Altronix T1RAL13F8P8 Trove Rack kit is pre-assembled and consist of Trove1AL1R enclosure/backplane with factory installed Altronix
power supply/chargers and sub-assemblies.
Configuration Chart:
Nominal DC
Altronix
Model
Number
T1RAL13F8P8
120VAC
60Hz
Input
Current
(A)
7
Power
Supply
Boards’
Input
Fuse
Rating
5A/
250V
Power
Supply
Boards’
Battery
Fuse
Rating
10A/
32V
Output Voltage
[DC][Aux]
Output
Range
(VDC)
20.19-
10.0-
Output
Range
(VDC)
Power Supply 1 (24VDC)
26.4
13.2
20.19-
26.4
Power Supply 2 (12VDC)
10.1-
13.2
Maximum Supply
Current for Main
and Aux. Outputs
on Power Supply
board and ACM8
Access Power
Controller’s outputs
24VDC @ 5.7A
12VDC @ 4A
Fail-Safe/
Fail-Secure
or Dry
Form “C”
Outputs
Additional
Fuse
Protected
Outputs
882.5A
Current Per
ACM8 Output
ACM8 Board
Input Fuse Rating
15A/
32V
ACM8 Board
Output Fuse Rating
PD8UL Board
Input Fuse Rating
3.5A/
250V
–
PD8UL Board
Output Fuse Rating
3.5A/
250V
Specifications:
Agency Listings:
• CE European Conformity.
Mechanical:
• Black enclosure with ample knockouts for convenient access.
• Includes: tamper switch, cam lock and mounting hardware.
• Modular 2U standard EIA 19” drawer with
extendable slides up to 48”.
• Dimensions (H x W x D): 3.25” x 19.0” x 26.5”
(82.6mm x 482.6mm x 673.1mm).
Included Accessories:
• One (1) tamper switch (Altronix Model TS112 or equivalent).
• Cam lock.
Available Accessories (not included):
• RE2: Rack Mount Battery Enclosure
accommodates up to four (4) 12VDC/7AH batteries.
• WM5, WM25, WM100: Magnetic Cable Tie Mounts
(5, 25, 100 counts).
- 2 - T1RAL13F8P8
Assembling and Attaching Z Bracket Wire Management Accessory (included):
Altronix Trove Rack enclosures include Z Bracket, a convenient and reliable wire management accessory.
1. Carefully unpack Z Bracket. Do not discard hardware (included) (Fig. 1, pg. 3).
2. Attach arms to each other using bolts and lock nuts (Fig. 1a, pg. 3).
3. Attach the hinge brackets to the ends of arms using bolts and nuts positioning them as shown on Fig. 1b, pg. 3.
4. Make sure that all nuts are tightened.
Hardware (included):
Ten (10) bolts and eight (8) lock nuts
Fig. 1a
5. Attach the hinge bracket on the longer side of Z Bracket to the adjustable rail using bolts and lock nuts (included) (Fig. 2, 2a, pg. 3).
6. Attach the hinge bracket on the shorter side of Z Bracket to the rear of the rack enclosure using bolts (included).
Fig. 2
Fig. 1
Two (2)
Fig. 1b
Fig. 2a
T1RAL13F8P8 - 3 -
Installation Instructions for T1RAL13F8P8:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having
jurisdiction. Product is intended for indoor use only.
1. Remove backplane from enclosure prior to installing into rack cabinet (do not discard hardware).
2. In order to mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) turn the enclosure upside down.
Punch out the knockout in designated location, on the back of the unit, from outside of the drawer (Fig. 3, pg. 3).
Insert the tamper switch into the knockout from outside of the drawer with the button facing outwards and spaded connectors inside
the drawer. Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device.
To activate alarm signal open the rack drawer.
3. Slide the Trove rack enclosure into an open 2U location in the rack cabinet.
4. Utilizing proper fasteners attach front ears to the rack rails.
5. Attach the rear of the adjustable slides to the rear rails of the rack cabinet with the proper fasteners.
6. Make sure that all internal cofigurations (wiring, voltage selection, switch settings, etc.) are complete before mounting backplane back
into enclosure.
7. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow4NB and eFlow6NB, and corresponding sub-assembly
Installation Guides for ACM8(CB) and PD8UL for further instructions.
Fig. 3
Back of the drawer,
viewed from outside.
Tamper Switch mounting location
- 4 - T1RAL13F8P8
Fig. 4
1 2 3 4
ON
1 2 3 4
ON
T1RAL13F8P8 Configuration
To IEC connector
FACP
TRIGGER
TRG
INPUT
+INP- T + RET-
ON
ON
Altronix
PD8UL
1 2 3 4 5 6 7 8
FACP INTERFACE
NO C NC
1 2 3 4
Altronix
1 2 3 4
ACM8
MAIN
P
10A 250V
LED
INPUT
D1
R1
P N
L G N
Altronix
eFlow4NB
12VDC
NC C NO
AC FAIL
NC C NO
BAT FAIL
AC
enable
2 hr.
disable
TRIGGER EOL
SUPERVISED
NO GND
RESET
+ AUX ---
DCAC1
1 min
--- BAT +--- DC +
FUSED POWER OUTPUTS
COMMON POWER OUTPUTS
N
Power Control
- + - +
OFF - 24V
ON - 12V
ON
To IEC connector
L G N
Altronix
eFlow6NB
24VDC
5 6 7 8
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
NC C NO
AC FAIL
NC C NO
BAT FAIL
AC
DCAC1
1 min
enable
2 hr.
disable
TRIGGER EOL
SUPERVISED
NO GND
RESET
+ AUX ---
--- BAT +--- DC +
OFF - 24V
ON - 12V
ON
T1RAL13F8P8 - 5 -
Notes:
- 6 - T1RAL13F8P8
TAL1R Dimensions:
18.5” x 15.25” x 0.3125” (469.9mm x 387.4mm x 7.9mm)
15.25” (387.4mm)
18.5”
469.9mm
T1RAL13F8P8 - 7 -
Trove1R Enclosure Dimensions (H x W x D):
3.25” x 19.0” x 26.5” (82.6mm x 482.6mm x 673.1mm). Shown with Z Bracket attached.
26.5”
673.1mm
2.4”
61mm
4.57”
116.1mm
1” (25.4mm)
11.175” (283.8mm)
0.55” (14mm)
R 1.27” (32.3mm)
0.1”
2.5mm
3.62”
92mm
1.5”
38.1mm
19” (482.6mm)
3.25”
82.3mm
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
web site: www.altronix.com | e-mail: info@altronix.com | Made in U.S.A.
IIT1RAL13F8P8 H21T