Altronix T1RAG3F8 Specsheet

T1RAG3F8
Trove / AMAG M4000 Kit
Access & Power Integration Solution
Description
Altronix T1RAG3F8 Trove™ Rack kit is pre-assembled and consists of
Trove1AG1R enclosure/backplane with the following factory installed
Altronix components:
- One (1) eFlow6NB - power supply/charger set at 24VDC;
- One (1) VR6 - Voltage Regulator;
- One (1) ACMS8 - Fused Dual Input/Output Access Power Controller;
This kit also accommodates various combinations of AMAG Symmetry
M4000 boards for up to eight (8) doors in a single enclosure.
Key Features
T1RAG3F8
- Output Power:
- Eight (8) 24VDC fused lock power outputs rated at 6A total max.
- Fire Alarm Disconnect is individually selectable by output.
- Accommodates the following AMAG Symmetry M4000 boards: M4000-DEC4, M4000-IOC20/16.
- Power status LED on front panel.
- Simplified board layout and wire management.
- Convenient knockout configuration:
- Six (6) 1.25” diameter knockouts located on the back of enclosure.
*Altronix Power Supply/Charger and Sub-Assemblies only
- 6’ IEC320 3-wire power cord.
- 2U drawer on extendable rails.
- Black powder coated steel enclosure.
- Included Z Bracket facilitates ease of wiring.
- Includes cam lock, tamper switch and mounting hardware.
- CE European Conformity.
- Lifetime Warranty* / Made in the U.S.A.
Optional Accessories
- RE2: Rack Mount Battery Enclosure accommodates up to four (4) 12VDC/7AH batteries.
- WM5, WM25, WM100: Magnetic Cable Tie Mounts (5, 25, 100 counts).
Rev. T1RAG3F8 - 07272020
T1RAG3F8
Trove / AMAG M4000 Kit
Access & Power Integration Solution
Specifications
Power Supply (eFlow6NB):
Input
Voltage 120VAC, 60Hz, 3.5A max. Main Fuse 5A / 250V.
Outputs
Voltage Factory set at 24VDC. Current 6A continuous. Auxiliary Class 2 power-limited @ 1A (unswitched). Other Overvoltage protection.
Filtered and regulated.
Battery Backup
Type Sealed lead acid or gel type. Fuse Rating 10A @ 32VDC. Failover Upon AC loss, instantaneous.
Fire Alarm Disconnect
Supervised Latching or non-latching. EOL 10K Resistor.
Supervision
AC Failure Form “C” contacts. Battery Form “C” contacts. Low DC Power Shutdown
Shuts down DC output terminals if battery voltage drops below 70-75% for 24V units. Prevents deep battery discharge.
Indicators (LED)
Input 120VAC is present. DC Output Powered. Battery Discharged or not connected.
Voltage Regulator (VR6):
Input
Voltage 24VDC from eFlow6NB.
Output
Voltage 12VDC. Current 6A continuous. Other Surge suppression.
Indicators (LED)
Input 24VDC is present. Output Powered.
Dual Input Access Power Controller (ACMS8):
Input
Voltage 24VDC from eFlow6NB and 12VDC from VR6. Input Fuse 15A/32V.
Outputs
Voltage 12 or 24VDC individually selectable. Eight (8) selectable 12VDC - 24VDC independently controlled
outputs or eight (8) indepently controlled Form “C” relay outputs: a) Fail-Safe and/or Fail-Secure power outputs. b) Form “C” Relays. 28VAC or VDC @ 2.5A Rated. c) Auxiliary power outputs (unswitched). d) Any combination of the above. Any of the eight (8) fuse protected power outputs are selectable
to follow power Input 1 or Input 2. Individual outputs may be set to OFF position for servicing. Output Fuses 3A/32VDC.
Indicators (LED)
Red LEDs Outputs are triggered (relays energized). Blue LED FACP disconnect is triggered. Individual voltage LEDs:
Green: 12VDC Red: 24VDC.
T1RAG3F8 Kit:
Agency Listings
CE European Conformity.
Physical and Environmental:
Dimensions (H x W x D): Modular 2U standard EIA 19” rack mount chassis.
3.25” x 19.0” x 26.5” (82.6mm x 482.6mm x 673.1mm).
Weights:
Product 20 lbs. (9.07 kg). Shipping 25 lbs. (11.34 kg).
Temperature Operating 0ºC to 49ºC (32ºF to 120ºF). Storage -20ºC to 70ºC (-4ºF to 158ºF). Relative Humidity 85% +/-5%. BTU/Hr.: 115 BTU/Hr.
Loading...