T2KSK7F12
Access & Power Integration Solution
Description
Altronix T2KSK7F12 kit consists of Trove2 enclosure, TKS2 Keri Systems/Altronix
backplane with one (1) 24VDC @ 10A power supply/charger, one (1) dual output
fused access power controller, one (1) voltage regulator, one (1) dual input fused
power distribution module, and one (1) fused access power controller.
This kit also accommodate various combinations of Keri Systems boards for up
to twelve (12) doors in a single enclosure. Trove simplifies board layout and wire
management, reduces installation time and labor costs.
Key Features
T2KSK7F12
- 24VDC power supply/charger.
- Accommodates up to three (3) Keri Systems NXT-2D-MSCNE,
NXT-4D-MSCNE or NXT-4X4NE boards.
- Convenient knockout configuration:
- Single 2” diameter knockout located top center of enclosure
- Sixteen (16) double knockouts (1” and 0.75”).
- 16 AWG galvanized steel backplane simplifies board layout
and wire management.
*Altronix Power Supply/Chargers and Sub-Assemblies only
Accessories (order separately)
LINQ2 - Network Supervision
Altronix LINQ2 Network Communication Module provides remote supervision, control and monitoring over LAN/WAN
- Remotely reports accurate power diagnostics
- Controls power and resets devices
- Reports system diagnostics via Email
LINQ2
WM5, WM25, WM100 - Magnetic Cable Tie Mounts
Altronix WM5, WM25, and WM100 are packs of 5, 25 or 100 magnetic cable tie mounts respectively.
They accommodate standard zip ties or velcro straps. These are ideal for wire management in our Trove series.
WM5
- Supervision
- AC Fail
- Low Battery and Battery Presence
- Low power shutdown.
- CE European Conformity.
- Enclosure accommodates up to four (4) 12VDC/12AH batteries.
- Lifetime Warranty*/Made in the U.S.A.
Mounting Magnet
MM4, MM8, MM12, MM24 - Magnetic Mounting Solution
Altronix mounting magnets accommodate screws and nylon standoffs to allow for mounting various boards/
accessories in any metal enclosure or backplane.
Rev. T2KSK7F12 - 03242020
T2KSK7F12
Access & Power Integration Solution
Specifications
Power Supply (eFlow104NB):
Input
Voltage 120VAC, 60Hz 4.5A.
Input Fuse 6.3A/250V.
Output
Voltage 24VDC @ 10A.
Auxiliary 1A (unswitched).
Protection Overvoltage protection. Filtered and regulated.
Battery Backup (not included)
Type Sealed lead acid or gel type.
Fuse Rating 10A/32VDC.
Failover Upon AC loss, instantaneous.
Fire Alarm Disconnect
Supervised Latching or non-latching.
EOL 10K Resistor.
Supervision
AC Failure Form “C” contacts.
Battery Form “C” contacts.
Low DC Power Shutdown
Shuts down DC output terminals if battery voltage drops below
70-75% for 24V units. Prevents deep battery discharge.
Indicators (LED)
AC Input 120VAC is present.
DC Output Powered.
Battery Discharged or not connected.
Access Power Controller (ACM4):
Input
Voltage 24VDC from eFlow104NB.
Input Fuse 10A/32V.
Outputs
Voltage 24VDC.
Four (4) independently controlled 2.5A outputs:
a) Four (4) Fail-Safe and/or Fail-Secure power outputs.
b) Four (4) dry form “C” 5A rated relay outputs.
c) Any combination of the above.
Four (4) auxiliary power outputs (unswitched).
Output Fuses 3A/32V.
Indicators (LED)
Red LEDs Outputs are triggered (relays energized).
Green LED FACP disconnect is triggered.
Voltage Regulator (VR6):
Input
Voltage 24VDC from eFlow104NB.
Output
Voltage 12VDC.
Current 6A continuous.
Other Surge suppression.
Indicators (LED)
Input 24VDC is present.
Output Powered.
Dual Input Access Power Controller (ACMS8):
Input
Voltage 24VDC from eFlow104NB and 12VDC from VR6.
Main Fuse 15A/32V.
Outputs
Voltage 12 or 24VDC individually selectable.
Eight (8) selectable 12VDC - 24VDC independently controlled
outputs or eight (8) indepently controlled Form “C” relay outputs:
a) Fail-Safe and/or Fail-Secure power outputs.
b) Form “C” Relays. 28VAC or VDC @ 2.5A Rated.
c) Auxiliary power outputs (unswitched).
d) Any combination of the above.
Any of the eight (8) fuse protected power outputs are selectable
to follow power Input 1 or Input 2.
Individual outputs may be set to OFF position for servicing.
Output Fuses 3A/32V.
Indicators (LED)
Red LEDs Outputs are triggered (relays energized).
Blue LED FACP disconnect is triggered.
Individual voltage LEDs:
Green: 12VDC
Red: 24VDC.
Dual Input Power Distribution Module (PDS8):
Input
Voltage 24VDC from eFlow104NB and 12VDC from VR6.
Main Fuse 10A/32V.
Outputs
Voltage 12 or 24VDC individually selectable.
Output Fuses 3A/32V.
Indicators (LED)
DC Output Eight (8) individual output LEDs.
Green: 12VDC
Red: 24VDC.
T2KSK7F12 Kit:
Agency Listings
All components of this Trove kit are UL Listed sub-assemblies.
Please refer to the corresponding Sub-Assembly Installation Guides for
further information.
CE European Conformity.
Physical and Environmental
Dimensions (H x W x D)
27.25” x 21.5” x 6.5” (692.2mm x 546.1mm x 165.1mm).
Weight (approx.)
Product 54.7 lb. (24.8 kg).
Shipping 59.7 lb. (27.1 kg).
Temperature
Operating 0ºC to 50ºC (32ºF to 122ºF).
Storage -20ºC to 70ºC (-4ºF to 158ºF).
Relative Humidity 85% +/-5%.
BTU/Hr (approx.): 131 BTU/Hr.