Altronix T1RAG3F8 Installation Guide

Access & Power Integration
T1RAG3F8
Fully assembled kit includes:
- Trove1R rack enclosure with T1AG1R Altronix/AMAG backplane
- (1) eFlow6NB - Power Supply/Charger
- (1) VR6 - Voltage Regulator
- (1) PDS8 - Fused Dual Output Power Distribution Module
- (1) ACM4 - Fused Access Power Controller
All registered trademarks are property of their respective owners. More than just power.™
Rev. T1RAG3F8_110419
Installing Company: _____________________ Service Rep. Name: __________________________________________
Address: ________________________________________________________ Phone #: _________________________
Overview:
Altronix T1RAG3F8 Trove rack kit is pre-assembled and consist of Trove rack enclosure/backplane with factory installed Altronix power supply/charger and sub-assemblies. Kits accommodate up to two (2) AMAG M4000 modules for up to eight (8) doors in a single enclosure.
Configuration Chart:
Nominal DC
Output Voltage
[DC] [Aux]
Output
Range (VDC)
20.17-
26.4
Output
Range (VDC)
20.28-
26.4
Maximum Supply
Current for Main and
Aux. Outputs on Power
Supply board and
ACMS8 Access Power
Controller’s outputs
24VDC @ 5.4A 8
Fail-Safe/
Fail-Secure
or Dry
Form “C”
Outputs
ACMS8
Board
Input
Fuse
Rating
15A/
32V
ACMS8
Board
Output
Fuse
Rating
3A/
32V
Altronix Model Number
T1RAG3F8
Power
Supply
120VAC
60Hz
Input
Current
3.5A 5A/250V
Board
Input
Fuse
Rating
Power
Supply
Board
Battery
Fuse
Rating
15A/
32V
Hardware and Accessories:
Spacer | 5/16” Pan Head Screw | Lock Nut
Specifications:
Agency Listings:
• CE European Conformity.
Mechanical:
• Black enclosure with ample knockouts for convenient access.
• Includes: tamper switch, cam lock and mounting hardware.
• Modular 2U standard EIA 19” drawer with extendable slides up to 48”.
• Dimensions (H x W x D): 3.25” x 19.0” x 26.5” (82.6mm x 482.6mm x 673.1mm).
Included Accessories:
• One (1) tamper switch (Altronix Model TS112 or equivalent).
• Cam lock.
Available Accessories (not included):
RE2: Rack Mount Battery Enclosure accommodates up to four (4) 12VDC/7AH batteries.
WM5, WM25, WM100: Magnetic Cable Tie Mounts (5, 25, 100 counts).
- 2 - T1RAG3F8
Assembling and Attaching Z Bracket Wire Management Accessory (included):
Altronix Trove Rack enclosures include Z Bracket, a convenient and reliable wire management accessory.
1. Carefully unpack Z Bracket. Do not discard hardware (included) (Fig. 1, pg. 3).
2. Attach arms to each other using bolts and lock nuts (Fig. 1a, pg. 3).
3. Attach the hinge brackets to the ends of arms using bolts and nuts positioning them as shown on Fig. 1b, pg. 3.
4. Make sure that all nuts are tightened.
Hardware (included):
Ten (10) bolts and eight (8) lock nuts
Fig. 1a
5. Attach the hinge bracket on the longer side of Z Bracket to the adjustable rail using bolts and lock nuts (included) (Fig. 2, 2a, pg. 3).
6. Attach the hinge bracket on the shorter side of Z Bracket to the rear of the rack enclosure using bolts (included).
Fig. 2
Fig. 1
Two (2)
Fig. 1b
Fig. 2a
T1RAG3F8 - 3 -
Installation Instructions for T1RAG3F8:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Remove backplane from enclosure prior to installing into rack cabinet (do not discard hardware).
2. In order to mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) turn the enclosure upside down. Punch out the knockout in designated location, on the back of the unit, from outside of the drawer (Fig. 3, pg. 3). Insert the tamper switch into the knockout from outside of the drawer with the button facing outwards and spaded connectors inside the drawer. Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the rack drawer.
3. Slide the Trove rack enclosure into an open 2U location in the rack cabinet.
4. Utilizing proper fasteners attach front ears to the rack rails.
5. Attach the rear of the adjustable slides to the rear rails of the rack cabinet with the proper fasteners.
6. Make sure that all internal cofigurations (wiring, voltage selection, switch settings, etc.) are complete before mounting backplane back into enclosure.
7. After all components are mounted on the backplane, attach it to the enclosure using included hardware.
8. Mount AMAG M4000 modules to TAG1R backplane, refer to page 5.
9. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow6NB and corresponding Sub-Assembly Installation Guides for the following models: ACMS8 and VR6 for further installation instructions.
Fig. 3
Back of the drawer,
viewed from outside.
Tamper Switch mounting location
- 4 - T1RAG3F8
T1RAG3F8: Configuration of AMAG M4000 Modules:
1. Align the AMAG M4000 modules on the backplane to match the boards’ mounting holes with corresponding pems.
2. Fasten spacers (provided) onto metal pems (Fig. 4a, pg. 3).
3. Mount AMAG M4000 modules to spacers utilizing pan head screws (provided) (Fig. 4a, pg. 3).
4. Fasten TAG1R backplane to Trove1R rack enclosure utilizing hardware (provided).
Position Chart for the Following Models:
M4000 Pem Mounting
M4000-DEC4, M4000-IOC20/16
Fig. 4
A
To IEC
connector
L G N
NC C NO
AC FAIL
NC C NO
BAT FAIL
AC
DCAC1
enable
2 hr.
disable
TRIGGER EOL
SUPERVISED
NO GND
RESET
+ AUX ---
Pan Head Screw
Power Supply or Sub-Assembly
eFlow6NB
Spacer
Pem
Backplane
OFF - 24V ON - 12V
1 min
ON
A
Fig. 4a
A
+
PWR2
+
PWR1
+
+
PWR2
PWR1
--- BAT + --- DC +
ACMS8
--
--
+ PWR2
+ PWR1
COM -
VR6 is
mounted
under
ACMS8
COM -
T1RAG3F8 - 5 -
Notes:
- 6 - T1RAG3F8
Notes:
T1RAG3F8 - 7 -
T1RAG3F8 Enclosure Dimensions (H x W x D):
3.25” x 19.0” x 26.5” (82.6mm x 482.6mm x 673.1mm). Shown with Z Bracket attached.
26.5”
673.1mm
2.4”
61mm
4.57”
116.1mm
1” (25.4mm)
11.175” (283.8mm)
0.55” (14mm)
R 1.27” (32.3mm)
0.1”
2.5mm
3.62”
92mm
1.5”
38.1mm
19” (482.6mm)
3.25”
82.3mm
Altronix is not responsible for any typographical errors.