- Trove2 enclosure with TM2 backplane and TMV2 door backplane
- (2) eFlow104NB - Power Supply/Charger
- (1) LINQ2 - Network Communications Module
- (2) ACM8CB - PTC Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8CB - Dual Input Power Distribution Module
Overview:
Edge of
Enclosure
to Access Control Panel
or U.L. Listed
Reporting Device
Enclosure
Honeywell
model # 112
Tamper Switch
or equivalent
(provided)
Altronix Trove Mercury kits are pre-assembled and consist of Trove2M2 enclosure with factory installed Altronix power supply/
charger(s) and sub-assemblies. These kits also accommodate various combinations of Mercury boards for up to sixteen (16) doors in
a single enclosure.
Configuration Chart:
Nominal DC Output
Voltage
Maximum
Supply
Current for
Main and Aux.
Outputs on Power
Supply board
and ACM4CB/
ACM8CB
Access Power
Controller’s
outputs
(VDC)
12VDC @ 9.3A
24VDC @ 9.2A
12VDC @ 9.3A
24VDC @ 9.2A
Fail-Safe/Fail-Secure Auto-
Resettable Outputs
120VAC 60Hz
1682.0
1682.0
24VDC @ 9.2A1692.0
24VDC @ 9.2A1692.0
Input Current (A)
Current Per
ACM4CB/ACM8CB Output (A)
Power Supply Board
5A/
250V
5A/
250V
5A/
250V
5A/
250V
6.3A/
250V
6.3A/
250V
6.3A/250V
5A/250V
6.3A/250V
5A/250V
6.3A/
250V
6.3A/
250V
Input Fuse Rating
Power Supply Board
Battery Fuse Rating
ACM4CB/ACM8CB
10A/
10A/
32V
250V
10A/
10A/
32V
250V
10A/
10A/
32V
250V
10A/
10A/
32V
250V
15A/
10A/
32V
250V
15A/
10A/
32V
250V
15A/
10A/
32V
250V
15A/
10A/
32V
250V
15A/
10A/
32V
250V
15A/
10A/
32V
250V
Board Input Fuse Rating
ACM4CB/ACM8CB Board
Output PTC Rating
PDS8CB Board
Input Fuse Rating
PDS8CB Board
Output PTC Rating
2A
2A
2A
2A
2A
2A
10A/
250V
10A/
250V
10A/
250V
10A/
250V
10A/
250V
10A/
250V
2A----
2A----
2A----
2A----
2A----
2A----
2A--------2A
2A--------2A
2A
2A
10A/
250V
10A/
250V
2A----
2A----
PD8ULCB Board
Altronix
Model Number
T2MK3F4D
T2MK3F4DQ
T2MK3F8D
T2MK3F8DQ
T2MK7F8D
T2MK7F8DQ
T2MK75F16D
T2MK75F16DQ
T2MK77F16D
T2MK77F16DQ
Power
Supply 1
Power
Supply 2
[DC] [Aux] [DC] [Aux]
Output Range
(VDC)
Output Range
(VDC)
Output Range
(VDC)
Output Range
20.19-
26.4
20.19-
26.4
20.19-
26.4
20.19-
26.4
20.17-
26.4
20.17-
26.4
20.17-
26.4
20.17-
26.4
20.17-
26.4
20.17-
26.4
20.19-
26.4
20.19-
26.4
20.19-
26.4
20.19-
26.4
20.28-
26.4
20.28-
26.4
20.28-
26.4
20.28-
26.4
20.28-
26.4
20.28-
26.4
--------24VDC @ 5.8A43.52.0
--------24VDC @ 5.8A43.52.0
--------24VDC @ 5.8A83.52.0
--------24VDC @ 5.8A83.52.0
--------24VDC @ 9.2A84.52.0
--------24VDC @ 9.2A84.52.0
9.7-
10.03-
13.2
13.2
9.7-
10.03-
13.2
13.2
20.17-
20.28-
26.4
26.4
20.17-
20.28-
26.4
26.4
Output PTC Rating
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities
having jurisdiction. Product is intended for indoor use only.
1. Remove backplane(s) from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws
in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws, level and secure.
Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the
enclosure’s upper keyholes over the three upper screws. Install the three lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch (Honeywell Model 112 or equivalent) in desired location, opposite hinge. Slide the
tamper switch bracket onto the edge of the enclosure approximately 2” from the right side
(Fig. 1, pg. 2). Connect tamper switch wiring to the Access Control Panel input or theappropriate UL Listed reporting device. To activate alarm signal open the
door of the enclosure.
4. Refer to the eFlow Power Supply/Charger Installation Guide (eFlow6NB, eFlow102NB,
eFlow104NB) and Sub-Assembly Installation Guide for the following models:
ACM4CB, ACM8CB, LINQ2, PDS8CB, VR6 for further installation instructions.
5. Fasten snap on standoffs onto metal pems configuration of backplane depending on the
Mercury access controller (Fig. 2-5, pg. 3-6).
6. Position Mercury access controller module over corresponding standoffs and depress onto
snap on standoffs (Fig. 2-5, pg. 3-6).
7. Mount backplane to enclosure with hardware.
- 2 - T2MKD Kits
Fig. 1
T2MK3F4D:
LINQ2
(T2MK3F4DQ, T2MK3F8DQ)
Altronix
eFlow6NB
or ACM8CB
(T2MK3F8)
Altronix
ACM4CB
(T2MK3F4)
Altronix
PDS8CB & VR6
One (1) eFlow6NB - 24VDC @ 6A Power Supply/Charger, one (1) ACM4CB - 4 PTC output Access Power Controller, one (1) VR6
- 24VDC input to 12VDC output Voltage Regulator, and one (1) PDS8CB - 8 PTC output Dual Input Power Distribution Module.
T2MK3F4DQ:
One (1) eFlow6NB - 24VDC @ 6A Power Supply/Charger, one (1) LINQ2 Network Communication Module, one (1) ACM4CB 4 PTC output Access Power Controller, one (1) VR6 - 24VDC input to 12VDC output Voltage Regulator, and one (1) PDS8CB 8 PTC output Dual Input Power Distribution Module.
T2MK3F8D:
One (1) eFlow6NB - 24VDC @ 6A Power Supply/Charger, one (1) ACM8CB - 8 PTC output Access Power Controller, one (1) VR6
- 24VDC input to 12VDC output Voltage Regulator, and one (1) PDS8CB - 8 PTC output Dual Input Power Distribution Module.
T2MK3F8DQ:
One (1) eFlow6NB - 24VDC @ 6A Power Supply/Charger, one (1) LINQ2 Network Communication Module, one (1) ACM8CB 8 PTC output Access Power Controller, one (1) VR6 - 24VDC input to 12VDC output Voltage Regulator, and one (1) PDS8CB 8 PTC output Dual Input Power Distribution Module.
Fig. 2
T2MKD Kits - 3 -
T2MK7F8D:
LINQ2
One (1) eFlow104NB - 24VDC @ 10A Power Supply/Charger, one (1) ACM8CB - 8 PTC output Access Power Controller, one (1) VR6
- 24VDC input to 12VDC output Voltage Regulator, and one (1) PDS8CB - 8 PTC output Dual Input Power Distribution Module.
T2MK7F8DQ:
One (1) eFlow104NB - 24VDC @ 10A Power Supply/Charger, one (1) LINQ2 Network Communication Module, one (1) ACM8CB 8 PTC output Access Power Controller, one (1) VR6 - 24VDC input to 12VDC output Voltage Regulator, and one (1) PDS8CB 8 PTC output Dual Input Power Distribution Module.
Fig. 3
(T2MK7F8DQ)
Altronix
eFlow104NB
Altronix ACM8CB
Altronix
PDS8CB & VR6
- 4 - T2MKD Kits
T2MK75F16D:
LINQ2
One (1) eFlow104NB - 24VDC @ 10A Power Supply/Charger and one (1) eFlow102NB - 12VDC @ 10A Power Supply/Charger,
two (2) ACM8CB - 8 PTC output Access Power Controller, and one (1) PD8ULCB - 8 PTC output Power Distribution Module.
T2MK75F16DQ:
One (1) eFlow104NB - 24VDC @ 10A Power Supply/Charger and one (1) eFlow102NB - 12VDC @ 10A Power Supply/Charger,
one (1) LINQ2 Network Communication Module, two (2) ACM8CB - 8 PTC output Access Power Controller,
and one (1) PD8ULCB - 8 PTC output Power Distribution Module.
Fig. 4
(T2MK75F16DQ)
Altronix
Altronix
PD8ULCB
eFlow104NB
Altronix
eFlow102NB
Altronix ACM8CB
Altronix ACM8CB
T2MKD Kits - 5 -
T2MK77F16D:
LINQ2
Two (2) eFlow104NB - 24VDC @ 6A Power Supply/Charger, two (2) ACM8CB - 8 PTC output Access Power Controller, one (1)
VR6 - 24VDC input to 12VDC output Voltage Regulator and one (1) PDS8CB - 8 PTC output Dual Input Power Distribution Module.
T2MK77F16DQ:
Two (2) eFlow104NB - 24VDC @ 6A Power Supply/Charger, one (1) LINQ2 Network Communication Module , two (2) ACM8CB - 8
PTC output Access Power Controller, one (1) VR6 - 24VDC input to 12VDC output Voltage Regulator and one (1) PDS8CB - 8 PTC
output Dual Input Power Distribution Module.
Fig. 5
(T2MK77F16DQ)
Altronix
PDS8CB & VR6
Altronix
eFlow104NB
Altronix
eFlow104NB
Altronix ACM8CB
Altronix ACM8CB
- 6 - T2MKD Kits
A
A
A
A
A
A
B
B
B
B
B
B
C
C
C
TMV2 (T2MK75F16D, T2MK75F16DQ, T2MK77F16D, and T2MK77F16DQ):
N
y
TMV2 accommodates a variety of Mercury boards with or without Altronix sub-assemblies for access systems.
Configuration of Mercury and/or Altronix Boards
Mercury Access Controllers:
1. Fasten snap on standoffs onto metal pems configuration (A) (B) of backplane depending on the access controller (Fig. 6, pg. 7).
2. Position access controller module over corresponding standoffs and depress onto snap on standoffs (Fig. 6a, pg. 7).
3. Mount backplane to enclosure with hardware.
Altronix Sub-Assemblies and/or Adapters:
1. Fasten nylon / snap on standoffs to pems which match the hole pattern for Altronix Sub-Assemblies (Fig. 6, 6a, pg. 7).
2. Mount boards to standoffs utilizing pan head screws provided with the product or by depressing board onto snap on standoff
(Fig. 6, pg. 7).
Note: For GB1 please use standoffs supplied with the adapter.
Access Controller Position Chart for the Following Models:
27.25” x 21.5” x 6.5” (692.15mm x 552.5mm x 165.1mm)
21.50”
(546.1mm)
2.00”
(50.8mm)
5.25”
(133.35mm)
3.50”
(88.9mm)
0.5625”
(14.29mm)
3.50”
(88.9mm)
(44.96mm)
2.415”
(61.34mm)
1.77”
5.25”
(133.35mm)
0.685”
(17.399mm)
Knockouts
1.125” (28.32mm)
0.885” (22.479mm)
6.25”
(158.75mm)
6.25”
(158.75mm)
1.25”
(31.75mm)
G
0.85”
(21.59mm)
1.5”
(38.1mm)
27.00”
(685.8mm)
19.80”
(502.92mm)
2.00”
(50.8mm)
6.75”
(171.45mm)
8.25”
(209.54mm)
0.85”
(21.59mm)
1.00”
(25.4mm)
2.00”
50.8mm
5.25”
133.35mm
7.00”
177.79mm
5.25”
133.35mm
2.00”
50.8mm
1.25”
(31.75mm)
1.25”
(31.75mm)
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
web site: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty | Made in U.S.A.
IITrove2M2 Kit Series B12R
- 8 - T2MKD Kits
8.00”
(203.2mm)
2.00”
(50.8mm)
MEMBER
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.