Access & Power Integration Solutions
Installation Guide for models:
T2MK3F4D
Fully assembled kit includes:
- Trove2 enclosure with TM2 backplane
- (1) eFlow6NB - Power Supply/Charger
- (1) ACM4CB - PTC Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8CB - Dual Input Power Distribution Module
T2MK3F4DQ
Fully assembled kit includes:
- Trove2 enclosure with TM2 backplane
- (1) eFlow6NB - Power Supply/Charger
- (1) LINQ2 - Network Communications Module
- (1) ACM4CB - PTC Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8CB - Dual Input Power Distribution Module
T2MK3F8D
Fully assembled kit includes:
- Trove2 enclosure with TM2 backplane
- (1) eFlow6NB - Power Supply/Charger
- (1) ACM8CB - PTC Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8CB - Dual Input Power Distribution Module
T2MK3F8DQ
Fully assembled kit includes:
- Trove2 enclosure with TM2 backplane
- (1) eFlow6NB - Power Supply/Charger
- (1) LINQ2 - Network Communications Module
- (1) ACM8CB - PTC Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8CB - Dual Input Power Distribution Module
T2MK7F8DQ
Fully assembled kit includes:
- Trove2 enclosure with TM2 backplane
- (1) eFlow104NB - Power Supply/Charger
- (1) LINQ2 - Network Communications Module
- (1) ACM8CB - PTC Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8CB - Dual Input Power Distribution Module
T2MK75F16D
Fully assembled kit includes:
- Trove2 enclosure with TM2 backplane and TMV2 door backplane
- (1) eFlow104NB and (1) eFlow102NB - Power Supply/Chargers
- (2) ACM8CB - PTC Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PD8ULCB - Power Distribution Module
T2MK75F16DQ
Fully assembled kit includes:
- Trove2 enclosure with TM2 backplane and TMV2 door backplane
- (1) eFlow104NB and (1) eFlow102NB - Power Supply/Chargers
- (1) LINQ2 - Network Communications Module
- (2) ACM8CB - PTC Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PD8ULCB - Power Distribution Module
T2MK77F16D
Fully assembled kit includes:
- Trove2 enclosure with TM2 backplane and TMV2 door backplane
- (2) eFlow104NB - Power Supply/Charger
- (2) ACM8CB - PTC Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8CB - Dual Input Power Distribution Module
T2MK7F8D
Fully assembled kit includes:
- Trove2 enclosure with TM2 backplane
- (1) eFlow104NB - Power Supply/Charger
- (1) ACM8CB - PTC Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8CB - Dual Input Power Distribution Module
Rev. TMKD060117 More than just power.™
Installing Company: __________________________ Service Rep. Name: ______________________________________________
Address: _______________________________________________________________ Phone #: ___________________________
T2MK77F16DQ
Fully assembled kit includes:
- Trove2 enclosure with TM2 backplane and TMV2 door backplane
- (2) eFlow104NB - Power Supply/Charger
- (1) LINQ2 - Network Communications Module
- (2) ACM8CB - PTC Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8CB - Dual Input Power Distribution Module
Overview:
Edge of
Enclosure
to Access Control Panel
or U.L. Listed
Reporting Device
Enclosure
Honeywell
model # 112
Tamper Switch
or equivalent
(provided)
Altronix Trove Mercury kits are pre-assembled and consist of Trove2M2 enclosure with factory installed Altronix power supply/
charger(s) and sub-assemblies. These kits also accommodate various combinations of Mercury boards for up to sixteen (16) doors in
a single enclosure.
Configuration Chart:
Nominal DC Output
Voltage
Maximum
Supply
Current for
Main and Aux.
Outputs on Power
Supply board
and ACM4CB/
ACM8CB
Access Power
Controller’s
outputs
(VDC)
12VDC @ 9.3A
24VDC @ 9.2A
12VDC @ 9.3A
24VDC @ 9.2A
Fail-Safe/Fail-Secure Auto-
Resettable Outputs
120VAC 60Hz
16 8 2.0
16 8 2.0
24VDC @ 9.2A 16 9 2.0
24VDC @ 9.2A 16 9 2.0
Input Current (A)
Current Per
ACM4CB/ACM8CB Output (A)
Power Supply Board
5A/
250V
5A/
250V
5A/
250V
5A/
250V
6.3A/
250V
6.3A/
250V
6.3A/250V
5A/250V
6.3A/250V
5A/250V
6.3A/
250V
6.3A/
250V
Input Fuse Rating
Power Supply Board
Battery Fuse Rating
ACM4CB/ACM8CB
10A/
10A/
32V
250V
10A/
10A/
32V
250V
10A/
10A/
32V
250V
10A/
10A/
32V
250V
15A/
10A/
32V
250V
15A/
10A/
32V
250V
15A/
10A/
32V
250V
15A/
10A/
32V
250V
15A/
10A/
32V
250V
15A/
10A/
32V
250V
Board Input Fuse Rating
ACM4CB/ACM8CB Board
Output PTC Rating
PDS8CB Board
Input Fuse Rating
PDS8CB Board
Output PTC Rating
2A
2A
2A
2A
2A
2A
10A/
250V
10A/
250V
10A/
250V
10A/
250V
10A/
250V
10A/
250V
2A ----
2A ----
2A ----
2A ----
2A ----
2A ----
2A ---- ---- 2A
2A ---- ---- 2A
2A
2A
10A/
250V
10A/
250V
2A ----
2A ----
PD8ULCB Board
Altronix
Model Number
T2MK3F4D
T2MK3F4DQ
T2MK3F8D
T2MK3F8DQ
T2MK7F8D
T2MK7F8DQ
T2MK75F16D
T2MK75F16DQ
T2MK77F16D
T2MK77F16DQ
Power
Supply 1
Power
Supply 2
[DC] [Aux] [DC] [Aux]
Output Range
(VDC)
Output Range
(VDC)
Output Range
(VDC)
Output Range
20.19-
26.4
20.19-
26.4
20.19-
26.4
20.19-
26.4
20.17-
26.4
20.17-
26.4
20.17-
26.4
20.17-
26.4
20.17-
26.4
20.17-
26.4
20.19-
26.4
20.19-
26.4
20.19-
26.4
20.19-
26.4
20.28-
26.4
20.28-
26.4
20.28-
26.4
20.28-
26.4
20.28-
26.4
20.28-
26.4
---- ---- 24VDC @ 5.8A 4 3.5 2.0
---- ---- 24VDC @ 5.8A 4 3.5 2.0
---- ---- 24VDC @ 5.8A 8 3.5 2.0
---- ---- 24VDC @ 5.8A 8 3.5 2.0
---- ---- 24VDC @ 9.2A 8 4.5 2.0
---- ---- 24VDC @ 9.2A 8 4.5 2.0
9.7-
10.03-
13.2
13.2
9.7-
10.03-
13.2
13.2
20.17-
20.28-
26.4
26.4
20.17-
20.28-
26.4
26.4
Output PTC Rating
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities
having jurisdiction. Product is intended for indoor use only.
1. Remove backplane(s) from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws
in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws, level and secure.
Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the
enclosure’s upper keyholes over the three upper screws. Install the three lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch (Honeywell Model 112 or equivalent) in desired location, opposite hinge. Slide the
tamper switch bracket onto the edge of the enclosure approximately 2” from the right side
(Fig. 1, pg. 2). Connect tamper switch wiring to the Access Control Panel input or the
appropriate UL Listed reporting device. To activate alarm signal open the
door of the enclosure.
4. Refer to the eFlow Power Supply/Charger Installation Guide (eFlow6NB, eFlow102NB,
eFlow104NB) and Sub-Assembly Installation Guide for the following models:
ACM4CB, ACM8CB, LINQ2, PDS8CB, VR6 for further installation instructions.
5. Fasten snap on standoffs onto metal pems configuration of backplane depending on the
Mercury access controller (Fig. 2-5, pg. 3-6).
6. Position Mercury access controller module over corresponding standoffs and depress onto
snap on standoffs (Fig. 2-5, pg. 3-6).
7. Mount backplane to enclosure with hardware.
- 2 - T2MKD Kits
Fig. 1
T2MK3F4D:
LINQ2
(T2MK3F4DQ, T2MK3F8DQ)
Altronix
eFlow6NB
or ACM8CB
(T2MK3F8)
Altronix
ACM4CB
(T2MK3F4)
Altronix
PDS8CB & VR6
One (1) eFlow6NB - 24VDC @ 6A Power Supply/Charger, one (1) ACM4CB - 4 PTC output Access Power Controller, one (1) VR6
- 24VDC input to 12VDC output Voltage Regulator, and one (1) PDS8CB - 8 PTC output Dual Input Power Distribution Module.
T2MK3F4DQ:
One (1) eFlow6NB - 24VDC @ 6A Power Supply/Charger, one (1) LINQ2 Network Communication Module, one (1) ACM4CB 4 PTC output Access Power Controller, one (1) VR6 - 24VDC input to 12VDC output Voltage Regulator, and one (1) PDS8CB 8 PTC output Dual Input Power Distribution Module.
T2MK3F8D:
One (1) eFlow6NB - 24VDC @ 6A Power Supply/Charger, one (1) ACM8CB - 8 PTC output Access Power Controller, one (1) VR6
- 24VDC input to 12VDC output Voltage Regulator, and one (1) PDS8CB - 8 PTC output Dual Input Power Distribution Module.
T2MK3F8DQ:
One (1) eFlow6NB - 24VDC @ 6A Power Supply/Charger, one (1) LINQ2 Network Communication Module, one (1) ACM8CB 8 PTC output Access Power Controller, one (1) VR6 - 24VDC input to 12VDC output Voltage Regulator, and one (1) PDS8CB 8 PTC output Dual Input Power Distribution Module.
Fig. 2
T2MKD Kits - 3 -