Altronix SMP10PM12P16CB, SMP10PM12P4CB, SMP10PM12P8CB Installation Guide

SMP10C12X Series Installation Guide
Overview:
These units convert a 115VAC 50/60Hz input into a regulated 12VDC output at up to 10A continuous supply current (see specifications).
SMP10C12X Series Power Supply Configuration Reference Chart:
Accessory
SMP10C12X SMP10C12XX* SMP10PMC12X SMP10PMC12XX* SMP10PM12P4 SMP10PM12P4CB SMP10PM12P8 SMP10PM12P8CB SMP10PM12P16 SMP10PM12P16CB
*Refer to Enclosure Dimensions on pg.7 for enclosure size.
Distribution
Module(s)
- 1
PD4
PD4CB -
PD8 PD8CB ­PD16W
PD16WCB -
Number
of
Outputs
4
8
16
Fused
Outputs
P
P
P
PTC
Outputs
- -
- -
- -
- -
Individual
Output
Rating (A) Supervised
10A
- 3.5A
P
- 3.5A
P
- 3.5A
P
2.5A
2.5A
2.5A
115VAC
50/60Hz
Input
Current
(A)
-
1.45A 10A
P
12VDC
Total
Output
Current
(A)
Specifications:
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 0.7A.
• Automatic switch over to stand-by battery when AC fails (zero voltage drop).
Features:
• AC input and DC output LED indicators.
• Short circuit and thermal overload protection.
Features (cont’d):
• Complete with power supply, power distribution module (when applicable), enclosure, cam lock, and battery leads.
• Power ON/OFF switch.
Supervised models only:
• AC fail supervision (form “C” contacts).
• Battery presence and low battery supervision (form “C” contacts).
Installation Instructions:
Wiring methods should be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install three fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 6-7). Secure enclosure to earth ground.
2. Connect AC power to the terminals marked [L & N]. Use 18 AWG or larger for all power connections (Battery, DC output).
3. Measure output voltage before connecting devices. This helps avoiding potential damage.
Keep power-limited wiring separate from non power-limited wiring (115VAC 50/60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided. CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
SMP10C12Xseries - 1 -
4. Connect devices to be powered: a. For Power Supply Board connect to the terminals marked [– DC +]. b. For Power Distribution Module(s) connect devices to be powered to the terminal pairs 1 to 4 marked [1P & 1N through 4P & 4N] (Fig. 3, pg. 4) 1 to 8 marked [1P & 1N through 8P & 8N] (Fig. 4, pg. 4) or 1 to 16 marked [1P & 1N through 16P & 16N] (Fig. 5, pg. 4), carefully observing correct polarity. *Note: Power switch is used to disconnect the L (HOT) terminal from the rest of the board. When servicing the unit, AC mains should be removed.
5. When using stand-by batteries, they must be lead acid or gel type. Connect battery to the terminals marked [– BAT +] (battery leads included). Note: When batteries are not used, a loss of AC will result in the loss of output voltage.
6. Connect appropriate signaling notification devices to the AC Fail & Low Bat supervisory relay outputs marked [NC, C, NO] (Fig. 1a, below).
Fig. 1
Fig. 1a
AC FAIL
NC C NO NC C NO
Wire Strap (from Enclosure to Door)
LOW BAT
CAUTION: De-energize unit prior to servicing. For continued protection against fire hazard replace fuse with the same type and rating, 15A, 32V.
OFF ON
5A 250V
Earth
Ground
115 power
mains
LGN
Power Supply
AC FAIL
NC C NO NC C NO
Board
INPUT
Divider
Power
Distribution
Module(s)
LOW BAT
AC DC
--- BAT + --- DC +
15A
12VDC Rechargeable Battery
(optional)
CAUTION: Optional rechargeable stand-by batteries must match the power supply output voltage setting.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
- 2 - SMP10C12Xseries
Fig. 2
CAUTION: De-energize unit prior to servicing. For continued protection against fire hazard replace fuse with the same type and rating, 15A, 32V.
Power Supply
Board
Wire Strap (from Enclosure to Door)
OFF ON
5A 250V
Earth Ground
LGN
AC FAIL
115 power mains
NC C NO NC C NO
AC DC
LOW BAT
15A
--- BAT + --- DC +
12VDC Rechargeable Battery
(optional)
CAUTION: Optional rechargeable stand-by batteries must match the power supply output voltage setting.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
SMP10C12Xseries - 3 -
Power Distribution Module(s):
Fig. 3 Fig. 4
F1
Used
on PTC
Models
Fig. 5
1
F1
1P, 2P, 3P, 4P = FUSED OUTPUTS 1N, 2N, 3N, 4N = COMMON OUTPUTS
1P
COMMON POWER OUTPUTS
F2 F3 F4
2N
2P
1N
3P
DC Output to devices
DC Output to devices
1P-16P Power Outputs,
)
1N-16N Common Outputs
12345678
common
outputs
protected
outputs
4P
3N
9 10 11 12 13 14 15 16
PD4
POWER DISTRIBUTING UNIT
LED
4N
From Power Supply
Board
(Factory Installed)
)
N
P
INPUT
NP
NPS
Used
on PTC
Models
From Power Supply Board (Factory Installed)
1
1 2 3 4 5 6 7 8
P
FUSED POWER OUTPUTS
N
COMMON POWER OUTPUTS
DC Output to devices
PD8
D1
LED
R1
INPUT
From Power Supply
Board
(Factory Installed)
Used
on PTC
Models
XFMR Input
For continuous protection against
risk of fire replace fuses with
3.5A 250V
same type and rating.
LED Diagnostics:
Power Supply Board
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition. ON OFF Loss of AC. Stand-by battery is supplying power. OFF ON No DC output. OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB - Power Distribution Module
Green Power Distribution Module Status
ON Normal operating condition.
- 4 - SMP10C12Xseries
Terminal Identification:
Power Supply Board
Terminal Legend Function/Description
L, G, N Connect 115VAC to these terminals: L to Hot, N to Neutral. – DC + 12VDC @ 10A continuous outputs. *AC FAIL
NC, C, NO
*Low Battery NC, C, NO
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1A @ 120VAC / 28VDC
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1A @ 120VAC / 28VDC. Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC
– BAT + Stand-by battery connections. Maximum charge rate 0.7A.
*Note: Supervised Models Only.
PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB - Power Distribution Module
Terminal Legend
PD4/PD4CB PD8/PD8CB PD16W/PD16WCB 1P to 4P 1P to 8P 1P to16P Positive DC power outputs.
Function/Description
SMP10C12Xseries - 5 -
Enclosure Dimensions for:
(
)
(
)
(
)
SMP10C12X SMP10PMC12X SMP10PM12P4 SMP10PM12P4CB SMP10PM12P8 SMP10PM12P8CB SMP10PM12P16 SMP10PM12P16CB
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)
1.40”
(36mm)
5.10”
(130mm)
1.20”
(31mm)
13.0”
(330mm)
(36mm)
0.75”
(19mm)
1.40”
4.85”
(123mm)
12.5”
(318mm)
11.0”
(279mm)
4.85”
(123mm)
1.40”
(36mm)
0.75”
(19mm)
1.20”
(31mm)
0.9375” (24mm)
3.25”
(83mm)
1.20”
(31mm)
1.40”
(36mm)
5.10”
(130mm)
5.10”
(130mm)
3.25”
(83mm)
1.0”
(25mm)
1.0”
25mm
10.5”
267mm
1.0”
25mm
0.9375” (24mm)
1.0”
(25mm)
3.25”
(83mm)
3.25”
(83mm)
6.5625”
(167mm)
- 6 - SMP10C12Xseries
Enclosure Dimensions for:
SMP10C12XX SMP10PMC12XX
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
1.5”
(38.1mm)
2.0”
(50.8mm)
1.25”
(31.75mm)
4.5”
(114.3mm)
0.91”
(23.114mm)
1.5”
(38.1mm)
1.1”
(27.94mm)
4.615”
(117.22mm)
12.23”
(310.64mm)
4.615”
(117.22mm)
1.5”
(38.1mm)
1.1”
(27.94mm)
1.75”
(44.45mm)
0.91”
(23.114mm)
(393.7mm)
1.375”
(34.925mm)
1.125”
(28.575mm)
15.5”
4.5”
(114.3mm)
1.25”
(31.75mm)
1.5”
(38.1mm)
2.0”
(50.8mm)
5.0”
(127.0mm)
1.25”
(31.75mm)
1.5”
(38.1mm)
4.615”
(117.22mm)
4.615”
(117.22mm)
1.1”
(27.94mm)
1.5”
(38.1mm)
0.79”
(20.06mm)
1.75”
(44.45mm)
1.25”
(31.75mm)
5.0”
(127.0mm)
SMP10C12Xseries - 7 -
Notes:
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com. Lifetime Warranty, Made in U.S.A.
- 8 - SMP10C12Xseries
IISMP10C12X Series - Rev. 051105 H18P
MEMBER
Loading...