Altronix VertiLine16D Installation Instructions

CCTV Rack Mount Power Supplies
Installation Guide
Models Include:
Vertiline16 Vertiline16D
- 24VAC or 28VAC @ 10 amp - 24VAC or 28VAC @ 10 amp
- Sixteen (16) fuse protected outputs - Sixteen (16) PTC protected outputs
Vertiline166 Vertiline166D
- 24VAC or 28VAC @ 14 amp - 24VAC or 28VAC @ 14 amp
- Sixteen (16) fuse protected outputs - Sixteen (16) PTC protected outputs
More than just power.
TM
Overview:
Altronix Vertiline CCTV Rack Mount Power Supplies provide 16 power outputs in a space saving 1U EIA 19” rack mount chassis which may be rack, wall or shelf mounted. The units feature individually selectable 24VAC and/or 28VAC power outputs with surge suppression. Vertiline CCTV Rack Mount Power Supplies are also available in eight (8) and twenty­four (24) output models with various power ratings.
Specifications:
• Selectab
• Sixteen (16) individually selectable 24VAC or 28VAC power outputs with OFF position.
• Sixteen (16) power LED indicators.
• External blade fuses or PTC protected outputs.
• Surge suppression.
• Illuminated power disconnect circuit breaker with manual reset.
le 115VAC 60 Hz/230VAC 50/60 Hz input.
• IEC 320 - 3-wire grounded line cord (detachable).
• Removable terminal blocks with locking screw flange.
• Ease of installation saves time and eliminates costly labor.
• Compact 1U rack mount chassis.
• Fits standard EIA 19” rack.
• Units can be rack, wall or shelf mounted.
Sixteen (16) Output Rack Mount Configuration Reference Chart:
Altronix Model Number
Vertiline16
Vertiline16D
Vertiline166
Vertiline166D
Voltage (VAC)
Output
24VAC or
28VAC
24VAC or
28VAC
24VAC or
28VAC
24VAC or
28VAC
Total Output Current (Power)
10 amp 16
10 amp 16
14 amp 16
14 amp 16
Number of Outputs
Output Protection
Fused -- 3 amp 3 amp
-- PTC 2.5 amp --
Fused -- 3 amp 3 amp
-- PTC 2.5 amp --
Output Protection
Class 2 Rated Power Limited
(max. per output)
Current
Fuse Rating
10 amp 3 amp 1.6 amp
15 amp 4 amp 2.5 amp
Input Current
Main Fuse Rating
115VAC 60Hz
Input Current
230VAC 50/60Hz
Agency Listings
UL Listed for
CCTV Equipment
Commercial
(UL 2044).
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to all local codes and in accordance with the National Electrical Code.
Installation Instructions:
1. Set the input voltage selector switch located on the left side of the Vertiline unit (facing front panel) for
115VAC or 230VAC operation (Fig. 1c, pg. 4).
2
. Attach mounting brackets to Vertiline unit for rack or wall mount installation (Figs. 4-5, pg. 7). Affix rubber pads to
V
ertiline for shelf installation (Fig. 6, pg. 7).
3.
Secure the unit in a rack, mount unit to a wall or place unit on a shelf as desired (unit should be spaced at least 3” from any video monitors). When installing the unit in a rack allow for one half of a U spacing above the unit for ventilation.
4. Plug the grounded AC line cord (included) into the IEC 320 connector of the Vertiline unit (Fig. 1g, pg. 4).
Insert the plug end of the line cord into a g
5. Set illuminated master power disconnect circuit breaker to the (ON) position (Fig. 3, pg. 6).
6. Select 24VAC or 28VAC pow
(Fig. 1b, pg. 4).
7.
Measure output voltage before connecting cameras. This helps avoid potential damage. All terminals with common suffix (P) “1P, 2P ...” are the same polarity.
8. Set illuminated master power disconnect circuit breaker to the (OFF) position (Fig. 3, pg. 6).
- 2 - Vertiline16
er output for cameras 1-16 with the corresponding voltage adjustment switches
rounded AC receptacle.
9. Connect the power outputs of terminals marked [1P & 1N] to the power inputs of camera 1 (Fig. 2, pg. 5).
Repeat this step for each additional camera (Outputs 2-16). After wiring is completed insert terminal block into the corresponding connector and secure by tightening the screws.
10. Upon completion of wiring, set illuminated master power disconnect circuit breaker to the
ON (RESET) position (Fig. 3, pg. 6).
1
1. The power LEDs (Green) on the faceplate for Outputs 1-16 will illuminate when AC power is present (Fig. 1a, pg. 4). If any of these LEDs are off, a loss of AC power output may be due to a blown fuse or a tripped PTC caused b
y a short circuit or overload condition. If all of the LEDs are OFF there may be a complete loss of supply power to the Vertiline unit or the illuminated master power disconnect circuit breaker is in the OFF position or the main fuse 1-8 or 9-16 is blown (Fig. 1d, pg. 4).*
To restore the power output for Vertiline16 or Vertiline166:
1- Switch corresponding output voltage switch to the OFF position (Fig. 1b, pg. 4). 2-
Eliminate the trouble condition. 3- Replace the corresponding automotive blade fuse.* 4- Switch output voltage switch to the 24VAC or 28VAC position as desired (Fig. 1b, pg. 4).
To restore the power output for Vertiline16D or Vertiline166D:
1- Switch corresponding output voltage switch to the OFF position (Fig. 1b, pg. 4). 2-
Eliminate the trouble condition. 3- Allow 1 minute for PTC to cool off. 4- Switch output voltage switch to the 24VAC or 28VAC position as desired (Fig. 1b, pg. 4).
*Note: Replace fuses with same type and rating:
Output fuses are rated @ 3 amp for all models.
Main fuse ratings:
10 amp for
Vertiline16 and Vertiline16D.
Automotive Blade Fuse
15 amp for Vertiline166 and Vertiline166D.
Vertiline16 - 3 -