![](/html/a4/a457/a4571561a5bd095653f67432689c1366ef67b67a3f5529138fd14c4bc471d8eb/bg1.png)
T1CVK3F4
Access & Power Integration Solution
Description
Altronix T1CVK3F4 kit consists of Trove1 enclosure, TC1 CDVI/Altronix backplane
with one (1) 12 or 24VDC @ 6A power supply/charger and one (1) fused access
power controller. This kit also accommodate various combinations of CDVI Atrium
A22K/A22NB/ADH10 boards for up to four (4) doors in a single enclosure. Trove sim-
plifies board layout and wire management, reduces installation time and labor costs.
Key Features
T1CVK3F4
- 12 or 24VDC power supply/charger.
- Accommodates up to two (2) CDVI Atrium
A22K/A22NB/ADH10 boards.
- Convenient knockout configuration:
- Single 1.5” diameter knockout located top center of enclosure
- Nine (9) double knockouts (1” and 0.75”).
- 16 AWG galvanized steel backplane simplifies board layout
and wire management.
*Altronix Power Supply/Chargers and Sub-Assemblies only
Accessories (order separately)
LINQ2 - Network Supervision
Altronix LINQ2 Network Communication Module provides remote supervision, control and monitoring over LAN/WAN
- Remotely reports accurate power diagnostics
- Controls power and resets devices
- Reports system diagnostics via Email
LINQ2
WM5, WM25, WM100 - Magnetic Cable Tie Mounts
Altronix WM5, WM25, and WM100 are packs of 5, 25 or 100 magnetic cable tie mounts respectively.
They accommodate standard zip ties or velcro straps. These are ideal for wire management in our Trove series.
WM5
- Supervision
- AC Fail
- Low Battery and Battery Presence
- Low power shutdown.
- CE European Conformity.
- Enclosure accommodates up to two (2) 12VDC/7AH batteries.
- Lifetime Warranty*/Made in the U.S.A.
Mounting Magnet
MM4, MM8, MM12, MM24 - Magnetic Mounting Solution
Altronix mounting magnets accommodate screws and nylon standoffs to allow for mounting various boards/
accessories in any metal enclosure or backplane.
Rev. T1CVK3F4 - 03162020
![](/html/a4/a457/a4571561a5bd095653f67432689c1366ef67b67a3f5529138fd14c4bc471d8eb/bg2.png)
T1CVK3F4
Access & Power Integration Solution
Specifications
Power Supply/Charger (eFlow 6NB):
Input
Voltage 120VAC, 60Hz, 3.5A max.
Input Fuse 5A/250V.
Outputs
Voltage 12VDC or 24VDC selectable.
Current 6A continuous max.
Auxiliary Power-limited @ 1A (unswitched).
Other Overvoltage protection. Filtered and regulated.
Back-up Battery (not included)
Type Sealed lead acid or gel type.
Fuse Rating 10A @ 32VDC.
Failover Upon AC loss, instantaneous.
Fire Alarm Disconnect
Supervised Latching or non-latching.
EOL 10K Resistor.
Supervision
AC Failure Form “C” contacts.
Battery Form “C” contacts.
Low DC Power Shutdown
Shuts down DC output terminals if battery voltage drops below
71-73% for 12V units and 70-75% for 24V units
(depending on the power supply). Prevents deep battery discharge.
Indicators (LED)
Input 120VAC is present.
DC Output Powered.
Access Power Controller (ACM4):
Input
Voltage 12VDC or 24VDC from eFlow6NB.
Input Fuse 10A/32V.
Outputs
Voltage 24VDC.
Four (4) independently controlled 2.5A outputs:
a) Four (4) Fail-Safe and/or Fail-Secure power outputs.
b) Four (4) dry form “C” 5A rated relay outputs.
c) Any combination of the above.
Four (4) auxiliary power outputs (unswitched).
Output Fuses 3A/32VDC.
Indicators (LED)
Red LEDs Outputs are triggered (relays energized).
Green LED FACP disconnect is triggered.
T1CVK3F4 Kit:
Agency Listings
All components of this Trove kit are UL Listed sub-assemblies.
Please refer to the corresponding Sub-Assembly Installation Guides for
further information.
CE European Conformity.
Physical and Environmental
Dimensions (H x W x D)
18” x 14.5” x 4.62” (457.2mm x 368.3mm x 118.0mm).
Weight (approx.)
Product 15.5 lb. (7.0 kg).
Shipping 19.5 lb. (8.9 kg).
Temperature
Operating 0ºC to 49ºC (32ºF to 120ºF).
Storage -20ºC to 70ºC (-4ºF to 158ºF).
Relative Humidity 85% +/-5%.
BTU/Hr (approx.):
12VDC: 40 BTU/Hr.
24VDC: 77 BTU/Hr.