Access & Power Integration
T2HWK7F8D
8 Door Kit with PTC Outputs
Fully assembled kit includes:
- Trove2 enclosure with THW2 Altronix/Honeywell backplane
- One (1) eFlow104NB - Power Supply/Charger
- One (1) ACM8CB - PTC Access Power Controller
- One (1) VR6 - Voltage Regulator
- One (1) PDS8CB - Dual Input PTC Power Distribution Module
T3HWK75F16D
16 Door Kit with PTC Outputs
Fully assembled kit includes:
- Trove3 enclosure with THW3 Altronix/Honeywell backplane and THWD2 Honeywell door backplane
- One (1) eFlow104NB - Power Supply/Charger
- One (1) eFlow102NB - Power Supply/Charger
- Two (2) ACM8CB - PTC Access Power Controllers
- One (1) PD8ULCB - PTC Power Distribution Module
- One (1) RSB2* - Rocker Switch Bracket with Two (2) Rocker Switches (Not evaluated by UL)
All components of these Trove kits are UL Listed sub-assemblies.
Please refer to the included corresponding Sub-Assembly Installation Guides for further information.
Installation Guide
All registered trademarks are property of their respective owners. More than just power.™
Rev. THWKD_031820
Installing Company: _____________________ Service Rep. Name: __________________________________________
Address: ________________________________________________________ Phone #: _________________________
![](/html/cd/cdc2/cdc20163aee765bf20a67b3e96cfb5087ef3c35217bad90b5c2d2f805d4e6968/bg2.png)
Overview:
Tamper Switch
(provided)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Altronix Trove Honeywell kits are pre-assembled and consist of Trove enclosures/backplanes with factory installed Altronix power supply/chargers and sub-assemblies. Both kits accommodate a variety of Honeywell modules for up to eight (T2HWK7F8D) or sixteen
(T3HWK75F16D) doors in a single enclosure.
Configuration Chart:
Nominal DC
Output Voltage
[DC] [Aux]
Output
Range
(VDC)
20.17-
20.17-
26.4
26.4
9.7-
13.2
Output
Range
(VDC)
20.28-
26.4
20.28-
26.4
10.03-
13.2
Fail-Safe/Fail-Secure
Outputs
Additional PTC
Outputs
ACM8CB Board
Input Fuse Rating
8 8
16 8
10A/
250V
10A/
250V
ACM8CB Board
Output PTC Rating
PDS8CB Board
Input PTC Rating
PDS8CB Board
Output PTC Rating
PD8ULCB Board
2.5A 9A 2.5A –
2.5A – – 3.5A
Altronix
Model
Number
T2HWK7F8D
T3HWK75F16D
Power Supply Board
Input Fuse Rating
6.3A/250V
eFlow104NB
6.3A/ 250V
eFlow102NB
5A/ 250V
Maximum Supply
Current for Main and
Power Supply board
and ACM8CB Access
Power Controllers’
Power Supply Board
Battery Fuse Rating
120VAC 60Hz
Input Current (A)
15A/
15A/
4.5 24VDC @ 9.7A
32V
7.5
32V
Aux. Outputs on
outputs
24VDC @ 9.4A
12VDC @ 10A
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having
jurisdiction. Product is intended for indoor use only.
1. Remove backplane from enclosure. Do not discard hardware.
If your application requires a raised backplane, re-mount it using metal spacers and screws (provided).
2. Mark and predrill holes in the wall to line up with the top two/three keyholes in the enclosure. Install two/three upper fasteners and
screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two/three upper screws;
level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three
fasteners. Place the enclosure’s upper keyholes over the two/three upper screws. Install the three lower screws and make sure to
tighten all screws.
3. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in
desired location, opposite hinge. Slide the tamper switch bracket onto the edge of the
enclosure approximately 2” from the right side (Fig. 1, pg. 2).
Connect tamper switch wiring to the Access Control Panel input or the appropriate
UL Listed reporting device. To activate alarm signal open the door of the enclosure.
4. Mount Honeywell modules to backplane(s), refer to pages 3, 4, 5.
5. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow104NB,
eFlow102NB and corresponding Sub-Assembly Installation Guides for
ACM8CB, PDS8CB, VR6 and PD8ULCB for further installation instructions.
Fig. 1
Output PTC Rating
Hardware:
Nylon Spacer | 5/16” Pan Head Screw | Lock Nut
- 2 - Trove Honeywell Kits PTC
![](/html/cd/cdc2/cdc20163aee765bf20a67b3e96cfb5087ef3c35217bad90b5c2d2f805d4e6968/bg3.png)
T2HWK7F8CB: Installation Instructions for Honeywell Access Controllers
1. Fasten spacers (provided) into pem configuration (A) or (B) of backplane (Fig. 2, pg. 3).
2. Mount boards to spacers utilizing 5/16” pan head screws (provided) (Fig. 2a, pg. 3).
3. Mount backplane to enclosure with hardware.
Honeywell ProWatch/WinPak Access Controller Position Chart for the Following Models:
Honeywell Board Pem Mounting
3200 Series or WIN-PAK Series A
PW6K1ICE or PW6K1R1E B
Fig. 2
– DC +– BAT +
Altronix
eFlow104NB
A
L G N
B
FACP
TRIGGER
5 6 7 8
INPUT
ON
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4
F1 F2 F3 F4 F5 F6 F7 F8
Altronix
ACM8CB
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
DM1 +
OFF
IN1 Fuse
IN1
IN2
+ INP1
IN2 Fuse
--
+ INP2
<
<
<
<
1 off 2
1 off 2
1 off 2
1 off 2
Out1
Out2
Out3
--
>
P
Common (--- )
N
DM2 +
1 2 3 4 5 6 7 8
Altronix VR6 mounted under PDS8CB
Out4
>
>
>
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
Common Power Outputs (NEG)
DM1 +
<
<
<
<
1 off 2
1 off 2
1 off 2
1 off 2
Out5
Out6
Out7
>
Out8
>
>
>
Common (--- )
DM2 +
B
TRG
+INP- T + RET-
ON
1 2 3 4
FACP INTERFACE
1 2 3 4
NO C NC
MAIN
10A 250V
- + - +
Power Control
A
A
A
Fig. 2a
Pem
Spacer
Pan Head
Trove Honeywell Kits PTC - 3 -
Access Controller
Honeywell
Backplane