Altronix T3VK75F20, T2VK7F8, T1VK3F4 Installation Guide

Access & Power Integration
T1VK3F4
4 Door Kit with Fused Outputs
Fully assembled kit includes:
- Trove1 enclosure with TV1 Altronix/HID VertX® backplane
- One (1) eFlow6NB - Power Supply/Charger
- One (1) VR6 - Voltage Regulator
T2VK7F8
8 Door Kit with Fused Outputs
Fully assembled kit includes:
- Trove2 enclosure with TV2 Altronix/HID VertX® backplane
- One (1) eFlow104NB - Power Supply/Charger
- One (1) ACM8 - Fused Access Power Controller
- One (1) VR6 - Voltage Regulator
All components of these Trove kits are UL Listed sub-assemblies. Please refer to the included corresponding Sub-Assembly Installation Guides for further information.
T3VK75F20
20 Door Kit with Fused Outputs
Fully assembled kit includes:
- Trove3 enclosure with TV3 Altronix/HID VertX® backplane
- One (1) eFlow104NB - Power Supply/Charger
- One (1) eFlow102NB - Power Supply/Charger
- Two (2) ACM8 - Fused Access Power Controllers
- One (1) ACM4 - Fused Access Power Controller
- One (1) PD8UL - Fused Power Distribution Module
- One (1) RSB2 - Rocker Switch Bracket with Two (2) Switches (Not evaluated by UL)
Installation Guide
All registered trademarks are property of their respective owners. More than just power.™
Rev. TVK_042519
Installing Company: _____________________ Service Rep. Name: __________________________________________
Address: ________________________________________________________ Phone #: _________________________
Overview:
Tamper Switch
(provided)
To Access Control Panel or UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Altronix Trove HID VertX® kits are pre-assembled and consist of Trove enclosures/backplanes with factory installed Altronix power sup­ply/chargers and sub-assemblies. All kits accommodate a variety of HID VertX® modules for up to four (T1VK3F4), eight (T2VK7F8) or twenty (T3VK75F20) doors in a single enclosure.
Configuration Chart:
Nominal DC
Output Voltage
[DC] [Aux]
Output
Range
(VDC)
20.17-
20.17-
20.17-
26.4
26.4
26.4
9.7-
13.2
Output
Range (VDC)
20.28-
26.4
20.28-
26.4
20.28-
26.4
10.03-
13.2
Fail-Safe/Fail-Secure
or Dry Form “C”
Outputs
Additional Fused
Outputs
ACM4/ACM8 Board
Input Fuse Rating
ACM8 Board
Output Fuse Rating
8
10A/
8 8
20 8
250V
10A/
250V
2.5A/ 250V
2.5A/ 250V
ACM4 Board
Output Fuse Rating
PDS8 Board
Input Fuse Rating
10A/
32V
10A/
32V
3A/
32V
PDS8 Board
Output Fuse Rating
PD8UL Board
3A/
32V
3A/
32V
3.5A/ 250V
Altronix Model Number
T1VK3F4
T2VK7F8
T3VK75F20
120VAC 60Hz
Input Current (A)
3.5 5A/ 250V
4.5 6.3A/250V
7.5
Power Supply Board
Input Fuse Rating
eFlow104NB
6.3A/ 250V
eFlow102NB
5A/ 250V
Maximum Supply Current for Main and Aux. Outputs
on Power Supply
board and ACM4/
ACM8 Access Power
Controllers’ outputs
Power Supply Board
Battery Fuse Rating
15A/
32V
15A/
32V
15A/
32V
24VDC @ 6A
24VDC @ 9.7A
24VDC @ 9.1A
12VDC @ 10A
Installation Instructions for Trove1, Trove2, Trove3:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Remove backplane from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top two/three keyholes in the enclosure. Install two/three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two/three upper screws, level and secure. Mark the position of the lower two/three holes. Remove the enclosure. Drill the lower holes and install the two/three fasteners. Place the enclosure’s upper keyholes over the upper screws. Install the two/three lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired location, opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 1, pg. 2). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the door of the enclosure.
4. Mount HID VertX® modules to backplane(s), refer to pages 3, 4, 5.
5. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow6NB, eFlow104NB, eFlow102NB and corresponding Sub-Assembly Installation Guides for ACM4, ACM8, PDS8, VR6 and PD8UL for further installation instructions.
Fig. 1
Output Fuse Rating
Hardware:
Nylon Spacer | 7/8” Pan Head Screw | Lock Nut
- 2 - Trove HID VertX Kits
T1VK3F4: Installation Instructions for HID VertX® Access Controllers
1. Fasten spacers (provided) onto metal pems configuration (A) of backplane (Fig. 2, pg. 3).
2. Mount HID VertX® modules to spacers utilizing 7/8” pan head screws (provided) (Fig. 2a, pg. 3).
3. Fasten backplane to Trove1 enclosure utilizing hardware (provided).
HID VertX® Access Controller Position Chart for the Following Models:
Sub-Assembly Pem Mounting
V100, V200, V300, V1000, V2000 A
Fig. 2
L G N
NC C NO NC
AC FAIL BAT FAIL
C NO
AC DCAC1
TRIGGER
SUPERVISED RESET
EOL NO GND
+AUX-
Altronix
eFlow6NB
- BAT +- DC +
DM1 +
OFF
IN1 Fuse
IN1
10
IN2
+ INP1
IN2 Fuse
--
10
+ INP2
--
<
<
<
<
1 off 2
1 off 2
33333333
Out1
Out2
>
>
<
1 off 2
1 off 2
1 off 2
Out3
Out4
>
Out5
>
>
DM1 +
<
<
<
1 off 2
1 off 2
1 off 2
Out6
Out7
>
Out8
>
>
P
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
Common (--- )
N
DM2 +
1 2 3 4 5 6 7 8
Common Power Outputs (NEG)
Common (--- )
DM2 +
Altronix VR6 mounted under PDS8
ON
OFF - 24V
ON - 12V
Altronix PDS8
A
HID VertX
Module
®
A
HID VertX
Module
®
Pem
Spacer
®
Backplane
Pan Head
HID VertX Access Controller
Screw
Trove HID VertX Kits - 3 -
Fig. 2a