Altronix T2ZK7F16, T2ZK7F8 Installation Guide

Access & Power Integration
T2ZK7F8
8 Door Kit with Fused Outputs
Fully assembled kit includes:
- Trove2 enclosure with TZ2 Altronix/ZKTeco backplane
- One (1) eFlow104NB - Power Supply/Charger
- One (1) ACM8 - Access Power Controller
- One (1) VR6 - Voltage Regulator
T2ZK7F16
16 Door Kit with Fused Outputs
Fully assembled kit includes:
- Trove2 enclosure with TZ2 Altronix/ZKTeco backplane
- One (1) eFlow104NB - Power Supply/Charger
- Two (2) ACM8 - Access Power Controllers
- One (1) VR6 - Voltage Regulator
All components of these Trove kits are UL Listed sub-assemblies. Please refer to the included corresponding Sub-Assembly Installation Guides for further information.
Installation Guide
All registered trademarks are property of their respective owners. More than just power.™
Rev. TZK_041019
Installing Company: _____________________ Service Rep. Name: __________________________________________
Address: ________________________________________________________ Phone #: _________________________
Overview:
Tamper Switch
(provided)
To Access Control Panel or UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Altronix T2ZK7F8 and T2ZK7F16 Trove ZKTeco kits are pre-assembled and consist of Trove enclosures/backplanes with factory installed Altronix power supply/chargers and sub-assemblies. T2ZK7F8 accommodates up to two (2) ZKTeco modules for up to eight (8) doors in a single enclosure. T2ZK7F16 accommodates up to four (4) ZKTeco modules for up to sixteen (16) doors in a single enclosure.
Configuration Chart:
Maximum Supply
Current for Main and
Aux. Outputs on
Nominal DC Output
Voltage
[DC] [Aux]
Power Supply board
Altronix Model Number
T2ZK7F8
T2ZK7F16
120VAC 60Hz
Input Current (A)
Power Supply Board
Input Fuse Rating
6.3A/ 250V
15A/
32V
4.5
and ACM8 Access
Power Controllers’
Power Supply Board
Battery Fuse Rating
outputs
24VDC @ 9.7A
24VDC @ 9.4A 16
Output
Range (VDC)
Output
Range (VDC)
20.17-26.4 20.28-26.4
Fail-Safe/Fail-Secure
or Dry Form “C”
Outputs
Additional Fused
Outputs
ACM8 Board
Input Fuse Rating
8
10A/
8
250V
ACM8 Board
Output Fuse Rating
PDS8 Board
Input Fuse Rating
2.5A/ 250V
10A/
32V
PDS8 Board
3A/
32V
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Remove backplane from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top two/three keyholes in the enclosure. Install two/three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two/three upper screws; level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two/three upper screws. Install the three lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired location, opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 1, pg. 2). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the door of the enclosure.
4. Mount ZKTeco modules to backplane, refer to pages 3 - 6.
5. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow104NB and corresponding Sub-Assembly Installation Guides for ACM8, PDS8 and VR6 for further installation instructions.
Fig. 1
Output Fuse Rating
Hardware:
Nylon Spacer | 5/16” Pan Head Screw | Lock Nut
- 2 - Trove ZKTeco Kits
T2ZK7F8: Configuration of ZKTeco inBio Modules:
1 2 3 4
ON
1 2 3 4
ON
1. Fasten DIN Rail (provided by ZKTeco) to pem spacers, utilizing 5/16” pan head screws (included) (Fig. 2, pg. 3).
2. Mount ZKTeco modules to DIN Rail (refer to below chart for model number, Fig. 2, pg. 3).
3. Fasten TZ2 backplane to Trove2 enclosure utilizing lock nuts (provided by Altronix).
ZKTeco Model Pem Mounting
inBio-160, inBio-160 Pro, inBio-260, inBio-260 Pro, inBio-460, inBio-460 Pro A
Fig. 2
A
– DC +– BAT +
Altronix
eFlow104NB
L G N
TRIGGER
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4
F1 F2 F3 F4 F5 F6 F7 F8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
DM1 +
OFF
IN1 Fuse
IN1
10
IN2
+ INP1
IN2 Fuse
--
10
+ INP2
<
<
<
1 off 2
1 off 2
1 off 2
33333333
Out1
--
Out2
>
>
P
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
Common (--- )
N
DM2 +
1 2 3 4 5 6 7 8
Common Power Outputs (NEG)
>
INPUT
5 6 7 8
Altronix PDS8
<
<
<
1 off 2
1 off 2
1 off 2
Out3
Out4
Out5
Out6
>
>
>
FACP
ON
Altronix
ACM8
DM1 +
<
<
1 off 2
1 off 2
Out7
Out8
>
>
Common (--- )
DM2 +
Altronix VR6 is mounted under PDS8
TRG
ON
1 2 3 4
1 2 3 4
10A 250V
+INP- T + RET-
FACP INTERFACE
NO C NC
MAIN
- + - +
Power Control
A
A
A
Trove ZKTeco Kits - 3 -
Loading...
+ 5 hidden pages