![](/html/c1/c112/c11228a51940b1cd9845e5d876aaff8cbdb42cf5f0a6275746324b8ecfcd8d7b/bg1.png)
Access & Power Integration
T2KHK3F12
12 Door Kit with Fused Outputs
Fully assembled kit includes:
- Trove2 enclosure with TKH2 Altronix/Kantech backplane
- One (1) eFlow6NB - Power Supply/Charger
- One (1) T1618300K - Transformer
- One (1) ACM4 - Fused Access Power Controller
- One (1) ACM8 - Fused Access Power Controller
All components of this Trove kit are UL Listed sub-assemblies.
Please refer to the included corresponding Sub-Assembly Installation Guides for further information.
Installation Guide
All registered trademarks are property of their respective owners. More than just power.™
Rev. 040819
Installing Company: _____________________ Service Rep. Name: __________________________________________
Address: ________________________________________________________ Phone #: _________________________
![](/html/c1/c112/c11228a51940b1cd9845e5d876aaff8cbdb42cf5f0a6275746324b8ecfcd8d7b/bg2.png)
Overview:
Tamper Switch
(provided)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Altronix T2KHK3F12 Trove Kantech kit is pre-assembled and consists of Trove2KH2 enclosure/backplane with factory
installed Altronix power supply/charger and sub-assemblies. T2KHK3F12 kit also accommodates various combinations of
Kantech boards for up to twelve (12) doors in a single enclosure.
TKH2 accommodates a combination of the following Kantech boards:
• Up to four (4) KT-MOD-INP16 or KT-MOD-OUTP16.
• Up to four (4) KT300.
• Up to three (3) KT400.
Configuration Chart:
Nominal DC Output
Voltage
[DC] [Aux]
Output
Range
(VDC)
Output
Range
(VDC)
Fail-Safe/Fail-Secure
or Dry Form “C”
Outputs
ACM4 Board
Input Fuse Rating
ACM4 Board
10A/
250V
3A/
32V
Output Fuse Rating
ACM8 Board
Input Fuse Rating
10A/
250V
2.5A/
250V
Altronix
Model Number
T2KHK3F12
Power Supply Board
Input Fuse Rating
Power Supply Board
Battery Fuse Rating
120VAC 60Hz
5A/
10A/
250V
3.5 24VDC @ 5.4A 20.17-26.4 20.28-26.4 12
32V
Maximum Supply
Current for Main and
Aux. Outputs on
Power Supply board
and ACM4/ACM8
Access Power
Input Current (A)
Controllers’outputs
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and
authorities having jurisdiction. Product is intended for indoor use only.
1. Remove backplane from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners
and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper
screws, level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and
install the three fasteners. Place the enclosure’s upper keyholes over the three upper screws. Install the three lower
screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired location, opposite hinge.
Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 1, pg. 2).
Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device.
To activate alarm signal open the door of the enclosure.
4. Mount Kantech boards to TKH2 backplane, refer to page 3.
5. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow6NB and corresponding Sub-Assembly
Installation Guides for the following models: ACM8, ACM4 and T1618300K for further installation instructions.
ACM8 Board
Output Fuse Rating
- 2 - T2KHK3F12
Fig. 1