Altronix T2HNK7F8 Installation Guide

Page 1
Access & Power Integration
T2HNK7F8
8 Door Kit with Fused Outputs
Fully assembled kit includes:
- Trove2 enclosure with THN2 Altronix/Honeywell NetAXS backplane
- One (1) eFlow104NB - Power Supply/Charger
- One (1) ACM8 - Fused Access Power Controller
- One (1) VR6 - Voltage Regulator
All components of this Trove kit are UL Listed sub-assemblies. Please refer to the included corresponding Sub-Assembly Installation Guides for further information.
Installation Guide
All registered trademarks are property of their respective owners. More than just power.™
Rev. 040819
Installing Company: _____________________ Service Rep. Name: __________________________________________
Address: ________________________________________________________ Phone #: _________________________
Page 2
Overview:
Tamper Switch
(provided)
To Access Control Panel or UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Altronix T2HNK7F8 Trove Honeywell NetAXS kit is pre-assembled and consists of Trove2HN2 enclosure/backplane with factory installed Altronix power supply/charger and sub-assemblies. T2HNK7F8 kit also accommodates various combinations of Honeywell NetAXS boards for up to eight (8) doors in a single enclosure.
THN2 accommodates a combination of the following Honeywell NetAXS boards:
Up to two (2) NX4PCB access control panels.
Up to four (4) NetAXS-123 access control panels.
Up to four (4) NXD1 or NXD2 add-on boards to NetAXS-123.
Up to four (4) NX4IN or NX4OUT boards.
Configuration Chart:
Nominal DC Output
Voltage
[DC] [Aux]
Output
Range (VDC)
Output
Range (VDC)
Fail-Safe/Fail-Secure
or Dry Form “C”
Outputs
Additional Fused
Outputs
ACM8 Board
Input Fuse Rating
10A/
250V
ACM8 Board
Output Fuse Rating
PDS8 Board
Input Fuse Rating
2.5A/ 250V
10A/
32V
3A/
32V
Altronix Model Number
T2HNK7F8
Power Supply Board
Input Fuse Rating
Power Supply Board
Battery Fuse Rating
120VAC 60Hz
6.3A/
15A/
250V
4.5 24VDC @ 9.7A 20.17-26.4 20.28-26.4 8 8
32V
Maximum Supply
Current for Main and
Aux. Outputs on
Power Supply board
and ACM8 Access
Power Controllers’
Input Current (A)
outputs
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Remove backplane from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws, level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the three upper screws. Install the three lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired location, opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure, approximately 2” from the right side (Fig. 1, pg. 2). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the door of the enclosure.
4. Mount Honeywell NetAXS boards to THN2 backplane, refer to pages 3-5.
5. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow104NB and corresponding Sub-Assembly Installation Guides for the following models: ACM8, PDS8 and VR6 for further installation instructions.
Fig. 1
PDS8 Board
Output Fuse Rating
Hardware:
Nylon Spacer | 5/16” Pan Head Screw | Lock Nut
- 2 - T2HNK7F8
Page 3
Screw
1 2 3 4
ON
1 2 3 4
ON
Configuration of Honeywell NX4PCB Boards:
1. Align Honeywell NX4PCB boards on the backplane to match the boards’ mounting holes with corresponding pems.
2. Fasten spacers (provided) onto metal pems (Fig. 2a, pg. 3).
3. Mount Honeywell NX4PCB boards to spacers utilizing pan head screws (provided) (Fig. 2a, pg. 3). Note: Honeywell NX4PCB boards have one (1) RJ45 jack and one (1) switch each. Please make sure that they are mounted correctly, as shown in Fig. 2 below.
4. Fasten THN2 backplane to Trove2 enclosure utilizing hardware (provided).
Fig. 2
Altronix
eFlow104NB
L G N
TRIGGER
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4
F1 F2 F3 F4 F5 F6 F7 F8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
DM1 +
OFF
IN1 Fuse
IN1
10
IN2
+ INP1
IN2 Fuse
--
10
+ INP2
<
<
<
1 off 2
1 off 2
1 off 2
33333333
Out1
--
Out2
>
>
P
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
Common (--- )
N
DM2 +
1 2 3 4 5 6 7 8
Common Power Outputs (NEG)
>
INPUT
5 6 7 8
Altronix PDS8
<
<
<
1 off 2
1 off 2
1 off 2
Out3
Out4
Out5
>
>
>
FACP
ON
Altronix
ACM8
DM1 +
<
<
1 off 2
1 off 2
Out6
Out7
Out8
>
>
Common (--- )
DM2 +
Altronix VR6 mounted under PDS8
– DC +– BAT +
RJ45 Jack
Honeywell
NX4PCB
TRG
+INP- T + RET-
ON
1 2 3 4
FACP INTERFACE
1 2 3 4
NO C NC
MAIN
10A 250V
- + - +
Power Control
RJ45 Jack
Honeywell
NX4PCB
Fig. 2a
Pem
Spacer
Pan Head
Honeywell Access Controller
T2HNK7F8 - 3 -
Backplane
Page 4
Screw
Bottom of NXD1/NXD2
1 2 3 4
ON
1 2 3 4
ON
Configuration of Honeywell NetAXS-123 with or without NXD1/NXD2 Boards:
1. Align Honeywell NetAXS-123 boards on the backplane to match the boards’ mounting holes with corresponding pems.
2. Fasten spacers (provided) onto metal pems (Fig. 3a, pg. 4).
3. Mount Honeywell NetAXS-123 boards to spacers utilizing pan head screws (provided) (Fig. 3a, pg. 4). Note: Honeywell NetAXS-123 boards have one (1) RJ45 jack. Please make sure that they are mounted correctly, as shown in Fig. 3 below. In order to properly mount and connect NXD1/NXD2 do the following:
- prior to mounting on backplane, attach NXD1/NXD2 to the NetAXS-123 by connecting the multi-pin connector on the bottom of NXD1/NXD2 to the multi-pin jack on NetAXS-123. Make sure that pre-installed bump screws on NXD1/ NXD2 go through the corresponding holes in NetAXS-123.
- secure NXD1/NXD2 to NetAXS-123 using pre-installed bump screws and included spacers (Fig. 3b, pg. 4).
- after NXD1/NXD2 is firmly attached and connected to NetAXS-123, follow steps 1 and 2 above to mount them onto THN2.
4. Fasten THN2 backplane to Trove2 enclosure utilizing hardware (provided).
Fig. 3
Fig. 3a
Altronix
eFlow104NB
L G N
FACP
TRIGGER INPUT
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4
F1 F2 F3 F4 F5 F6 F7 F8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
DM1 +
+ INP1
IN2 Fuse
--
10
+ INP2
--
Common (--- )
DM2 +
5 6 7 8
OFF
IN1 Fuse
IN1
10
IN2
Altronix PDS8
<
<
<
<
1 off 2
1 off 2
Out2
Out3
>
>
Common Power Outputs (NEG)
<
1 off 2
1 off 2
Out4
Out5
>
>
1 off 2
33333333
Out1
>
P
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
N
1 2 3 4 5 6 7 8
ON
Altronix
ACM8
DM1 +
<
<
<
1 off 2
1 off 2
1 off 2
Out6
Out7
Out8
>
>
>
Common (--- )
DM2 +
Altronix VR6 mounted under PDS8
RJ45 Jack
– DC +– BAT +
Honeywell
NXD1 or NXD2
Pan Head
Honeywell Access Controller
Pem
Spacer
Backplane
Honeywell NetAXS-123
Fig. 3b
TRG
+INP- T + RET-
ON
FACP INTERFACE
1 2 3 4
1 2 3 4
NO C NC
MAIN
10A 250V
- + - + Power Control
RJ45 Jack
Honeywell
NXD1 or NXD2
Honeywell NetAXS-123
RJ45 Jack
Honeywell
NXD1 or NXD2
Mounting Hole
Pre-installed Bump Screw
Spacer
Bottom of NetAXS-123
Honeywell NetAXS-123
RJ45 Jack
Honeywell
NXD1 or NXD2
Honeywell NetAXS-123
- 4 - T2HNK7F8
Page 5
1 2 3 4
ON
1 2 3 4
ON
Configuration of Honeywell NX4IN or NX4OUT Boards:
Screw
1. Align Honeywell NX4IN or NX4OUT boards on the backplane to match the boards’ mounting holes with corresponding pems.
2. Fasten spacers (provided) onto metal pems (Fig. 4a, pg. 5).
3. Mount Honeywell NX4IN or NX4OUT boards to spacers utilizing pan head screws (provided) (Fig. 4a, pg. 5).
4. Fasten THN2 backplane to Trove2 enclosure utilizing hardware (provided).
Fig. 4
– DC +– BAT +
L G N
Altronix
eFlow104NB
Honeywell
NX4IN or NX4OUT
TRIGGER
1 2 3 4
F1 F2 F3 F4 F5 F6 F7 F8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
DM1 +
+ INP1
IN2 Fuse
--
10
+ INP2
--
Common (--- )
DM2 +
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
OFF
IN1 Fuse
IN1
10
IN2
<
<
1 off 2
1 off 2
33333333
Out1
Out2
>
>
P
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
N
1 2 3 4 5 6 7 8
Common Power Outputs (NEG)
INPUT
5 6 7 8
Altronix PDS8
<
<
<
1 off 2
>
<
1 off 2
1 off 2
1 off 2
Out3
Out4
Out5
>
>
>
Out6
FACP
ON
1 2 3 4
Altronix
ACM8
DM1 +
<
<
1 off 2
1 off 2
Out7
Out8
>
>
Common (--- )
DM2 +
Altronix VR6 mounted under PDS8
TRG
+INP- T + RET-
ON
FACP INTERFACE
1 2 3 4
NO C NC
Honeywell
MAIN
10A 250V
- + - +
Power Control
NX4IN or NX4OUT
Honeywell
NX4IN or NX4OUT
Honeywell
NX4IN or NX4OUT
Fig. 4a
Pem
Spacer
Pan Head
Honeywell Access Controller
T2HNK7F8 - 5 -
Backplane
Page 6
Notes:
- 6 - T2HNK7F8
Page 7
eFlow Power Supply/Chargers can be Controlled and Monitored while
Reporting Power/Diagnostics from Anywhere over the Network...
LINQ2 - Network Communication Module
LINQ2 provides remote IP access to real-time data from eFlow power supply/chargers to help keep systems up and running at optimal levels. It facilitates fast and easy installation and set-up, mini­mizes system downtime, and eliminates unnecessary service calls, which helps reduce Total Cost of Ownership (TCO) - as well as creating a new source of Recurring Monthly Revenue (RMR).
LINQ2
Features:
- UL Listed in the U.S. and Canada.
- Local or remote control of up to (2) two Altronix eFlow power output(s) via LAN and/or WAN.
- Monitor real time diagnostics: DC output voltage, output current, AC & battery status/service, input trigger state change, output state change and unit temperature.
- Access control and user managment: Restrict read/write, Restrict users to specific resources
- Two (2) integral network controlled Form “C” Relays.
- Three (3) programmable input triggers: Control relays and power supplies via external hardware sources.
- Email and Windows Dashboard notifications
- Event log tracks history.
- Secure Socket Layer (SSL).
- Programmable via USB or web browser - includes operating software and 6 ft. USB cable.
LINQ2 Mounts Inside any Trove Enclosure
LINQ2 Module
Network Connection:
Installation, Programming and Monitoring
Altronix eFlow
Power Supply
T2HNK7F8 - 7 -
Page 8
6.25” (158.8mm)
1.25” (31.8mm)
Enclosure Dimensions (H x W x D approximate):
27.25” x 21.75” x 6.5” (692.2mm x 552.5mm x 165.1mm)
21.50” (546.1mm)
2.00” (50.8mm) 2.00” (50.8mm)
1.25”
(31.8mm)
5.25” (133.35mm)
0.5625” (14.3mm)
3.5”(88.9mm) 3.5”(88.9mm)
1.77”
(45mm)
2.415” (61.3mm)
1.5”
(38.1mm)
19.80” (502.9mm)
5.25” (133.35mm)
0.685” (17.4mm)
Knockouts
1.125” (28.3mm)
0.885” (22.5mm)
6.25” (158.8mm)
2.00” (50.8mm)
6.75” (171.5mm)8.25” (209.5mm)
1.00” (25.4mm)
2.00” (50.8mm)
27” (685.8mm)
0.85” (21.6mm)
5.25” (133.4mm) 5.25” (133.4mm)7.00” (177.8mm)
8.00” (203.2mm)
2.00” (50.8mm)
1.25” (31.8mm)
1.25” (31.8mm)
2.00” (50.8mm)