• Built-in charger for sealed lead acid or
gel type batteries.
• Maximum charge current 0.7A.
• Zero voltage drop when switching over
to battery backup.
Individual
Fused
Outputs
--10A-
--10A
P
P
P
PTC
Outputs
-3.5A
P
-3.5A
P
-3.5A
P
Output
Rating (A) Supervised
2.5A
2.5A
2.5A
Specifications:
Supervision:
• AC fail supervision (form “C” contacts).
• Battery presence and low battery supervision
(form “C” contacts).
Visual Indicators:
• AC input and DC output LED indicators.
Electrical:
• Operating temperature: 0º C to 49º C ambient.
• BTU/Hr.: 122.84 BTU/Hr.
• System AC input VA requirement: 310.5VA.
Mechanical:
• Enclosure Dimensions (H x W x D approx.):
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)
- Accommodates up to two (2)12VDC/7AH batteries.
P
115VAC,
50/60Hz
Input
Current (A)
2.7A10A
24VDC
Total
Output
Current (A)
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install three fasteners. Place the enclosure’s upper keyholes over the two
upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 6).
Secure enclosure to earth ground.
2. Connect AC power to the terminals marked [L & N], connect ground to the terminal marked [G] (if used),
(Fig. 1, pg. 4 or Fig. 4, pg. 5). Use 18 AWG or larger for all power connections (Battery, DC output).
Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, Battery Wires).
Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
3. Measure output voltage before connecting devices. This helps avoiding potential damage.
4. Connect devices to be powered:
a. For Power Supply Board connect to the terminals marked [--- DC +].
b. For Power Distribution Module(s) connect devices to be powered to the terminal pairs 1 to 4 marked
[1P & 1N] through [4P & 4N] (Fig. 2, pg. 4), 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 3, pg. 4),
or 1 to 16 marked [1P & 1N] through [16P & 16N] (Fig. 5, pg. 5) carefully observing correct polarity.
- 2 - SMP10C24X Series
5. When using stand-by batteries, they must be lead acid or gel type. Connect battery to the terminals marked [--- BAT +]
(battery leads included) (Fig. 1, pg. 4 or Fig. 4, pg. 5).
Note: When batteries are not used, a loss of AC will result in the loss of output voltage.
6. For Supervised Models Only:
Connect appropriate signaling notification devices to AC Fail & Low Bat supervisory relay outputs marked
[N.O., C, N.C.] (Fig. 1a, pg. 4, Fig. 4a, pg. 5).
LED Diagnostics:
OLS250/OLS257 - Power Supply Board
Red (DC)Green (AC) Power Supply Status
ONONNormal operating condition.
ONOFFLoss of AC. Stand-by battery supplying power.
OFFONNo DC output.
OFFOFFLoss of AC. Discharged or no stand-by battery. No DC output.
PD4/PD4CB/PD8/PD8CB - Power Distribution Module
GreenPower Distribution Module Status
ONNormal operating condition.
Terminal Identification:
OLS250/OLS257 - Power Supply Board
Terminal Legend Function/Description
L, G, NConnect 115VAC to these terminals: L to Hot, N to Neutral, G to ground (if used).
--- DC +24VDC @ 10A total supply current.
*AC FAIL
N.C., C, N.O.
Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay normally
energized when AC power is present. Contact rating 1A @ 120VAC / 28VDC.
Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized
*Low Battery
N.C., C, N.O.
--- BAT +Stand-by battery connections. Maximum charge rate 0.7A.
PD4/PD4CBPD8/PD8CBPD16W/PD16WCB
1P to 4P1P to 8P1P to 16PPositive DC power outputs.
1N to 4N1N to 8N1N to 16NNegative DC power outputs.
Function/Description
SMP10C24X Series - 3 -
Fig. 1
LOW BAT
NC C NO NC C NO
OFF ON
5A 250V
AC FAIL
Power
Distribution
Module
Divider
CAUTION: De-energize unit prior to servicing. For continued protection against risk of
electric shock and fire hazard replace fuse with the same type and rating 5A, 250V.
Fig. 1a
Door
Wire Strap
(from Enclosure
to Door)
Earth
Ground
115 power
mains
Class 1
5A 250V
AC FAIL
NC C NO NC C NO
LOW BAT
--- BAT + --- DC +
OFF ON
Divider
Power
Distribution
Module
AC DC
15
Optional Rechargeable
Stand-by Battery
Optional Rechargeable
Stand-by Battery
CAUTION: Optional rechargeable stand-by batteries must match
the power supply output voltage setting.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
CAUTION: De-energize unit prior to servicing. For continued protection against risk of
electric shock and fire hazard replace fuse with the same type and rating 5A, 250V.
Fig. 4a
Door
Wire Strap
(from Enclosure
to Door)
Green
Lead
115 power
mains
Class 1
5A 250V
AC FAIL
NC C NO NC C NO
LOW BAT
--- BAT + --- DC +
OFF ON
Divider
AC DC
15
Fig. 5
Used
on PTC
Models
CAUTION: Optional rechargeable stand-by batteries must match
the power supply output voltage setting.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
PD16W/PD16WCB
DC Output to devices
1P-16P Power Outputs,
1N-16N Common Outputs
12345678
common
outputs
protected
outputs
Optional Rechargeable
Stand-by Battery
Power Distribution Module(s):
9 10 11 12 13 14 15 16
N
P
NP
From
NPS
Power Supply Boar
(Factory Installed)
XFMR Input
Optional Rechargeable
Stand-by Battery
For continuous protection against
risk of fire replace fuses with
3.5A 250V
SMP10C24X Series - 5 -
same type and rating.
Enclosure Dimensions (H x W x D approx.):
(
)
(
)
(
)
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)
Enclosure accommodates up to two (2) 12VDC/7AH batteries.
1.40”
(36mm)
5.10”
(130mm)
1.20”
(31mm)
13.0”
(330mm)
(36mm)
0.75”
(19mm)
1.40”
4.85”
(123mm)
12.5”
(318mm)
11.0”
(279mm)
4.85”
(123mm)
1.40”
(36mm)
0.75”
(19mm)
1.20”
(31mm)
0.9375”
(24mm)
3.25”
(83mm)
1.20”
(31mm)
1.40”
(36mm)
5.10”
(130mm)
5.10”
(130mm)
3.25”
(83mm)
1.0”
(25mm)
1.0”
25mm
10.5”
267mm
1.0”
25mm
0.9375”
(24mm)
1.0”
(25mm)
3.25”
(83mm)
3.25”
(83mm)
6.5625”
(167mm)
- 6 - SMP10C24X Series
Notes:
SMP10C24X Series - 7 -
Notes:
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
web site: www.altronix.com, e-mail: info@altronix.com. Lifetime Waranty, Made in U.S.A.
- 8 - SMP10C24X Series
IISMP10C24X - Rev. 071212 A11P