Altronix T1RM3F4, T1RM3F4D Installation Guide

Page 1
Access & Power Integration
T1RM3F4
Fully assembled kit includes:
- Trove1R rack enclosure with Altronix/Mercury backplane (TM1R)
- (1) eFlow6NB - Power Supply/Charger
- (1) VR6 - Voltage Regulator
- (1) PDS8 - Fused Dual Output Power Distribution Module
- (1) ACM4 - Fused Access Power Controller
Fully assembled kit includes:
- Trove1R rack enclosure with Altronix/Mercury backplane (TM1R)
- (1) eFlow6NB - Power Supply/Charger
- (1) VR6 - Voltage Regulator
- (1) PDS8CB - PTC Dual Output Power Distribution Module
- (1) ACM4CB - PTC Access Power Controller
Installation Guide
All registered trademarks are property of their respective owners. More than just power.™
Rev. T1RM3F4080720
Installing Company: _____________________ Service Rep. Name: __________________________________________
Address: ________________________________________________________ Phone #: _________________________
Page 2
Overview:
Altronix T1RM3F4 and T1RM3F4D rack kits are pre-assembled and consist of Trove1M1R enclosure/backplane with factory installed Altronix power supply/charger and sub-assemblies. These kits also accommodate various combinations of Mercury boards for up to four (4) doors in a single enclosure.
Configuration Chart:
Altronix Model Number
T1RM3F4
T1RM3F4D
120VAC 60Hz
P/S Input Current (A)
Power Supply Board
Input Fuse Rating
Power Supply Board
5A/
250V
10A/
32V
3.5
Nominal DC
Output Voltage
[DC] [Aux]
Battery Fuse Rating
24VDC
Output
Range (V)
24VDC
20.28-
26.4
20.28-
26.4
Maximum Supply
Current for Main and
Aux. Outputs on
Power Supply board,
PDS8(CB) Power
Distribution Module
and ACM4(CB) Access
Power Controller’s
Output
outputs (A)
Range (V)
24VDC @ 5.6A
Current Per
ACM4 Output (A)
Current Per
ACM4CB Output (A)
ACM4(CB) Board
Input Fuse Rating
ACM4 Board
Output Fuse Rating
ACM4CB Board
Output PTC Rating
Fail-Safe/Fail-Secure or
Dry Form “C” Outputs
(ACM4 Only)
PDS8 Board
Input Fuse Rating
PDS8 Board
Output Fuse Rating
PDS8CB Board
Input PTC Rating
10A/
3A/
2.5
2.0 2.5A 9A 2.5A
10A/
250V
32V
4
32V
3A/
32V
PDS8 Board
Output Fuse Rating
Hardware and Accessories:
Spacer | 5/16” Pan Head Screw | Lock Nut
Specifications:
Agency Listings:
• CE European Conformity.
Mechanical:
• Black enclosure with ample knockouts for convenient access.
• Includes: tamper switch, cam lock and mounting hardware.
• Modular 2U standard EIA 19” drawer with extendable slides up to 48”.
• Dimensions (H x W x D): 3.25” x 19.0” x 26.5” (82.6mm x 482.6mm x 673.1mm).
Included Accessories:
• One (1) tamper switch (Altronix Model TS112 or equivalent).
• Cam lock.
Available Accessories (not included):
RE2: Rack Mount Battery Enclosure accommodates up to four (4) 12VDC/7AH batteries.
WM5, WM25, WM100: Magnetic Cable Tie Mounts (5, 25, 100 counts).
- 2 - T1RM3F4(D)
Page 3
Assembling and Attaching Z Bracket Wire Management Accessory (included):
Altronix Trove Rack enclosures include Z Bracket, a convenient and reliable wire management accessory.
1. Carefully unpack Z Bracket. Do not discard hardware (included) (Fig. 1, pg. 3).
2. Attach arms to each other using bolts and lock nuts (Fig. 1a, pg. 3).
3. Attach the hinge brackets to the ends of arms using bolts and nuts positioning them as shown on Fig. 1b, pg. 3.
4. Make sure that all nuts are tightened.
Hardware (included):
Ten (10) bolts and eight (8) lock nuts
Fig. 1a
5. Attach the hinge bracket on the longer side of Z Bracket to the adjustable rail using bolts and lock nuts (included) (Fig. 2, 2a, pg. 3).
6. Attach the hinge bracket on the shorter side of Z Bracket to the rear of the rack enclosure using bolts (included).
Fig. 2
Fig. 1
Two (2)
Fig. 1b
Fig. 2a
T1RM3F4(D) - 3 -
Page 4
Installation Instructions for T1RM3F4(D):
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Remove backplane from enclosure prior to installing into rack cabinet (do not discard hardware).
2. In order to mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) turn the enclosure upside down. Punch out the knockout in designated location, on the back of the unit, from outside of the drawer (Fig. 3, pg. 4). Insert the tamper switch into the knockout from outside of the drawer with the button facing outwards and spaded connectors inside the drawer. Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the rack drawer.
3. Slide the rack enclosure into an open 2U location in the four post rack cabinet.
4. Utilizing proper fasteners attach front ears to the rack rails.
5. Attach the rear of the adjustable slides to the rear rails of the rack cabinet with the proper fasteners.
6. Ensure that all internal cofigurations (voltage selection, switch settings, etc.) are completed before mounting backplane back into Trove rack enclosure.
7. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow6NB and corresponding sub-assembly Installation Guides for the following models: ACM4(CB), PDS8(CB), VR6 for further instructions.
Fig. 3
Back of the drawer,
viewed from outside.
Tamper Switch mounting location
- 4 - T1RM3F4(D)
Page 5
T1RM3F4(D): Configuration of Mercury Boards:
1. Fasten spacers onto metal pems configuration (A), (B), (C) or (D) of backplane depending on the access controller (Fig. 4, pg. 5).
2. Position access controller module over corresponding spacers and fasten screws into spacers (Fig. 4a, pg. 5).
3. Mount backplane to enclosure with hardware.
Access Controller Position Chart for the Following Models:
Mercury Access Controller Pem Mounting
EP1502, MR52, MR16IN, MR16OUT
EP2500, MUX8
EP1501, MR51e
MR50
Fig. 4
A
To IEC
connector
Pan Head Screw
A
B
C
D
Fig. 4a
B
B
A
D
C
C
L G N
eFlow6NB
NC C NO
AC FAIL
NC C NO
BAT FAIL
AC
DCAC1
1 min
enable
2 hr.
disable
TRIGGER EOL
SUPERVISED
NO GND
RESET
+ AUX ---
--- BAT + --- DC +
PWR1+
+ INP1 - + INP2 -
PDS8(CB)/VR6
P
OUT1
COM(-)
PWR1+
VR6 in mounted under PDS8(CB)
OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
N
1 2 3 4 5 6 7 8
Common Power Outputs (NEG)
Power Supply or Sub-Assembly
Spacer
Pem
Backplane
OFF - 24V ON - 12V
ON
PWR1+
P
N
COM(-)
PWR2+
D
IN GND
1
NC C NO COM
OUTPUT 1
IN GND3IN GND
IN GND
4
2
ACM4(CB)
NC C NO COM
OUTPUT 2
TRIGGER
INPUT
NC C NO COM
OUTPUT 3
NC C NO COM
OUTPUT 4
RoHS
TRG
INTERFACE
+ INP --- T + RET ---
FACP
NO C NC
Control
--- +
MAIN
Power
--- +
ACM4
ACCESS POWER CONTROLLER
T1RM3F4(D) - 5 -
Page 6
Notes:
- 6 - T1RM3F4(D)
Page 7
Notes:
T1RM3F4(D) - 7 -
Page 8
Trove1R Enclosure Dimensions (H x W x D):
3.25” x 19.0” x 26.5” (82.6mm x 482.6mm x 673.1mm). Shown with Z Bracket attached.
26.5”
673.1mm
2.4”
61mm
4.57”
116.1mm
1” (25.4mm)
11.175” (283.8mm)
0.55” (14mm)
R 1.27” (32.3mm)
0.1”
2.5mm
3.62”
92mm
1.5”
38.1mm
19” (482.6mm)
3.25”
82.3mm
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056 web site: www.altronix.com | e-mail: info@altronix.com | Made in U.S.A. IIT1RM3F4(D) H20T
- 8 - T1RM3F4(D)