Altronix T2SSK75F14, T2SSK7F8 Installation Guide

Access & Power Integration
T2SSK7F8
8 Door Kit with Fused Outputs
Fully assembled kit includes:
- Trove2 enclosure with TSS2 Altronix/Lenel-S2 (S2 Security Platform) backplane
- One (1) eFlow104NB - Power Supply/Charger
- One (1) ACM8 - Fused Access Power Controller
- One (1) VR6 - Voltage Regulator
- One (1) PDS8 - Dual Input Fused Power Distribution Module
T2SSK75F14
14 Door Kit with Fused Outputs
Fully assembled kit includes:
- Trove2 enclosure with TSS2 Altronix/Lenel-S2 (S2 Security Platform) backplane
- One (1) eFlow104NB - Power Supply/Charger
- One (1) eFlow102NB - Power Supply/Charger
- Two (2) ACM8 - Fused Access Power Controllers
- Two (2) PD8UL - Fused Power Distribution Module
- One (1) RSB2* - Rocker Switch Bracket with Two (2) Rocker Switches (Not evaluated by UL)
All components of these Trove kits are UL Listed sub-assemblies. Please refer to the included corresponding Sub-Assembly Installation Guides for further information.
Installation Guide
All registered trademarks are property of their respective owners. More than just power.™
Rev. TSSK2_051520
Installing Company: _____________________ Service Rep. Name: __________________________________________
Address: ________________________________________________________ Phone #: _________________________
Overview:
Tamper Switch
(provided)
To Access Control Panel or UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Lock Nut
Altronix T2SSK7F8 and T2SSK75F14 Trove S2 kits are pre-assembled and consist of Trove enclosures/backplanes with factory installed Altronix power supply/chargers and sub-assemblies. Both kits accommodate Lenel-S2 (S2 Security Platform) S2-INST Installation Kit for S2 Network Node for up to eight (8) (T2SSK7F8) or fourteen (14) (T2SSK75F14) doors in a single enclosure.
Configuration Chart:
Nominal DC
Output Voltage
[DC] [Aux]
Output
Range
(VDC)
20.17-
20.17-
26.4
26.4
9.7-
13.2
Output
Range (VDC)
20.28-
26.4
20.28-
26.4
10.03-
13.2
Fail-Safe/Fail-Secure
Outputs
Additional Fused
Outputs
ACM8 Board
Input Fuse Rating
8 8
16 16
10A/
250V
10A/
250V
ACM8 Board
Output Fuse Rating
PDS8 Board
Input Fuse Rating
3.5A/
10A/
250V
32V
3.5A/ 250V
PDS8 Board
Output PTC Rating
PD8UL Board
3A/
32V
3.5A/ 250V
Altronix Model Number
T2SSK7F8
T2SSK75F14
Power Supply Board
Input Fuse Rating
6.3A/250V
eFlow104NB
6.3A/ 250V
eFlow102NB
5A/ 250V
Maximum Supply
Current for Main and
Power Supply board
and ACM8CB Access
Power Controllers’
Power Supply Board
Battery Fuse Rating
120VAC 60Hz
Input Current (A)
15A/
15A/
4.5 24VDC @ 9.7A
32V
7.5
32V
Aux. Outputs on
outputs
24VDC @ 9.4A
12VDC @ 10A
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Remove backplane from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top two/three keyholes in the enclosure. Install two/three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two/three upper screws; level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two/three upper screws. Install the three lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired location, opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 1, pg. 2). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the door of the enclosure.
4. Mount S2-INST Installation Kit to backplane, refer to pages 3, 4.
5. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow102NB, eFlow104NB and corresponding Sub-Assembly Installation Guides for ACM8, PDS8, VR6 and PD8UL for further installation instructions.
Fig. 1
Output Fuse Rating
Hardware:
- 2 - Trove2 SS Kits
T2SSK7F8: Access Controller Position Chart for the S2-INST Installation Kit:
1 2 3 4
ON
1 2 3 4
ON
1. Align S2-INST mounting holes with pems on TSS2 (Fig. 2, pg. 3).
2. Attach S2-INST to backplane with lock nuts (provided) (Fig. 2a, pg. 3).
3. Mount backplane to enclosure with hardware.
4. Fasten TSS2 backplane to Trove2 enclosure utilizing hardware (provided).
Fig. 2
– DC +– BAT +
Altronix
eFlow104NB
RSB1
L G N
TRIGGER
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4
F1 F2 F3 F4 F5 F6 F7 F8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
DM1 +
OFF
IN1 Fuse
IN1
10
IN2
+ INP1
IN2 Fuse
--
10
+ INP2
<
<
<
1 off 2
1 off 2
1 off 2
33333333
Out1
--
Out2
>
>
P
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
Common (--- )
N
DM2 +
1 2 3 4 5 6 7 8
Common Power Outputs (NEG)
>
INPUT
5 6 7 8
Altronix PDS8
<
<
<
1 off 2
1 off 2
1 off 2
Out3
Out4
Out5
>
>
>
Altronix VR6 mounted under PDS8
FACP
ON
Altronix
ACM8
DM1 +
<
<
1 off 2
1 off 2
Out6
Out7
Out8
>
>
Common (--- )
DM2 +
S2-INST Installation Kit For S2 Network Node
TRG
+INP- T + RET-
ON
1 2 3 4
FACP INTERFACE
1 2 3 4
NO C NC
MAIN
10A 250V
- + - +
Power Control
Fig. 2a
Pem
Lock nut
Backplane
S2-INST Bracket
Trove2 SS Kits - 3 -