
ReServ4WP - Outdoor Video Surveillance UPS
Overview:
ReServ4 Video Surveillance UPS unit is designed to provide power for 24VAC and 12VDC cameras during normal or
power outage conditions. True sine wave regulated AC outputs and/or regulated DC outputs.
Specifications:
Input:
• 115VAC 60Hz, 3.5 amp.
Output:
• PTC protected outputs:
- 24VAC @ 4 amp max.
- 12VDC @ 1 amp.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switchover to stand-by battery when AC fails.
Supervision:
• AC fail & low battery supervision (form “C” contacts).
Visual & Audio Indicators:
• AC/DC power LED indicators.
Stand-by Specifications:
Stand-by Batteries 4 amp (100VA) load at 24VAC and 1 amp load at 12VDC max.
Two (2) 12VDC/7AH 45 minutes
Two (2) 12VDC/12AH 90 minutes
Visual Indicators:
• Individual power output LED indicators.
• Low voltage input and Shutdown LED indicators.
Additional Features:
• True sine wave regulated AC outputs &
regulated DC outputs.
• Unit maintains camera synchronization.
• Ease of installation saves time and eliminates costly labor.
Enclosure Dimensions:
• NEMA4 / IP66 Rated enclosure accommodates up to
two (2) 12VDC/7AH batteries.
17.5”H x 12”W x 6.625”D
Installation Instructions:
This installation should be made by qualified service personnel and should conform to all local codes and in accordance
with the National Electrical Code. Product is intended for indoor use only. This product contains no serviceable parts.
1. Mount unit in desired location. Mark & predrill holes in the wall to line up with the top two keyholes in the enclosure.
Install two upper fasteners & screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes
over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the
lower holes and install the two fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the
two lower screws and make sure to tighten all screws (Enclosure, pg. 4). Secure enclosure to earth ground.
Note: This product needs to be secured to the building before operation.
2. Connect AC power mains to terminals marked [L & N], connect ground to terminal marked [G] (Fig. 1, pg. 3).
Use 18 AWG or larger for all power connections (Battery, output) (Fig. 1, pg. 3).
Use 18 AWG to 22 AWG for power limited circuits (AC Fail/Low Battery reporting) (Fig. 1, pg. 3).
Note: A readily accessible disconnect device shall be incorporated in the building installation wiring.
3. The LEDs on the power supply board will illuminate when AC power is present.
4. Measure output voltage before connecting cameras/devices to outputs. This helps avoid potential damage.
5. Connecting Fluidmesh Wireless Radio/Bosch Autodome:
Connect 12VDC Fluidmesh Wireless Radio to terminals marked [P 1-2, N 1-2] (Fig. 1, pg. 3).
Connect 24VAC Bosch Autodome to terminals marked [15-16] (Fig. 1, pg. 3).
6. Connect batteries to terminals marked [-- BAT + ] (Fig. 1, pg. 3). Use two (2) 12VDC batteries connected in
series for 24VDC operation (battery leads included).
Use batteries - Casil CA1270 (12V/7AH), Genesis NP7-12 (12V/7AH), Ultratech UT1270 (12V/7AH).
7. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1, pg. 3) supervisory relay outputs.
8. The power LEDs on the unit for Outputs 1-2 & 15-16 will illuminate when AC power is present (Fig. 1, pg. 3).
Note: If any of the power LEDs are not illuminated the cause may be due to the following:
a. AC mains and battery fail.
b. One (1) or more power output PTCs are tripped due to a short circuit or overload condition.
c. Unit damaged/defective. To reset the PTC:
1. Temporarily remove wiring from output with tripped PTC (Fig. 1, pg. 3).
2. Eliminate the trouble condition (short circuit or overload).
3. Allow 1 minute for PTC to cool off (reset).
4. Re-attach wiring to the output (Fig. 1, pg. 3).
5. Power LEDs will illuminate indicating power has been restored to outputs (Fig. 1, pg. 3).
- 1 - ReServ

WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to all local codes and
in accordance with the National Electrical Code.
LED Diagnostics:
Power Supply Board
Red (DC) Green (AC1) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC, Stand-by battery supplying power.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
ReServ Board
LED LED State Unit Status
Output LEDs
Low Battery
Shutdown
ON ------ Normal operating condition.
------ OFF Loss of 24VACand/or 12VDC output power.
ON ------ Stand-by batteries are low.
------ OFF Normal operating condition.
ON ------ Loss of 24VACand/or 12VDC output power. Discharged stand-by battery.
------ OFF Normal operating condition.
Terminal Identification:
Power Supply Board
Terminal Legend Function/Description
L, G, N Connect 115VAC 60Hz to these terminals: L to hot, N to neutral, G to ground.
-- DC + 24VDC non-power limited output.
AC FAIL
NO, C, NC
BAT FAIL
NO, C, NC
-- BAT + Stand-by battery connections. Maximum charge current 0.7 amp.
Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation devices,
with AC present terminals marked NO and C are open, NC and C are closed. When loss of AC
occurs terminals marked NO and C are closed, NC and C are open.
Form “C” dry contacts used to signal low battery voltage or loss of battery voltage. Under normal
conditions terminals marked NO and C are open, NC and C are closed. During a trouble condition
terminals marked NO and C are closed, and NC and C are open.
ReServ Board
Terminal Legend Function/Description
Input --- 24VDC + 24VDC input from power supply board.
N, P 1-2 12VDC outputs. N = Negative, P = Positive (Fig. 1, pg. 3).
N, P 15-16 24VAC outputs.
ReServ - 2 -

The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the
P
N
LOW BATTERY
SHUTDOWN
Input
--- 24VDC +
15 16 1 2
24VAC
Outputs
(4 amp max.)
12VDC
Outputs
(1 amp max.)
Green
Lead
12VDC Rechargeable Battery
(order separately)
12VDC Rechargeable Battery
(order separately)
5A
250V
unswitched
115VAC
60Hz, 3.5 amp
power mains
Note: Tw o (2) 12VDC rechargeable batteries
connected in series required.
Supervised
Green
Lead
CAUTION: Risk of explosion if battery is replaced by an
incorrect type dispose of used batteires according to the instructions.
presence of an insulated “DANGEROUS VOLTAGE” within the products enclosure that may be of sufficient
magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important
operating and maintenance (servicing) instructions in the literature accompanying the appliance.
Fig. 1 - ReServ4WP
CAUTION: To reduce the risk of electric shock do not open enclosure.
There are no user serviceable parts inside. Refer servicing to qualified
service personnel.
- 3 - ReServ

1.25”
12.00”
16.00”
6.312”
1.25”
10.00”
Enclosure Dimensions:
NEMA4/IP66 rated enclosure.
17.5”H x 12”W x 6.625”D
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: info@altronix.com, Made in U.S.A.
IIReServ4WP C25K
- 4 - ReServ