Altronix T1RAL33F16, T1RAL3F8 Installation Guide

Access & Power Integration
T1RAL3F8
8 Door Kit with Fused Outputs
Fully assembled kit includes:
- Trove1R rack enclosure with Altronix backplane (TAL1R)
- (1) eFlow6NB - Power Supply/Charger
- (1) VR6 - Voltage Regulator
- (1) PDS8 - Fused Dual Output Power Distribution Module
T1RAL33F16
16 Door Kit with Fused Outputs
Fully assembled kit includes:
- Trove1R rack enclosure with Altronix backplane (TAL1R)
- (2) eFlow6NB - Power Supply/Chargers
- (2) ACMS8 - Fused Dual Output Access Power Controllers
Installation Guide
All registered trademarks are property of their respective owners. More than just power.™
Rev. T1RAL111518
Installing Company: _____________________ Service Rep. Name: __________________________________________
Address: ________________________________________________________ Phone #: _________________________
Overview:
Altronix Trove Rack kits are pre-assembled and consist of Trove1AL1R enclosure/backplane with factory installed Altronix power supply/ charger(s) and sub-assemblies.
Configuration Chart:
Maximum Supply
Current for Main and Aux. Outputs
on Power Supply
board and ACMS8
Access Power
Controllers’ outputs
24VDC @ 5.6A 8 2.5
24VDC @ 5.6A
12VDC @ 5.3A
Fail-Safe/
Fail-Secure or Dry Form “C” Outputs
16 2.5
Current
Per
ACMS8
Output
(A)
ACMS8
Board
Input
Fuse
Rating
15A/
32V
15A/
32V
ACMS8
Board
Output
Fuse
Rating
3A/
32V
3A/
32V
PDS8
Board
Input
Fuse
Rating
10A/
32V
PDS8
Board
Output
Fuse
Rating
3A/
32V
Altronix Model Number
T1RAL3F8
T1RAL33F16
120VAC
60Hz
Input
Current
(A)
3.5
7
Power
Supply
Board
Input
Fuse
Rating
5A/
250V
5A/
250V
Power
Supply
Board
Battery
Fuse
Rating
10A/
32V
10A/
32V
Nominal DC
Output Voltage
[DC] [Aux]
Output
Range
(VDC)
20.19-
20.19-
10.0-
Output
Range (VDC)
26.4
26.4
13.2
20.19-
26.4
Power Supply 1 (24VDC)
20.19-
26.4
Power Supply 2 (12VDC)
10.1-
13.2
Specifications:
Agency Listings:
• CE European Conformity.
Mechanical:
• Black enclosure with ample knockouts for convenient access.
• Includes: tamper switch, cam lock and mounting hardware.
• Modular 2U standard EIA 19” drawer with extendable slides up to 48”.
• Dimensions (H x W x D): 3.25” x 19.0” x 26.5” (82.6mm x 482.6mm x 673.1mm).
Included Accessories:
• One (1) tamper switch (Altronix Model TS112 or equivalent).
• Cam lock.
Available Accessories (not included):
RE2: Rack Mount Battery Enclosure accommodates up to four (4) 12VDC/7AH batteries.
WM5, WM25, WM100: Magnetic Cable Tie Mounts (5, 25, 100 counts).
- 2 - Trove1RAL Series
Assembling and Attaching Z Bracket Wire Management Accessory (included):
Altronix Trove Rack enclosures include Z Bracket, a convenient and reliable wire management accessory.
1. Carefully unpack Z Bracket. Do not discard hardware (included) (Fig. 1, pg. 3).
2. Attach arms to each other using bolts and lock nuts (Fig. 1a, pg. 3).
3. Attach the hinge brackets to the ends of arms using bolts and nuts positioning them as shown on Fig. 1b, pg. 3.
4. Make sure that all nuts are tightened.
Hardware (included):
Ten (10) bolts and eight (8) lock nuts
Fig. 1a
5. Attach the hinge bracket on the longer side of Z Bracket to the adjustable rail using bolts and lock nuts (included) (Fig. 2, 2a, pg. 3).
6. Attach the hinge bracket on the shorter side of Z Bracket to the rear of the rack enclosure using bolts (included).
Fig. 2
Fig. 1
Two (2)
Fig. 1b
Fig. 2a
Trove1RAL Series - 3 -
Installation Instructions for Altronix Trove Rack Kits:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Remove backplane from enclosure prior to installing into rack cabinet (do not discard hardware).
2. In order to mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) turn the enclosure upside down. Punch out the knockout in designated location, on the back of the unit, from outside of the drawer (Fig. 3, pg. 4). Insert the tamper switch into the knockout from outside of the drawer with the button facing outwards and spaded connectors inside the drawer. Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the rack drawer.
3. Slide the rack enclosure into an open 2U location in the four post rack cabinet.
4. Utilizing proper fasteners attach front ears to the rack rails.
5. Attach the rear of the adjustable slides to the rear rails of the rack cabinet with the proper fasteners.
6. Ensure that all internal cofigurations (voltage selection, switch settings, etc.) are completed before mounting backplane back into Trove rack enclosure.
7. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow6NB and corresponding sub-assembly Installation Guides for the following models: ACMS8, PDS8, VR6 for further instructions.
Fig. 3
Back of the drawer,
viewed from outside.
Tamper Switch mounting location
- 4 - Trove1RAL Series
Fig. 4
T1RAL3F8 Configuration
To IEC connector
+ INP1 - + INP2 -
Common(-)
DM2+
N
1 2 3 4 5 6 7 8
P
OUT1
OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
DM1+
IN2 Fuse
Fuse1
Fuse2 Fuse3 Fuse4 Fuse5 Fuse6 Fuse7 Fuse8
IN1 Fuse
L G N
eFlow6NB
24VDC
Common Power Outputs (NEG)
P
N
Common(-)
DM2+
VR6/PDS8
COM--
NO C NC COM NO C NC COM
Output 1Output 2
NO C NC COM NO C NC COM
RISK OF FIRE REPLACE FUSES WITH SAME TYPE AND RATING
Output 3 Output 4
OFF
PWR2
PWR1
PWR1
PWR2
<-- >
Power 2
15
3
3
ON
PWR1
PWR2
NO
<-- >
8
INP Logic
3
<-- >
NC
ACMS8
ACMS8CB
15
Power 1
ON
4
567
PDS8
Power Distribution
Dual Voltage
Module
DM1+
+PWR1-- +PWR2--
PWR2+
PWR1+
123
+INP2--+INP1-- +INP3-- +INP4-- +INP5-- +INP6-- +INP7-- +INP8--
NC C NO
AC FAIL
NC C NO
BAT FAIL
AC
DCAC1
1 min
enable
2 hr.
disable
TRIGGER EOL
SUPERVISED
NO GND
RESET
+ AUX ---
--- BAT + --- DC +
OFF - 24V ON - 12V
ON
PWR1
PWR2
<-- >
3
NO C NC COM NO C NC COM
Output 5 Output 6
3
3
NO C NC COM NO C NC COM
Output 7 Output 8
3
3
COM--
PWR2
PWR2
<-- >
EN <-- >
FACP
DIS
<-- >
FACP
OUT1
OUT2
OUT3
OUT4
PWR1
OUT5
OUT6
OUT7
OUT8
8
ONON
PWR1
EOL JMP
NC RST EOL +F +R
C GND GND -F -R
1234567
FACP
PWR2+
PWR1+
FACP
ACMS8
Trove1RAL Series - 5 -
Fig. 5
T1RAL33F16 Configuration
ACMS8
ACMS8CB
+PWR1-- +PWR2--
To IEC
connector
PWR2+
PWR1+
COM--
NO C NC COM NO C NC COM
Output 1Output 2
OFF
PWR2
PWR1
PWR1
PWR2
<-- >
Power 2
3
15
L G N
<-- >
PWR2
PWR2
PWR2
PWR1
NO
INP Logic
<-- >
NC
<-- >
<-- >
EN <-- >
FACP
DIS
<-- >
FACP
15
Power 1
ON
ON
4
567
8
PWR1
OUT1
OUT2
OUT3
OUT4
PWR1
OUT5
OUT6
OUT7
OUT8
8
ONON
PWR1
EOL JMP
NC RST EOL +F +R
C GND GND -F -R
eFlow6NB
123
+INP2--+INP1-- +INP3-- +INP4-- +INP5-- +INP6-- +INP7-- +INP8--
NC C NO
AC FAIL
NC C NO
BAT FAIL
AC
1234567
FACP
PWR2+
PWR1+
FACP
enable
2 hr.
disable
TRIGGER EOL
SUPERVISED
NO GND
RESET
+ AUX ---
DCAC1
1 min
24VDC
--- BAT + --- DC +
OFF - 24V ON - 12V
ON
3
NO C NC COM NO C NC COM
RISK OF FIRE REPLACE FUSES WITH SAME TYPE AND RATING
Output 3 Output 4
PWR2
3
3
NO C NC COM NO C NC COM
Output 5Output 6
3
3
NO C NC COM NO C NC COM
Output 7 Output 8
3
3
COM--
ACMS8
ACMS8
ACMS8CB
Power 1
ON
4
ONON
EOL JMP
+PWR1-- +PWR2--
PWR2+
PWR1+
L G N
123
+INP2--+INP1-- +INP3-- +INP4-- +INP5-- +INP6-- +INP7-- +INP8--
eFlow6NB
12VDC
NC C NO
AC FAIL
NC C NO
BAT FAIL
enable
2 hr.
disable
TRIGGER EOL
SUPERVISED
NO GND
RESET
+ AUX ---
AC
DCAC1
1 min
OFF - 24V ON - 12V
ON
1234567
FACP
PWR2+
PWR1+
FACP
3
3
3
PWR2
3
3
3
3
3
PWR2
<-- >
PWR2
PWR2
PWR2
OFF
PWR2
PWR1
PWR1
<-- >
PWR1
NO
INP Logic
<-- >
NC
<-- >
PWR1
<-- >
EN
<-- >
FACP
DIS
PWR1
<-- >
FACP
Power 2
15
15
ON
567
8
PWR1
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
8
NC RST EOL +F +R
C GND GND -F -R
COM--
NO C NC COM NO C NC COM
Output 1Output 2
NO C NC COM NO C NC COM
RISK OF FIRE REPLACE FUSES WITH SAME TYPE AND RATING
Output 3 Output 4
NO C NC COM NO C NC COM
Output 5 Output 6
NO C NC COM NO C NC COM
Output 7 Output 8
COM--
ACMS8
--- BAT + --- DC +
- 6 - Trove1RAL Series
Notes:
Trove1RAL Series - 7 -
Trove1R Enclosure Dimensions (H x W x D):
3.25” x 19.0” x 26.5” (82.6mm x 482.6mm x 673.1mm). Shown with Z Bracket attached.
26.5”
673.1mm
2.4”
61mm
4.57”
116.1mm
1” (25.4mm)
11.175” (283.8mm)
0.55” (14mm)
R 1.27” (32.3mm)
0.1”
2.5mm
3.62”
92mm
1.5”
38.1mm
19” (482.6mm)
3.25”
82.3mm
Altronix is not responsible for any typographical errors.