- Accommodates up to
two (2) 12VDC/12AH batteries.
12/24VDC
Total
Output
Current (A)
Power Supply Voltage Output Specifications:*
Output VDCSwitch PositionMax. Load DC
12VDCSW1 - ON (Fig. 1c, pg. 5)6A
24VDCSW1 - OFF (Fig. 1c, pg. 5)6A
*Specified at 25˚C ambient.
- 2 - SMP7CTX Series
ON
OFF - 24V
Page 3
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with
Installation Instructions:
all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes
in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place
the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower
two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s
upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws
(Enclosure Dimensions, pgs. 7, 8). Secure enclosure to earth ground.
2. Slide [Power ON/OFF] switch t o OFF position.
3. Set SW1 on the power supply board to the desired DC output voltage (Fig. 1c, pg. 5) (Power Supply Voltage Output Specification Chart).
4. Connect AC power to the terminals marked [L & N], connect ground to the green flying lead (Fig. 1, pg. 5).
Use 18 AWG or larger for all power connections (Battery, DC output).
Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).
5. Slide [Power ON/OFF] switch to ON position.
6. Measure output voltage before connecting devices. This helps avoiding potential damage.
Keep power-limited wiring separate from non power-limited wiring (115VAC, 60Hz Input,
Battery Wires). Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts.
Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
7. Slide [Power ON/OFF] switch t o OFF position.
8. Connect devices to be powered:
a. For Power Supply Board connect to the terminals marked [– DC +].
b. For Power Distribution Module(s) connect devices to be powered to the terminal pairs 1 to 4 marked
[1P & 1N] through [4P & 4N] (Fig. 2, pg. 6), 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 3, pg. 6),
or 1 to 16 marked [1P & 1N] through [16P & 16N] (Fig. 4, pg. 6), carefully observing correct polarity.
Note: Power switch is used to disconnect the L (HOT) terminal from the rest of the board (Fig. 1a, pg. 5).
When servicing the unit, AC mains should be removed.
9. When using stand-by batteries, they must be lead acid or gel type.
Connect battery to the terminals marked [– BAT +] (battery leads included).
12VDC operation: Use one (1) 12VDC battery.24VDC operation: Use two (2) 12VDC batteries connected in series.Note: When batteries are not used, a loss of AC will result in the loss of output voltage.
For supervised models only:
10. Connect appropriate signaling notification devices to AC Fail and Low Bat supervisory relay outputs
marked [NC, C, NO] (Fig. 1b, pg. 5).
11. Slide [Power ON/OFF] switch to ON position.
LED Diagnostics:
Power Supply Board
Red (DC)Green (AC)Power Supply Status
ONONNormal operating condition.
ONOFFLoss of AC. Stand-by battery is supplying power.
OFFONNo DC output.
OFFOFFLoss of AC. Discharged or no stand-by battery. No DC output.
Power Distribution Module
GreenPower Distribution Module Status
ONNormal operating condition.
OFFNo Power Output.
SMP7CTX Series - 3 -
Page 4
Terminal Identification:
Power Supply Board:
Terminal LegendFunction/Description
L, G, NConnect 115VAC to these terminals: L to Hot, N to Neutral.
– DC +12VDC / 24VDC @ 6A continuous output.
*AC FAIL
NC, C, NO
*Low Battery
NC, C, NO
– BAT +Stand-by battery connections. Maximum charge rate 0.7A.
*Note: Supervised models only
PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB - Power Distribution Module:
PD4/PD4CBPD8/PD8CBPD16W/PD16WCB
1P to 4P1P to 8P1P to16PPositive DC power outputs.
1N to 4N1N to 8N1N to 16NNegative DC power outputs.
Caution: Equipment to be installed / serviced by authorized / trained personnel only.
Shut branch circuit power before installing / servicing equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to the National
Electrical Code and all local codes.
Used to notify loss of AC power, e.g. connect to audible device or alarm panel.
Relay normally energized when AC power is present.
Contact rating 1A @ 120VAC / 28VDC.
Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally
energized when DC power is present. Contact rating 1A @ 120VAC / 28VDC.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC,
24VDC output threshold set @ approximately 21VDC.
Terminal Legend
Function/Description
The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user
to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may
be of sufficient magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of
important operating and maintenance (servicing) instructions in the literature accompanying the
appliance.
CAUTION: To reduce the risk of electric shock do not open
enclosure. There are no user serviceable parts inside.
Refer servicing to qualified service personnel.
- 4 - SMP7CTX Series
Page 5
--- BAT +--- DC +
AC
DC
LOW BAT
NC C NO NC C NO
AC FAIL
LGN
OFF ON
5A 250V
Power Supply
Green
Lead
115VAC
power mains
--- BAT +--- DC +
AC
DC
LOW BAT
NC C NO NC C NO
AC FAIL
OFF - 24VON - 12V
ON
Distribution
Module(s)
Optional Rechargeable
Stand-by Battery
Optional Rechargeable
Stand-by Battery
OFF - 24V
ON - 12V
ON
Optional Rechargeable
Stand-by Battery
Fig. 1
Fig. 1b
Fig. 1a
Switch disables power mains line voltage input.
If stand-by battery (batteries) are connected, the DC output remains on
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)
Enclosure accommodates up to two (2) 12VDC/7AH batteries.
Also available to accommodate up to two (2) 12VDC/12AH batteries (please contact Altronix).
1.40”
(36mm)
1.20”
(31mm)
0.75”
(19mm)
1.40”
(36mm)
4.85”
(123mm)
12.5”
(318mm)
11.0”
(279mm)
4.85”
(123mm)
1.40”
(36mm)
0.75”
(19mm)
1.20”
(31mm)
0.9375”
(24mm)
3.25”
(83mm)
1.20”
(31mm)
1.40”
(36mm)
5.10”
(130mm)
5.10”
(130mm)
3.25”
(83mm)
(330mm)
1.0”
(25mm)
5.10”
(130mm)
13.0”
6.5625”
(167mm)
0.9375”
(24mm)
3.25”
(83mm)
3.25”
(83mm)
1.0”
(25mm)
1.0”
25mm
10.5”
267mm
25mm
1.0”
SMP7CTX Series - 7 -
Page 8
Enclosure Dimensions (BC400):
SMP7PMCTXX
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
Enclosure accommodates up to two (2) 12VDC/12AH batteries.
1.5”
(38.1mm)
2.0”
(50.8mm)
2.0”
(50.8mm)
5.0”
(127.0mm)
1.25”
(31.75mm)
1.25”
(31.75mm)
4.5”
(114.3mm)
0.91”
(23.114mm)
1.5”
(38.1mm)
1.1”
(27.94mm)
4.615”
(117.22mm)
12.23”
(310.64mm)
4.615”
(117.22mm)
1.5”
(38.1mm)
(27.94mm)
(27.94mm)
1.75”
(44.45mm)
1.375”
(34.925mm)
1.125”
(28.575mm)
1.1”
0.91”
(23.114mm)
15.5”
(393.7mm)
0.79”
1.1”
(20.06mm)
4.5”
(114.3mm)
1.25”
(31.75mm)
1.25”
(31.75mm)
1.5”
(38.1mm)
5.0”
(127.0mm)
1.75”
(44.45mm)
1.5”
(38.1mm)
4.615”
(117.22mm)
4.615”
(117.22mm)
1.5”
(38.1mm)
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty | Made in U.S.A.
IISMP7CTX Series C26R