Altronix VertiLine16C, VertiLine166C, VertiLine166CD Installation Guide

CCTV Rack Mount Power Supplies
Installation Guide
Models Include:
Vertiline16C Vertiline16CD
- 24VAC or 28VAC @ 10A - 24VAC or 28VAC @ 10A
- Sixteen (16) fuse protected outputs - Sixteen (16) PTC protected outputs
Vertiline166C Vertiline166CD
- 24VAC or 28VAC @ 14A - 24VAC or 28VAC @ 14A
- Sixteen (16) fuse protected outputs - Sixteen (16) PTC protected outputs
Rev. 031808
TM
Overview:
Altronix Vertiline CCTV Rack Mount Power Supplies provide 16 power outputs in a space saving 1U EIA 19” rack mount chassis which may be rack, wall or shelf mounted. The units feature individually selectable 24VAC and/or 28VAC power outputs with surge suppression. Vertiline CCTV Rack Mount Power Supplies are also available in eight (8) and twenty-four (24) output models with various power ratings.
Specifications:
Input:
• 115VAC 60 Hz.
Output:
• Sixteen (16) individually selectable 24VAC or 28VAC power outputs with OFF position.
• Sixteen (16) external blade fuse or PTC protected outputs.
• Surge suppression.
Features:
• Sixteen (16) power LED indicators.
• Removable terminal blocks with locking screw flange.
Features (cont’d):
• Illuminated master power disconnect circuit breaker with manual reset.
• IEC 320 - 3-wire grounded line cord (detachable).
Mechanical:
• Units can be rack, wall or shelf mounted.
• Modular 1U standard EIA 19” rack mount chassis
• Enclosure Dimensions (H x W x D approx.):
1.625” x 19.125” x 8.5” (41.3mm x 486mm x 216mm).
Sixteen (16) Output Rack Mount Configuration Reference Chart:
Output Altronix Model Number
Vertiline16C
Vertiline16CD
Vertiline166C
Vertiline166CD
Voltage
(VAC)
24VAC or
28VAC
24VAC or
28VAC
24VAC or
28VAC
24VAC or
28VAC
Total Output
Current (Power)
Number of Outputs
10A 16
10A 16
14A 16
14A 16
Output Protection
Class 2 Rated Power-
Limited Output protection
Current (max. per output)
Fused -- 3A 3A
-- PTC 2.5A --
Fused -- 3A 3A
-- PTC 2.5A --
Fuse Rating
Main Fuse Rating
115VAC 60Hz Input
10A 3A
15A 4A
Agency
Listings
Current
UL Listings and
File Numbers
UL Listed for
Commercial
CCTV Equipment
(UL 2044).
CUL Listed - CSA
Standard
C22.2 No.1-04,
Audio, Video and
Similar Equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to the National Electrical Code and all local codes.
Installation Instructions:
1. Attach mounting brackets to Vertiline unit for rack or wall mount installation (Figs. 4-5, pg. 7). Affix rubber pads to Vertiline for shelf installation (Fig. 6, pg. 7).
2. Secure the unit in a rack, mount unit to a wall or place unit on a shelf as desired (unit should be spaced at least 3” from any video monitors). When installing the unit in a rack allow for one half of a U spacing above the unit for ventilation.
3. Plug the grounded AC line cord (included) into the IEC 320 connector of the Vertiline unit (Fig. 1f, pg. 4). Insert the plug end of the line cord into a grounded AC receptacle.
- 2 - Vertiline16C
4. Set illuminated master power disconnect circuit breaker to the (ON) position (Fig. 3, pg. 6).
5. Select 24VAC or 28VAC power output for cameras 1-16 with the corresponding voltage adjustment switches (Fig. 1b, pg. 4).
6. Measure output voltage before connecting cameras. This helps avoiding potential damage. All terminals with common suffix (P) “1P, 2P ...” are the same polarity.
7. Set illuminated master power disconnect circuit breaker to the (OFF) position (Fig. 3, pg. 6).
8. Connect the power outputs of terminals marked [1P & 1N] to the power inputs of camera 1 (Fig. 2, pg. 5). Repeat this step for each additional camera (Outputs 2-16). After wiring is completed insert terminal block into the corresponding connector and secure by tightening the screws.
9. Upon completion of wiring, set illuminated master power disconnect circuit breaker to the ON (RESET) position (Fig. 3, pg. 6).
10. The power LEDs (Green) on the faceplate for Outputs 1-16 will illuminate when AC power is present (Fig. 1a, pg. 4). If any of these LEDs are off, a loss of AC power output may be due to a blown fuse or a tripped PTC caused by a short circuit or overload condition. If all of the LEDs are OFF there may be a complete loss of supply power to the Vertiline unit or the illuminated master power disconnect circuit breaker is in the OFF position or the main fuse 1-8 or 9-16 is blown (Fig. 1c, pg. 4).* To restore the power output for Vertiline16C or Vertiline166C: 1- Switch corresponding output voltage switch to the OFF position (Fig. 1b, pg. 4). 2- Eliminate the trouble condition. 3- Replace the corresponding automotive blade fuse.* 4- Switch output voltage switch to the 24VAC or 28VAC position as desired (Fig. 1b, pg. 4). To restore the power output for Vertiline16CD or Vertiline166CD: 1- Switch corresponding output voltage switch to the OFF position (Fig. 1b, pg. 4). 2- Eliminate the trouble condition. 3- Allow 1 minute for PTC to cool off. 4- Switch output voltage switch to the 24VAC or 28VAC position as desired (Fig. 1b, pg. 4).
*Note: Replace fuses with same type and rating:
Output fuses are rated @ 3A for all models. Main fuse ratings: 10A for Vertiline16C and Vertiline16CD. 15A for Vertiline166C and Vertiline166CD.
Automotive Blade Fuse
Vertiline16C - 3 -
AC POWER
1f - IEC 320
Connector:
115VAC 60Hz
(grounded line
cord included).
OFF
28VAC
24VAC
AC POWER
1b - Output voltage switches:
Selects 24VAC or 28VAC
or OFF for each output.
1a - LED(s) 1-16:
Power LED indicators.
78 910111213141516
6
OFF
28VAC
34 5
2
1
1-8
Main Fuse
P
N P
N P
N P
N
P
N P
N P
N P
N
P
N P
N P
N P
N
1e - Output Fuses:
Automotive blade fuses.
1d - Power
Outputs: 24VAC
1c - Main Fuse:
Protects the
transformer
or 28VAC.
against overload.
1234
5678
24VAC
9101112
P
1234
N P
N P
N P
N
P
5678
N P
N P
N P
N
1-8
Main Fuse
P
9101112
N P
N P
N P
N
13141516
RESET
Vertiline16C, Vertiline16CD,
Vertiline166C or Vertiline166CD (front)
OFF
Vertiline16C or Vertiline166C (rear)
P
N P
N P
N P
N
9-16
Main Fuse
Vertiline16CD or Vertiline166CD (rear)
P
13141516
N P
N P
N P
N
9-16
Main Fuse
Vertiline16CD and Vertiline166CD do not have output fuses on the rear of the rack
Fig. 1
- 4 - Vertiline16C
mount chassis. The output PTCs are located on the inside of the rack mount chassis.
AC POWER
OFF
28VAC
24VAC
78 910111213141516
6
Typical Hookup:
28VAC
34 5
1234
5678
OFF
24VAC
P
N P
N P
N P
N
P
N P
N P
N P
N
1-8
Main Fuse
Fig. 2
RESET
2
1
OFF
9101112
13141516
P
N P
N P
N P
N
P
N P
N P
N P
N
9-16
Main Fuse
Vertiline16C - 5 -
The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure. There are no user serviceable parts inside. Refer servicing to qualified service personnel.
1U EIA 19” Rack Mount Chassis Mechanical Drawing & Dimensions (H x W x D):
1.625” x 19.125” x 8.5” (41.3mm x 486mm x 216mm)
REAR
17.125”
(434.97mm)
Main Fuse
1-8
NPNPNPN
5678
P
NPNPNPN
1234
P
1.625”
(41.275mm)
Main Fuse
9-16
NPNPNPN
13141516
P
NPNPNPN
9101112
P
TOP and BOTTOM
AC POWER
(215.9mm)
0.95”
(24.13mm)
8.5”
RESET
FRONT
1
34 5
2
OFF
(ON)
28VAC
OFF
24VAC
78 910111213141516
6
19.125”
(485.775mm)
28VAC
OFF
24VAC
Fig. 3
Power switch with built-in circuit breaker: OFF position - Switch not illuminated. Outputs not powered. RESET (ON) position - Switch illuminated. Outputs powered. Circuit breaker tripped - Switch not illuminated. Power LEDs on faceplate are not illuminated. Outputs not powered. To reset circuit breaker set power switch to the ON (RESET) position (Fig. 3, pg. 6).
- 6 - Vertiline16C
Mounting Options:
Rack Mount Installation
1. Remove factory installed screws from both sides of rack chassis (Fig. 4a).
2. Install mounting brackets (A) on the left and right sides of the rack chassis using the two (2) flat head screws (B) (included) (Fig. 4b).
3. Place unit into the desired EIA 19” rack position and secure with mounting screws (not included) (Fig. 4c).
Fig. 4
Fig. 4a
Top Top
Fig. 4b
Fig. 4c
Top
Front
Front Left
B
Left
Front Left
Remove
A
Wall Mount Installation
1. Install mounting brackets (A) on the left and right sides of the rack chassis using two (2) flat head screws (B) (included) (Fig. 5a).
2. Place unit at the desired location and secure with mounting screws (not included) (Fig. 5b).
Caution: It is necessary to make sure mounting screws are securely fastened to a beam when installing.
Fig. 5
Fig. 5a
Fig. 5b
B
A
Shelf Installation
1. Position and affix rubber pads (C) (included) at each corner on the bottom of the unit (Fig. 6).
2. Place unit in desired location.
Fig. 6
Left Side
C
Vertiline16C - 7 -
Rubber Pad
MountingHardware (Included):
A
Two (2) mounting brackets
Six (6) flat head screws
B
for mounting brackets.
C
Four (4) rubber pads.
Notes: