![](/html/97/9749/974906ab5ab484688dce50f8a6d1c73353b5cf45bd858e749116f5b4dd5cd7ea/bg1.png)
SMP3CTX Series Installation Guide
Overview:
These units convert a 115VAC or 230VAC, 50/60Hz input into a regulated 12VDC or 24VDC output up to 2.5A of continuous load current (see specifications).
SMP3CTX Series Power Supply Configuration Reference Chart:
Accessory
Altronix
Model Number
SMP3CTX
SMP3PMCTX
SMP3PMCTXX
SMP3PMP4
SMP3PMP4CB
SMP3PMP8
SMP3PMP8CB
SMP3PMP16
SMP3PMP16CB
Power
Distribution
Module(s)
---- 1 ---- ---- 2.5A
PD4
PD4CB ----
PD8
PD8CB ---PD16W
PD16WCB ----
Number
of
Outputs
4
8
16
Fused
Outputs
P
P
P
Outputs
Specifications:
Agency Listings:
• CE European Conformity.
Input:
• Input 115VAC, 50/60Hz, 0.65A or
230VAC, 50/60Hz, 0.35A.
Output:
• 12VDC or 24VDC selectable output.
• 2.5A supply current.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 0.5A.
• Zero voltage drop when switching over to battery backup.
Features:
• Power ON/OFF switch.
Individual
PTC
---- 2.5A
P
---- 2.5A
P
---- 2.5A
P
Output
Rating (A) Supervised
2.5A
2.5A
2.5A
115VAC/
230VAC
Input
Current (A)
----
0.65A/0.35A 2.5A
P
12VDC/
24VDC
Total Output
Current (A)
Supervision (select models):
• AC fail supervision (form “C” contacts).
• Low battery supervision (form “C” contacts).
Visual Indicators:
• AC input and DC output LED indicators.
Electrical:
• Operating temperature: 0º C to 49º C ambient.
Mechanical:
• Enclosure Dimensions (H x W x D approx.):
SMP3CTX, SMP3PMCTX, SMP3PMP4,
SMP3PMP4CB, SMP3PMP8, SMP3PMP8CB,
SMP3PMP16, SMP3PMP16CB:
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)
- Accommodates up to two (2) 12VDC/7AH batteries.
SMP3PMCTXX:
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
- Accommodates up to two (2) 12VDC/12AH batteries.
Power Supply Voltage Output Specifications:*
Output VDC Switch Position Max. Load DC
12VDC SW1 - ON (Fig. 1c, pg. 3) 2.5A
24VDC SW1 - OFF (Fig. 1c, pg. 3) 2.5A
*Specified at 25˚ C ambient.
Installation Instructions:
Wiring methods should be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two
upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 4).
Secure enclosure to earth ground.
![](/html/97/9749/974906ab5ab484688dce50f8a6d1c73353b5cf45bd858e749116f5b4dd5cd7ea/bg2.png)
2. Slide [Power ON/OFF] switch t o OFF position.
3. Set SW1 on the power supply board to the desired DC output voltage (Fig. 1c, pg. 3) (Power Supply Voltage
Output Specification Chart).
4. Connect AC power to the terminals marked [L & N], connect ground to the green flying lead (Fig. 1, pg. 3).
Use 18 AWG or larger for all power connections (Battery, DC output).
Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).
5. Slide [Power ON/OFF] switch to ON position.
6. Measure output voltage before connecting devices. This helps avoiding potential damage.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
7. Slide [Power ON/OFF] switch t o OFF position.
8. Connect devices to be powered:
a. For Power Supply Board connect to the terminals marked [– DC +].
b. For Power Distribution Module(s) connect devices to be powered to the terminal pairs 1 to 4 marked
[1P & 1N] through [4P & 4N] (Fig. 2, pg. 3), 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 3, pg. 3),
or 1 to 16 marked [1P & 1N] through [16P & 16N] (Fig. 4, pg. 3), carefully observing correct polarity.
Note: Power switch is used to disconnect the L (HOT) terminal from the rest of the board (Fig. 1a, pg. 3).
When servicing the unit, AC mains should be removed.
9. When using stand-by batteries, they must be lead acid or gel type.
Connect battery to the terminals marked [– BAT +] (battery leads included).
12VDC operation: Use one (1) 12VDC battery.
24VDC operation: Use two (2) 12VDC batteries connected in series.
Note: When batteries are not used, a loss of AC will result in the loss of output voltage.
For supervised models only:
10. Connect appropriate signaling notification devices to AC Fail and Low Bat supervisory relay outputs
marked [NC, C, NO] (Fig. 1b, pg. 3).
11. Slide [Power ON/OFF] switch to ON position.
LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery supplying power.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Terminal Identification:
Power Supply Board:
Terminal Legend Function/Description
L, G, N Connect 115VAC/230VAC to these terminals: L to Hot, N to Neutral.
– DC + 12VDC / 24VDC @ 2.5A continuous output.
*AC FAIL
NC, C, NO
*Low Battery
NC, C, NO
– BAT + Stand-by battery connections. Maximum charge rate 0.5A.
*Note: Supervised models only
Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay normally
energized when AC power is present. Contact rating 1A @ 120VAC / 28VDC.
Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally
energized when DC power is present. Contact rating 1A @ 120VAC / 28VDC.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC,
24VDC output threshold set @ approximately 21VDC.
PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB - Power Distribution Module:
Terminal Legend
PD4/PD4CB PD8/PD8CB PD16W/PD16WCB
1P to 4P 1P to 8P 1P to16P Positive DC power outputs.
1N to 4N 1N to 8N 1N to 16N Negative DC power outputs.
- 2 - SMP3CTX series
Function/ Description