Access & Power Integration
T1SAK3F4
4 Door Kit with Fused Outputs
Fully assembled kit includes:
- Trove1 enclosure with TSA1 Altronix/Salto backplane
- (1) eFlow6NB - Power Supply/Charger
- (1) ACM4 - Fused Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8 - Dual Input Power Distribution Module
T2SAK75F12
12 Door Kit with Fused Outputs
Fully assembled kit includes:
- Trove2 enclosure with TSA2 Altronix/Salto backplane
- (1) eFlow104NB - Power Supply/Charger
- (1) eFlow102NB - Power Supply/Charger
- (1) ACM8 - Fused Access Power Controller
- (1) ACM4 - Fused Access Power Controller
- (1) PDS8 - Dual Input Power Distribution Module
T2SAK7F8
8 Door Kit with Fused Outputs
Fully assembled kit includes:
- Trove2 enclosure with TSA2 Altronix/Salto backplane
- (1) eFlow104NB - Power Supply/Charger
- (1) ACM8 - Fused Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8 - Dual Input Power Distribution Module
All components of these Trove kits are UL Listed sub-assemblies.
Please refer to the included corresponding Sub-Assembly Installation Guides for further information.
Installation Guide
All registered trademarks are property of their respective owners. More than just power.™
Rev. TSAK032919
Installing Company: _____________________ Service Rep. Name: __________________________________________
Address: ________________________________________________________ Phone #: _________________________
Overview:
Tamper Switch
(provided)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Altronix Trove Salto kits are pre-assembled and consist of Trove1SA1 or Trove2SA2 enclosure/backplane with factory installed Altronix
power supply/charger(s) and sub-assemblies. These kits also accommodate various combinations of Salto modules for up to twelve (12)
doors in a single enclosure.
Configuration Chart:
Nominal DC Output
Voltage
Altronix
Model Number
T1SAK3F4
T2SAK7F8
T2SAK75F12
120VAC 60Hz
Input Current (A)
Power Supply Board
3.5
4.5
8
5A/
250V
6.3A/
250V
6.3A/250V
5A/250V
Power
Supply 1
[DC] [Aux] [DC] [Aux]
Input Fuse Rating
Power Supply Board
Battery Fuse Rating
Output Range
10A/
20.19-
32V
26.4
15A/
20.17-
32V
26.4
15A/
20.17-
32V
26.4
(VDC)
20.19-
26.4
20.28-
26.4
20.28-
26.4
Power
Supply 2
Maximum Supply
Current for Main and
Aux. Outputs on Power
Supply board and
ACM4/ACM8
Access Power
Output Range
(VDC)
Output Range
(VDC)
– – 24VDC @ 5.6A 4 2.5
– – 24VDC @ 9.2A 8 2.5
10.03-
10.03-
13.2
13.2
Controller’s outputs
Output Range
(VDC)
12VDC @ 9.3A
24VDC @ 9.2A
Fail-Safe/Fail-Secure or
Dry Form “C” Outputs
Current Per
ACM4/ACM8 Output (A)
ACM4/ACM8 Board
Input Fuse Rating
10A/
10A/
10A/
3A/
250V
2.5A/
250V
2.5A/
250V
12 2.5
250V
250V
250V
ACM4/ACM8 Board
Output Fuse Rating
PDS8 Board
Input Fuse Rating
PDS8 Board
Output Fuse Rating
10A/
10A/
10A/
3A/
250V
3A/
250V
3A/
250V
250V
250V
250V
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having
jurisdiction. Product is intended for indoor use only.
1. Remove backplane(s) from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws
in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws, level and secure.
Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the
enclosure’s upper keyholes over the three upper screws. Install the three lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired location, opposite hinge. Slide the
tamper switch bracket onto the edge of the enclosure approximately 2” from the right side
(Fig. 1, pg. 2). Connect tamper switch wiring to the Access Control Panel input or the
appropriate UL Listed reporting device. To activate alarm signal open the
door of the enclosure.
4. Mount Salto modules to TSA2 backplane, refer to pg. 3, 4, 5.
5. Refer to the eFlow Power Supply/Charger Installation Guide eFlow6NB, eFlow102NB,
eFlow104NB and corresponding Sub-Assembly Installation Guides for
ACM4, ACM8, PDS8, VR6 for further installation instructions.
Fig. 1
Hardware:
Nylon Spacer | 5/16” Pan Head Screw | Lock Nut
- 2 - Trove / SALTO Kits
T1SAK3F4: Configuration of Salto Modules:
1. Fasten spacers onto metal pems configuration (A) of backplane (Fig. 2, pg. 3).
2. Position Salto modules over corresponding spacers and mount them utilizing pan head screws (provided) (Fig. 2a, pg. 3).
3. Mount backplane to enclosure with hardware.
Access Controller Position Chart for the Following Models:
Salto Access Controller Pem Mounting
CU42E0, CU4200 or CU4EB8
Fig. 2
L G N
Altronix
eFlow6NB
NC C NO NC C NO
AC FAIL BAT FAIL
AC DCAC1
1 min enable
2 hr disable
TRIGGER EOL
SUPERVISED
NO GND
RESET
+ AUX -
--- BAT +
--- DC +
TRIGGER
IN GND1IN GND2IN GND3IN GND
LED1 LED2 LED3 LED4
NC C NO COM NC C NO COM NC C NO COM NC C NO COM
OUTPUT 1
INPUT
4
OUTPUT 2 OUTPUT 3
OUTPUT 4
Altronix
ACM4
MAIN
TRG
INTERFACE
+INP- T +RET-
FACP
NO C NC
-- +
CONTROL
POWER
-- +
Altronix PDS8
DM1+
ON
OFF - 24V
ON - 12V
+ INP1 - + INP2 -
Common(-)
IN1 Fuse
Fuse1
IN2 Fuse
Fuse2 Fuse3 Fuse4 Fuse5 Fuse6 Fuse7 Fuse8
P
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
N
DM2+
1 2 3 4 5 6 7 8
Common Power Outputs (NEG)
DM1+
P
N
Common(-)
DM2+
Altronix VR6 is mounted under PDS8
A
A A
Fig. 2a
Backplane
Spacer
HS4 Module
Pan Head Screw
Trove / SALTO Kits - 3 -