Altronix SMP7PMP8CB Installation Instructions

Page 1
SMP7CTX Series - Installation Guide
SMP7CTX Series Power Supply Configuration Reference Chart:
ower
Model Number
Altronix
SMP7CTX - 1 - - - - 1.45 6
SMP7PMCTX - 1 - - - x 1.45 6
SMP7PMP4 PD4 4 x - 3.5 x 1.45 6
SMP7PMP4CB PD4CB 4 - x 2.5 x 1.45 6
SMP7PMP8 PD8 8 x - 3.5 x 1.45 6
SMP7PMP8CB PD8CB 8 - x 2.5 x 1.45 6
SMP7PMP16 PD16W 16 x - 3.5 x 1.45 6
SMP7PMP16CB PD16WCB 16 - x 2.5 x 1.45 6
Distribution
Accessory P
Module(s)
Number of Outputs
Fused Outputs
Individual
PTC Outputs
Output Rating (amp)
Supervised
115VAC / 60Hz
12/24VDC Total
Input Current (amp)
Output Current (amp)
Overview:
These units will convert a 115VAC / 60Hz input, into a regulated 12VDC or 24VDC output up to 6 amp of continuous load current (see specifications).
Specifications:
• Maximum charge current .7 amp.
• Filtered and electronically regulated outputs.
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switch over to stand-by battery when AC fails (zero voltage drop).
• AC input and DC output LED indicators.
• Short circuit and thermal overload protection.
• Complete with power supply, power distribution module (when applicable), enclosure, cam lock & battery leads.
• Power on-off switch.
Supervised models only:
• AC fail supervision (form "C" contacts).
• Low battery supervision (form "C" contacts).
Power Supply Voltage Output Specifications: *
Output VDC Switch Position Max. Load DC
12VDC
24VDC SW1 - Open
*Specified at 25˚ C ambient.
SW1 - Closed
ig. 1B, pg. 3)
(F
6 amp
Installation Instructions:
The unit should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Mount the unit in desired location.
2. Set SW1 on the power supply board to the desired DC output voltage (Power Supply Voltage Output Specification Chart).
wer to terminals marked [L & N], connect ground to terminal marked [G] (if used).
C po
Connect
3.
4. Measure output v
5. Connect devices to be powered: a. For Power Supply Board connect to terminals marked [+ DC --]. b. For Power Distribution Module(s) connect devices to be powered to terminal pairs 1 to 4 marked
A
oid potential damage.
oltage before connecting de
vices.
This helps a
- 1 -
v
Page 2
[1P & 1N through 4P & 4N] (F
-- DC +
Power Supply
Board
Power
Distribution
Module(s)
BAT FAIL
NO C NC NO C NC
-- BAT +
Fuse Cover
DC
AC
AC FAIL
L G N
OFF ON
SW1:
24V - OPEN
12V - CLOSED
CAUTION: De-energize unit prior
to servicing. For continued protection against fire hazard replace fuse with the same type and rating 3.5A, 250V. Replace protective cover on the fuse of the power supply board, before energizing unit.
Green
Lead
Wire Strap (from Enclosure to Door)
115 power
mains
INPUT
BAT FAIL
NO C NC NO C NC
AC FAIL
SW1: 24V - OPEN 12V - CLOSED
ig. 2, pg. 3)
, 1 to 8 mark
ed [1P & 1N through 8P & 8N] (Fig. 3, pg. 3)
or 1 to 16 marked [1P & 1N through 16P & 16N] (Fig. 4, pg. 3) carefully observing correct polarity.
*Note: P
ower switch is used to disconnect the L (HOT) terminal from the rest of the board. When servicing the unit,
AC mains should be removed.
6. When using stand-by batteries, they must be lead acid or gel type. Connect battery to terminals marked [- BAT +] (battery leads included). Use two (2) 12VDC batteries connected in series for 24VDC operation. Note: When batteries are not used a loss of AC will result in the loss of output voltage.
Supervised models only:
7. Connect appropriate signaling notification devices to AC Fail & Low Bat supervisory relay outputs marked [NO, C, NC]
(Fig. 1A, below).
Fig. 1
Fig. 1A
Fig. 1B
- 2 -
Page 3
INPUT
LED
1P, 2P, 3P, 4P = FUSED OUTPUTS 1N, 2N, 3N, 4N = COMMON OUTPUTS
F1
F1
F2 F3 F4
COMMON POWER OUTPUTS
1P
1N
2P
2N
3P
3N
4P
4N
DC Output to devices
From Power Supply
Board
(Factory Installed)
Used on
PTC Models
N
COMMON POWER OUTPUTS
P
FUSED POWER OUTPUTS
1 2 3 4 5 6 7 8
1
D1
INPUT
R1
LED
DC Output to devices From Power Supply
Board
(Factory Installed)
Power Distribution Module(s):
common
outputs
protected
outputs
P
N
NPS
XFMR Input
12345678
9 10 11 12 13 14 15 16
P
N
3.5A 250V
For continuous protection against risk of fire
replace fuses with same type and rating.
Used on
PTC Models
Fig. 2 Fig. 3
Fig. 4
ON
LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON OFF Loss of AC, Stand-by battery supplying power. OFF
ON
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Normal operating condition.
No DC output.
- 3 -
Page 4
00
0
.81"
0
1.1875"
1.1875"
3.25"
3.25"
0 1.1875" 3.25".75" 1.5" 6.25" 11"
1.4"
6.5"
5.5"
1.4"
11.66"
12.1"
13"
12.5"
11.75"
TOP ONLY
Terminal Identification:
Terminal Function/Description Legend
L, G, N Connect 115VAC to these terminals:
L to Hot, N to Neutral, G to ground (if used).
+ DC - 12VDC / 24VDC @ 6 amp continuous non-power limited output.
*AC FAIL Used to notify loss of AC power, e.g. connect to audible device or alarm
N.O., C, N.C. panel. Relay normally energized when AC power is present.
Contact rating 1 amp @ 120VAC / 28VDC
*Low Battery Used to indicate low battery condition, e.g. connect to alarm panel.
N.O., C, N.C. Relay normally energized when DC power is present.
Contact rating 1 amp @ 120VAC / 28VDC Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC, 24VDC output threshold set @ approximately 21VDC.
- BAT + Stand-by battery connections. Maximum charge rate .7 amp.
* Note: Supervised models only
PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB - Power Distribution Module
Terminal Legend Function/
PD4/PD4CB PD8/PD8CB PD16W/PD16WCB Description
1P to 4P 1P to 8P 1P to16P Positive DC power outputs.
1N to 4N 1N to 8N 1N to 16N Negative DC power outputs.
Enclosure Dimensions:
13”H x 13.5”W x 3.25”D
Altronix is not responsible for any typographical errors.
Altronix Corp. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Made in U IISMP7CTX - Rev. 120104
.S.A.
L01D
- 4 -
MEMBER
Loading...