Altronix R248ULCB Installation Instructions

Rack Mount Series
UL Listed CCTV Power Supplies
Installation Guide
Models Include:
R248UL
- 24VAC @ 3.5 amp (85VA)
or 28VAC @ 3 amp (85VA).
R248ULCB
- 24VAC @ 3.5 amp (85VA)
or 28VAC @ 3 amp (85VA).
- Eight (8) PTC Protected Outputs.
Rev. 040506
Overview:
These Altronix Rack Mount CCTV Power Supplies provide 24VAC or 28VAC distributed via eight (8) fuse or PTC protected outputs for powering CCTV Cameras, heaters and other video accessories.
Rack Mount Configuration Reference Chart:
Altronix
Output Voltage
Model Number
R248UL
R248ULCB
(VAC)
24VAC 3.5 amp
28VAC 3 amp
24VAC 3.5 amp
28VAC 3 amp
Total Output Current
(Power)
Number of Outputs
8
8 Yes
PTC Protected Outputs
(Class 2 power-limited
for Dry locations).
(Class 3 for Wet locations).
Fuse Protected
Class 1 Outputs
Individual Output Current
Yes 3.5 amp
2.5 amp
(max per output - not to
exceed total output current)
Fuse Ratings
3.5
3.5 amp/
amp
3.5 amp/
Primary In-line Fuse
Ratings
250V
250V
115VAC 50/60Hz Input
Current
0.85 amp
0.85 amp
Specifications:
Agency Listings:
• UL Listed for Commercial
Closed-Circuit Television Equipment (UL2044). CUL Listed - CSA Standard C22.2 No.1-98, Audio, Video and Similar Equipment.
• CE European Conformity
Output:
• 24VAC or 28VAC outputs.
• Surge suppression.
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.
Visual Indicators:
• Individual power LED indicators.
• Illuminated power disconnect circuit breaker
with manual reset.
Features:
• Unit maintains camera synchronization.
• Ease of installation saves time and eliminates
costly labor.
• Removable terminal blocks with locking screw flanges.
Rack Dimensions (H x W x D):
• 2U rack mount chassis for use in standard EIA 19” rack.
3.26” x 19.125” x 8.5” (83mm x 486mm x 216mm)
Agency
Listings
Installation Instructions:
1. Mount unit in the desired rack location (Space unit at least 3” from any video monitors), Do not obstruct side air vents.
2. Set power disconnect circuit breaker to OFF position (Fig. 1d, pg. 3).
3. All units are factory set for 24VAC operation. For 28VAC operation, adjust unit prior to mounting and applying power as follows: Change the wire position so that the black wire [28V] is connected to the terminal marked [P] and the yellow wire [24V] is connected to the terminal marked [S].
Note: R248ULCB set for 28VAC operation is not Class 2 Rated, not power-limited.
4. Plug power cord into a grounded 115VAC 50/60 Hz receptacle (Fig. 1c, pg. 3), ground should be connected as indicated in (Fig. 1e, pg. 3).
5. Set power disconnect circuit breaker to RESET (ON) position (Fig. 1d, pg. 3).
6. Measure output voltage before connecting devices. This helps avoiding potential damage. All terminals with common suffix (P) “1P, 2P...” are the same polarity.
7. Set power disconnect circuit breaker to OFF position (Fig. 1d, pg. 3).
8. Connect devices to removable terminal blocks marked [1P & 1N through 8P & 8N] for eight (8) output models (Fig. 1a, pg. 3). When wiring is completed on the terminal blocks they can be locked down by tightening screw flanges.
9. Upon completion of the wiring, set power disconnect circuit breaker to RESET (ON) position (Fig. 1d, pg. 3).
10. Green power LEDs on faceplate will illuminate when power is present. When an output is in a trouble condition (blown fuse or tripped PTC), the corresponding LED will not be illuminated (Fig. 1, pg. 3). a. Blown fuse (R248UL) - Set power disconnect circuit breaker on back of unit to the OFF position (Fig. 1d, pg. 3). Remove front faceplate to access fuses. Replace with fuses rated @ 3.5A/250VA (Altronix model # Fuse1).
- 2 - R248UL Series
b. Tripped PTC (R248ULCB) - To reset PTC, set power disconnect circuit breaker on back of unit to the OFF position. After approximately 30 secs. set power disconnect circuit breaker to the ON (RESET) position (Fig. 1d, pg. 3).
11. Illuminated power disconnect circuit breaker with manual reset: OFF position - Switch not illuminated. Outputs not powered. RESET (ON) position - Circuit breaker illuminated. Outputs powered. Circuit breaker tripped - Circuit breaker is not illuminated. Power LEDs on faceplate are not illuminated. Outputs not powered. To reset circuit breaker set power disconnect circuit breaker to RESET (ON) position (Fig. 1d, pg. 3).
Note: Do not exceed units electrical load ratings as indicated in reference chart (pg. 2). Do not place mechanical load on unit. Unit is designed optimally for normal data room office installations.
Data racks should always be properly ventilated.
CAUTION: Equipment to be installed/serviced by authorized personnel only. Shut brunch circuit power before servicing/installing equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to all local codes and in accordance with the National Electrical Code.
Fig. 1
N
P
ALTRONIX CORP.
BROOKLYN, NY 11220
MADE IN USA
Fig. 1a
Removable Terminal
Block
Fig. 1b Fig. 1d
Fuse
N
PS
Fig. 1c
XFMR
Strain Relief
Line Cord
Divider
Illuminated
Power Disconnect
Circuit Breaker with
manual reset
PTC1
Used
on PTC
Models
AC Power
LED's
AC Power
LED's
24VAC Output
(Factory Set)
SP N
28VAC Output
SP N
(Green Wire Earth GND)
Fig. 1e
28VAC (Black)
24VAC (Yellow)
COM (Brown)
R248UL Series - 3 -
24VAC (Yellow)
28VAC (Black)
COM (Brown)
For fuse protected models:
Replace fuses with the same type and rating 3.5A/250V.
3.5A
250V
The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure. There are no user serviceable parts inside. Refer servicing to qualified service personnel.
Rack Mechanical Drawing & Dimensions
3.26” x 19.125” x 8.5” (83mm x 486mm x 216mm)
19.125”
(485.78mm)
17.5”
(444.5mm)
2.95”
(74.93mm)
(215.9mm)
8.5”
0.65”
(16.51mm)
Front View
Bottom View
2.52”
(64mm)
RESET
1.5”
(38mm)
1.0”
(25.4mm)
Rear View
3.26”
(83mm)
Altronix is not responsible for any typographical errors.