Altronix SMP10C24X220 Series power supply/chargers convert a 220VAC (working range 198VAC - 256VAC),
LGN
5A 250V
OFF ON
Lug
50/60Hz input into a regulated 24VDC output with up to 10A of continuous load current (see specifications).
SMP10C24X220 Series Power Supply Configuration Reference Chart:
Overview:
Accessory
Altronix
Model Number
SMP10C24X220
SMP10PMC24X220
SMP10PM24P4220
SMP10PM24P4CB220
SMP10PM24P8220
SMP10PM24P8CB220
SMP10PM24P16220
SMP10PM24P16CB220
Power
Distribution
Module(s)
-1
PD4
PD4CB–
PD8
PD8CB–
PD16W
PD16WCB–
Number
of
Outputs
4
8
16
Specifications:
Input:
• Input 220VAC, 50/60Hz, 1.8A.
Output:
• 24VDC output.
• 10A supply current.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• Maximum charge current 0.7A.
• Zero voltage drop when switching over to
battery backup.
Features:
• Power ON/OFF switch.
Fused
Outputs
––
––
P
P
P
PTC Outputs
(auto-resettable)
Individual Output
10A
–3.5A
2.5A
P
–3.5A
2.5A
P
–3.5A
2.5A
P
Rating (A)
Supervised
220VAC
50/60Hz
Input
Current
–
P
1.8A10A
(A)
24VDC
Total
Output
Current
(A)
Supervision (select models):
• AC fail supervision (form “C” contacts).
• Battery presence and low battery supervision
(form “C” contacts).
Visual Indicators:
• AC input and DC output LED indicators.
Electrical:
• Operating temperature: 0ºC to 49ºC ambient.
• BTU/Hr. (approx.): 122 BTU/Hr.
• System AC input VA requirement: 310.5VA.
Mechanical:
• Enclosure Dimensions (H x W x D approx.):
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)
- Accommodates up to
two (2)12VDC/7AH batteries.
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with
Installation Instructions:
all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes
in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place
the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower
two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s
upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws
(Enclosure Dimensions, pg. 8). Secure enclosure to earth ground.
2. Slide [Power ON/OFF] switch t o OFF position (Fig. 1a, pg. 4, Fig. 2a, pg. 5).
3. Connect AC circuit (220VAC, 50/60Hz) as follows:
Green branch wire connects to earth (safety) ground . Line and Neutral to the connector on power supply board marked [L, N] respectively
(Fig. 1, pg. 4, Fig. 2, pg. 5).
Use 18 AWG or larger for all power connections (Battery, DC output).
Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).
4. Slide [Power ON/OFF] switch to ON position.
- 2 - SMP10C24X220 Series
Page 3
5. Measure output voltage before connecting devices. This helps avoiding potential damage.
Keep power-limited wiring separate from non power-limited wiring (220VAC, 50/60Hz Input,
Battery Wires). Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts.
Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
6. Slide [Power ON/OFF] switch t o OFF position.
7. Connect devices to be powered:
a. For Power Supply Board connect to the terminals marked [– DC +].
b. For Power Distribution Module(s) connect devices to be powered to the terminal pairs 1 to 4 marked
[1P & 1N] through [4P & 4N] (Fig. 3, pg. 6), 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 4, pg. 6),
or 1 to 16 marked [1P & 1N] through [16P & 16N] (Fig. 5, pg. 6), carefully observing correct polarity.
Note: Power switch is used to disconnect the L (HOT) terminal from the rest of the board (Fig. 1a, pg. 4,
Fig. 2a, pg. 5).
When servicing the unit, AC mains should be removed.
8. When using stand-by batteries, they must be lead acid or gel type.
Connect battery to the terminals marked [– BAT +] (battery leads included).
Note: When batteries are not used, a loss of AC will result in the loss of output voltage.
For supervised models only:
9. Connect appropriate signaling notification devices to AC Fail and Low Bat supervisory relay outputs
marked [NC, C, NO] (Fig. 1b, pg. 4 or Fig. 2b, pg. 5).
10. Slide [Power ON/OFF] switch to ON position.
LED Diagnostics:
Power Supply Board
Red (DC)Green (AC)Power Supply Status
ONONNormal operating condition.
ONOFFLoss of AC. Stand-by battery is supplying power.
OFFONNo DC output.
OFFOFFLoss of AC. Discharged or no stand-by battery. No DC output.
Power Distribution Module
GreenPower Distribution Module Status
ONNormal operating condition.
OFFNo Power Output.
Terminal Identification:
Power Supply Board:
Terminal LegendFunction/Description
L, G, NConnect 220VAC to these terminals: L to Hot, N to Neutral.
– DC +24VDC @ 10A continuous output.
*AC FAIL
NC, C, NO
*Low Battery
NC, C, NO
– BAT +Stand-by battery connections. Maximum charge rate 0.7A.
*Note: Supervised models only
PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB - Power Distribution Module:
PD4/PD4CBPD8/PD8CBPD16W/PD16WCB
1P to 4P1P to 8P1P to16PPositive DC power outputs.
1N to 4N1N to 8N1N to 16NNegative DC power outputs.
SMP10C24X220 Series - 3 -
Used to notify loss of AC power, e.g. connect to audible device or alarm panel.
Relay normally energized when AC power is present.
Contact rating 1A @ 120VAC / 28VDC.
Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally
energized when DC power is present. Contact rating 1A @ 120VAC / 28VDC.
Low battery threshold:
24VDC output threshold set @ approximately 21VDC.
Terminal Legend
Function/Description
Page 4
Caution: Equipment to be installed / serviced by authorized / trained personnel only.
LOW BAT
NC C NO NC C NO
AC FAIL
--- BAT +--- DC +
LGN
5A 250V
OFF ON
AC
DC
Power Supply
220VAC
power mains
Ground
Lug
LOW BAT
NC C NO NC C NO
AC FAIL
--- BAT +--- DC +
AC
DC
Module(s)
Optional Rechargeable
12VDC Stand-by Battery
Optional Rechargeable
12VDC Stand-by Battery
Shut branch circuit power before installing / servicing equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to the National
Electrical Code and all local codes.
The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user
to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may
be of sufficient magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of
important operating and maintenance (servicing) instructions in the literature accompanying the
appliance.
CAUTION: To reduce the risk of electric shock do not open
enclosure. There are no user serviceable parts inside.
Refer servicing to qualified service personnel.
Fig. 1
Fig. 1a
Switch disables power mains line voltage input.
If stand-by battery (batteries) are connected, the DC output remains on
Ground
Lug
5A 250V
LGN
220VAC
power mains
AC FAIL
NC C NO NC C NO
Fig. 1b
AC
LOW BAT
--- BAT +--- DC +
DC
Optional Rechargeable
12VDC Stand-by Battery
OFF ON
Power Supply
Board
See
LED Diagnostics,
pg. 3
Power
Distribution
Module(s)
Optional Rechargeable
12VDC Stand-by Battery
- 4 - SMP10C24X220 Series
Page 5
LOW BAT
NC C NO NC C NO
AC FAIL
--- BAT +--- DC +
LGN
5A 250V
OFF ON
AC
DC
Power Supply
Green
Lead
115VAC
power mains
LOW BAT
NC C NO NC C NO
AC FAIL
--- BAT +--- DC +
AC
DC
Module
Optional Rechargeable
12VDC Stand-by Battery
Optional Rechargeable
12VDC Stand-by Battery
Fig. 2
Fig. 2a
Switch disables power mains line voltage input.
If stand-by battery (batteries) are connected, the DC output remains on
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)
Enclosure accommodates up to two (2) 12VDC/7AH batteries.
Also available to accommodate up to two (2) 12VDC/12AH batteries (please contact Altronix).
1.40”
(36mm)
1.20”
(31mm)
0.75”
(19mm)
1.40”
(36mm)
4.85”
(123mm)
12.5”
(318mm)
11.0”
(279mm)
4.85”
(123mm)
1.40”
(36mm)
0.75”
(19mm)
1.20”
(31mm)
0.9375”
(24mm)
3.25”
(83mm)
1.20”
(31mm)
1.40”
(36mm)
5.10”
(130mm)
5.10”
(130mm)
3.25”
(83mm)
(330mm)
1.0”
(25mm)
5.10”
(130mm)
13.0”
6.5625”
(167mm)
0.9375”
(24mm)
3.25”
(83mm)
3.25”
(83mm)
1.0”
(25mm)
1.0”
25mm
10.5”
267mm
1.0”
25mm
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty | Made in U.S.A.
IISMP10C24X220 Series C28R
- 8 - SMP10C24X220 Series