Altronix SMP5CTX, SMP5PMCTX Installation Guide

SMP5CTX Series Installation Guide
Overview:
These units convert a 115VAC or 230VAC, 50Hz/60Hz input into a regulated 12VDC or 24VDC output up to 4A of continuous load current (see specifications).
SMP5CTX Series Power Supply Configuration Reference Chart:
Accessory
Altronix Model Number
SMP5CTX SMP5PMCTX SMP5PMCTXX SMP5PMP4 SMP5PMP4CB SMP5PMP8 SMP5PMP8CB SMP5PMP16 SMP5PMP16CB
Power
Distribution
Module(s)
- 1 - - 4A
PD4
PD4CB -
PD8 PD8CB ­PD16W
PD16WCB -
Number
of
Outputs
4
8
16
Fused
Outputs
P
P
P
Specifications:
Agency Listings:
• CE European Conformity.
Input:
• Input 115VAC, 50/60Hz, 0.95A or 230VAC, 50/60Hz, 0.5A.
Output:
• 12VDC or 24VDC selectable output.
• 4A supply current.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 0.5A.
• Zero voltage drop when switching over to battery backup.
Features:
• Power ON/OFF switch.
PTC
Outputs
- 3.5A
P
- 3.5A
P
- 3.5A
P
Individual
Output
Rating (A) Supervised
-
2.5A
P
2.5A
2.5A
115VAC/
230VAC
Input
Current (A)
0.95A / 0.5A 4A
12/24VDC
Current (A)
Supervision (select models):
• AC fail supervision (form “C” contacts).
• Low battery supervision (form “C” contacts).
Visual Indicators:
• AC input and DC output LED indicators.
Electrical:
• Operating temperature: 0º C to 49º C ambient.
Mechanical:
• Enclosure Dimensions (H x W x D approx.):
SMP5CTX, SMP5PMCTX, SMP5PMP4, SMP5PMP4CB, SMP5PMP8, SMP5PMP8CB, SMP5PMP16, SMP5PMP16CB:
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)
- Accommodates up to two (2) 12VDC/7AH batteries.
SMP5PMCTXX:
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
- Accommodates up to two (2) 12VDC/12AH batteries.
Total
Output
Power Supply Voltage Output Specifications: *
Output VDC Switch Position Max. Load DC
12VDC SW1 - ON (Fig. 1b, pg. 3) 4A 24VDC SW1 - OFF (Fig. 1b, pg. 3) 4A
*Specified at 25˚ C ambient.
Installation Instructions:
The unit should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 5-6). Secure enclosure to earth ground.
SMP5CTX Series - 1 -
2. Slide [Power ON/OFF] switch t o OFF position.
3. Set SW1 on the power supply board to the desired DC output voltage (Power Supply Voltage Output Specification Chart).
4. Connect AC power to the terminals marked [L & N]. Use 18 AWG or larger for all power connections (Battery, DC output). Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).
5. Slide [Power ON/OFF] switch to ON position.
Keep power-limited wiring separate from non power-limited wiring (115/230VAC / 60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided. CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
Note: Measure output voltage before connecting devices. This helps avoiding potential damage.
6. Slide [Power ON/OFF] switch t o OFF position.
7. Connect devices to be powered: a. For Power Supply Board: connect to the terminals marked [– DC + ]. b. For Power Distribution Module(s): connect devices to be powered to the terminal pairs 1 to 4 marked [1P & 1N] through [4P & 4N] (Fig. 2, pg. 4) or 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 3, pg. 4) or 1 to 16 marked [1P & 1N] through [16P & 16N] (Fig. 4, pg. 4), carefully observing correct polarity. Note: Power switch is used to disconnect the L (HOT) terminal from the rest of the board. When servicing the unit, AC mains should be removed.
8. When using stand-by batteries, they must be lead acid or gel type. Connect battery to the terminals marked [– BAT +] (battery leads included). Use two (2) 12VDC batteries connected in series for 24VDC operation. Note: When batteries are not used, a loss of AC will result in the loss of output voltage.
9. Connect appropriate signaling notification devices to AC Fail & Low Bat supervisory relay outputs marked [NC, C, NO] (Fig. 1a, pg. 3).
10. Slide [Power ON/OFF] switch to ON position.
LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition. ON OFF Loss of AC. Stand-by battery supplying power. OFF ON No DC output OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Terminal Identification:
Power Supply Board:
Terminal Legend Function/Description
L, G, N Connect 115VAC/230VAC to these terminals: L to Hot, N to Neutral. – DC + 12VDC / 24VDC @ 4A continuous non power-limited output. AC FAIL
NC, C, NO
Low Battery NC, C, NO.
– BAT + Stand-by battery connections. Maximum charge rate 0.5A.
Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1A @ 120VAC / 28VDC.
Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1A @ 120VAC / 28VDC. Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC, 24VDC output threshold set @ approximately 21VDC.
PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB - Power Distribution Module:
Terminal Legend
PD4/PD4CB PD8/PD8CB PD16W/PD16WCB
1P to 4P 1P to 8P 1P to16P Positive DC power outputs. 1N to 4N 1N to 8N 1N to 16N Negative DC power outputs.
Function/ Description
- 2 - SMP5CTX Series
Fig. 1
Switch disables power mains line voltage input.
If stand-by battery (batteries) are connected, the DC output remains on.
Fig. 1a
AC FAIL
NC C NO NC C NC
ON OFF
LOW BAT
Wire Strap (from Enclosure to Door)
CAUTION: De-energize unit prior to servicing. For continued protection against fire hazard replace fuse with the same type and rating.
OFF ON
5A 250V
LGN
Green
Lead
115/230VAC
power mains
AC FAIL
NC C NO NC C NO
AC DC
Distribution
Power
INPUT
Module(s)
LOW BAT
LED Diagnostics
Red Green Power Supply Status (DC) (AC)
ON ON Normal operating condition. ON OFF Loss of AC. Stand-by battery
(batteries) supplying power. OFF ON No DC output. OFF OFF Loss of AC. Discharged or no stand-by
battery (batteries). No DC output.
ON
Fig. 1b
Switch On - 12V Switch Off - 24V
SW1 24VDC output - OFF
12VDC output - ON
--- BAT + --- DC +
1
Optional Rechargeable
Stand-by Battery
OFF  
ON  
ON
Optional Rechargeable
Stand-by Battery
CAUTION: Optional rechargeable stand-by batteries must match the power supply output voltage setting.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
SMP5CTX Series - 3 -