).
8. Connect the power output of terminals marked [+ 1 --- ] to the power input of device (Fig. 1b, pg. 4).
Repeat this step for each additional device (Outputs 2-16).
9. Upon completion of wiring, set illuminated master power disconnect circuit breaker to the
ON (RESET) position (Fig. 1c, pg. 4).
10. The power LEDs on the faceplate for Outputs 1-8 will illuminate when AC power is present (Fig. 1a, pg. 4).Note: If any of the power LEDs are not illuminated, the cause may be due to the following:
a. AC mains fail.
b. Illuminated master power disconnect circuit breaker is OFF or tripped.
c. One (1) or more power output PTCs are tripped due to a short circuit or overload condition.
To reset the PTC:
1. Set illuminated master power disconnect circuit breaker to the (OFF) position (Fig. 1c, pg. 4).
2. Eliminate the trouble condition (short circuit or overload).
3. Allow 1 minute for PTC to cool off (reset).
4. Set illuminated master power disconnect circuit breaker to the (ON) position (Fig. 1c, pg. 4).
5. All power LEDs will illuminate indicating power has been restored to all outputs (Fig. 1a, pg. 4).
The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the
presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient
magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important
operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure. There are
no user serviceable parts inside. Refer servicing to qualified service personnel.
1U EIA 19” Rack Mount Chassis Mechanical Drawing and Dimensions:
1.625” x 19.125” x 8.5” (41.3mm x 486mm x 216mm)
REAR
1.625"
41.3mm
17.625"
447.7mm
8.5"
216mm
0.75"
19.05mm
TOP & BOTTOM
FRONT
19.125"
486mm
Illuminated master power disconnect circuit breaker:
OFF position - Switch not illuminated. Outputs not powered.
RESET (ON) position - Switch illuminated. Outputs powered.
Circuit breaker tripped - Switch not illuminated. Power LEDs on faceplate
are not illuminated. Outputs not powered.
To reset circuit breaker, set power switch to the ON (RESET) position.
Altronix is not responsible for any typographical errors.