Altronix SMP10PM24P8CB220, SMP10PM24P4220, SMP10PMC24X220, SMP10C24X220, SMP10PM24P4CB220 Installation Manual

...
Page 1
SMP10C24X220 Series
Power Supply/Charger
Installation Guide
Models Include:
SMP10C24X220 SMP10PMC24X220
- Single Output.
SMP10PM24P4220
- Four (4) Fuse Protected Outputs.
SMP10PM24P8220
- Eight (8) Fuse Protected Outputs.
SMP10PM24P16220
- Sixteen (16) Fuse Protected Outputs.
Rev. 012610
SMP10PM24P4CB220
- Four (4) PTC Protected Outputs.
SMP10PM24P8CB220
- Eight (8) PTC Protected Outputs.
SMP10PM24P16CB220
- Sixteen (16) PTC Protected Outputs.
More than just power.
TM
Page 2
Altronix SMP10C24X220 Series power supply/chargers convert a 220VAC (working range 198VAC - 256VAC),
LGN
5A 250V
OFF ON
Lug
50/60Hz input into a regulated 24VDC output with up to 10A of continuous load current (see specifications).
SMP10C24X220 Series Power Supply Configuration Reference Chart:
Overview:
Accessory
Altronix Model Number
SMP10C24X220
SMP10PMC24X220
SMP10PM24P4220
SMP10PM24P4CB220
SMP10PM24P8220
SMP10PM24P8CB220
SMP10PM24P16220
SMP10PM24P16CB220
Power
Distribution
Module(s)
- 1
PD4
PD4CB
PD8
PD8CB
PD16W
PD16WCB
Number
of
Outputs
4
8
16
Specifications:
Input:
• Input 220VAC, 50/60Hz, 1.8A.
Output:
• 24VDC output.
• 10A supply current.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 0.7A.
• Zero voltage drop when switching over to battery backup.
Features:
• Power ON/OFF switch.
Fused
Outputs
P
P
P
PTC Outputs
(auto-resettable)
Individual Output
10A
3.5A
2.5A
P
3.5A
2.5A
P
3.5A
2.5A
P
Rating (A)
Supervised
220VAC 50/60Hz
Input
Current
P
1.8A 10A
(A)
24VDC
Total
Output
Current
(A)
Supervision (select models):
• AC fail supervision (form “C” contacts).
• Battery presence and low battery supervision (form “C” contacts).
Visual Indicators:
• AC input and DC output LED indicators.
Electrical:
• Operating temperature: 0ºC to 49ºC ambient.
• BTU/Hr. (approx.): 122 BTU/Hr.
• System AC input VA requirement: 310.5VA.
Mechanical:
• Enclosure Dimensions (H x W x D approx.):
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)
- Accommodates up to two (2)12VDC/7AH batteries.
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with
Installation Instructions:
all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 8). Secure enclosure to earth ground.
2. Slide [Power ON/OFF] switch t o OFF position (Fig. 1a, pg. 4, Fig. 2a, pg. 5).
3. Connect AC circuit (220VAC, 50/60Hz) as follows: Green branch wire connects to earth (safety) ground . Line and Neutral to the connector on power supply board marked [L, N] respectively (Fig. 1, pg. 4, Fig. 2, pg. 5). Use 18 AWG or larger for all power connections (Battery, DC output). Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).
4. Slide [Power ON/OFF] switch to ON position.
- 2 - SMP10C24X220 Series
Page 3
5. Measure output voltage before connecting devices. This helps avoiding potential damage.
Keep power-limited wiring separate from non power-limited wiring (220VAC, 50/60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided. CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
6. Slide [Power ON/OFF] switch t o OFF position.
7. Connect devices to be powered: a. For Power Supply Board connect to the terminals marked [– DC +]. b. For Power Distribution Module(s) connect devices to be powered to the terminal pairs 1 to 4 marked [1P & 1N] through [4P & 4N] (Fig. 3, pg. 6), 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 4, pg. 6), or 1 to 16 marked [1P & 1N] through [16P & 16N] (Fig. 5, pg. 6), carefully observing correct polarity. Note: Power switch is used to disconnect the L (HOT) terminal from the rest of the board (Fig. 1a, pg. 4, Fig. 2a, pg. 5). When servicing the unit, AC mains should be removed.
8. When using stand-by batteries, they must be lead acid or gel type. Connect battery to the terminals marked [– BAT +] (battery leads included). Note: When batteries are not used, a loss of AC will result in the loss of output voltage.
For supervised models only:
9. Connect appropriate signaling notification devices to AC Fail and Low Bat supervisory relay outputs marked [NC, C, NO] (Fig. 1b, pg. 4 or Fig. 2b, pg. 5).
10. Slide [Power ON/OFF] switch to ON position.
LED Diagnostics:
Power Supply Board
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition. ON OFF Loss of AC. Stand-by battery is supplying power. OFF ON No DC output. OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Power Distribution Module
Green Power Distribution Module Status
ON Normal operating condition. OFF No Power Output.
Terminal Identification:
Power Supply Board:
Terminal Legend Function/Description
L, G, N Connect 220VAC to these terminals: L to Hot, N to Neutral. – DC + 24VDC @ 10A continuous output.
*AC FAIL NC, C, NO
*Low Battery NC, C, NO
– BAT + Stand-by battery connections. Maximum charge rate 0.7A.
*Note: Supervised models only
PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB - Power Distribution Module:
PD4/PD4CB PD8/PD8CB PD16W/PD16WCB
1P to 4P 1P to 8P 1P to16P Positive DC power outputs. 1N to 4N 1N to 8N 1N to 16N Negative DC power outputs.
SMP10C24X220 Series - 3 -
Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1A @ 120VAC / 28VDC.
Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1A @ 120VAC / 28VDC. Low battery threshold: 24VDC output threshold set @ approximately 21VDC.
Terminal Legend
Function/Description
Page 4
Caution: Equipment to be installed / serviced by authorized / trained personnel only.
LOW BAT
NC C NO NC C NO
AC FAIL
--- BAT +--- DC +
LGN
5A 250V
OFF ON
AC
DC
Power Supply
220VAC
power mains
Ground
Lug
LOW BAT
NC C NO NC C NO
AC FAIL
--- BAT +--- DC +
AC
DC
Module(s)
Optional Rechargeable
12VDC Stand-by Battery
Optional Rechargeable
12VDC Stand-by Battery
Shut branch circuit power before installing / servicing equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to the National Electrical Code and all local codes.
The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure. There are no user serviceable parts inside. Refer servicing to qualified service personnel.
Fig. 1
Fig. 1a
Switch disables power mains line voltage input. If stand-by battery (batteries) are connected, the DC output remains on
Ground
Lug
5A 250V
LGN
220VAC
power mains
AC FAIL
NC C NO NC C NO
Fig. 1b
AC
LOW BAT
--- BAT +--- DC +
DC
Optional Rechargeable
12VDC Stand-by Battery
OFF ON
Power Supply
Board
See LED Diagnostics, pg. 3
Power
Distribution
Module(s)
Optional Rechargeable
12VDC Stand-by Battery
- 4 - SMP10C24X220 Series
Page 5
LOW BAT
NC C NO NC C NO
AC FAIL
--- BAT +--- DC +
LGN
5A 250V
OFF ON
AC
DC
Power Supply
Green
Lead
115VAC
power mains
LOW BAT
NC C NO NC C NO
AC FAIL
--- BAT +--- DC +
AC
DC
Module
Optional Rechargeable
12VDC Stand-by Battery
Optional Rechargeable
12VDC Stand-by Battery
Fig. 2
Fig. 2a
Switch disables power mains line voltage input. If stand-by battery (batteries) are connected, the DC output remains on
OFF ON
5A 250V
Ground
LGN
Lug
220VAC
power mains
AC FAIL
NC C NO NC C NO
Fig. 2b
AC
LOW BAT
--- BAT +--- DC +
DC
Optional Rechargeable
12VDC Stand-by Battery
Power Supply
Board
See LED Diagnostics, pg. 3
Power
Distribution
Module
Optional Rechargeable
12VDC Stand-by Battery
SMP10C24X220 Series - 5 -
Page 6
Fig. 3 - PD4/PD4CB
F1 F2 F3 F4
Used on
PTC Models
Fig. 4 - PD8/PD8CB
Used on
PTC Models
P
Power Distribution Module(s):
1P, 2P, 3P, 4P = FUSED OUTPUTS 1N, 2N, 3N, 4N = COMMON OUTPUTS
2N
2P
1N
1P
COMMON POWER OUTPUTS
DC Output to devices
1 2 3 4 5 6 7 8
FUSED POWER OUTPUTS
3N
3P
4N
4P
From Power Supply
(Factory Installed)
LED
Board
D1
R1
INPUT
SW1
ON OFF
LED
N
COMMON POWER OUTPUTS
DC Output to devices
From Power Supply
(Factory Installed)
INPUT
Board
Fig. 5 - PD16W/PD16WCB
common
outputs
protected
outputs
Used on
PTC Models
12345678
For continuous protection against risk of fire
3.5A 250V
- 6 - SMP10C24X220 Series
9 10 11 12 13 14 15 16
N
P
replace fuses with same type and rating.
N
NPS
P
XFMR Input
Page 7
Notes:
SMP10C24X220 Series - 7 -
Page 8
Enclosure Dimensions (BC300):
(
)
(
)
(
)
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm) Enclosure accommodates up to two (2) 12VDC/7AH batteries.
Also available to accommodate up to two (2) 12VDC/12AH batteries (please contact Altronix).
1.40”
(36mm)
1.20”
(31mm)
0.75”
(19mm)
1.40”
(36mm)
4.85”
(123mm)
12.5”
(318mm)
11.0”
(279mm)
4.85”
(123mm)
1.40”
(36mm)
0.75”
(19mm)
1.20”
(31mm)
0.9375” (24mm)
3.25”
(83mm)
1.20”
(31mm)
1.40”
(36mm)
5.10”
(130mm)
5.10”
(130mm)
3.25”
(83mm)
(330mm)
1.0”
(25mm)
5.10”
(130mm)
13.0”
6.5625”
(167mm)
0.9375” (24mm)
3.25”
(83mm)
3.25”
(83mm)
1.0”
(25mm)
1.0”
25mm
10.5”
267mm
1.0”
25mm
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056 website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty | Made in U.S.A. IISMP10C24X220 Series C28R
- 8 - SMP10C24X220 Series
MEMBER