![](/html/69/69bd/69bd7c54a876b13ed816e78b2ef864a0f3c38518452168b9cae0ea280b2049c4/bg1.png)
PM224 - Supervised Linear
AC AC - DC + - BAT +
MADE
IN U.S.A.
PM2 POWER MONITOR
AL
TRONIX CORP
.
POWER
SUPPLY
CHARGER
AC
DC
C NO
AC
BAT
NC C NO
NC
Power Supply/Charger
Overview:
The PM224 supervised linear power supply/charger converts a low voltage “AC” input to a filtered and regulated
24VDC, 750mA continuous power limited output.
Specifications:
Input:
• 24VAC/40VA
Output:
• 24VDC output
• 750ma continuous supply current
• Filtered and electronically regulated output
• Thermal and short circuit protection with auto reset
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries
• Automatic switchover to stand-by battery when AC Fails
• PTC battery protection.
Supervision:
• AC fail supervision (form “C” contacts)
• Low battery supervision (form “C” contacts)
• Low battery disconnect prevents batteries from deep discharge
Additional Features:
• AC input and DC output LED indicators
• Includes battery leads
Board Dimensions (approximate): 5.25"L x 2.75"W x 1.5"H
Installation Instructions:
1. Connect proper transformer (24VAC, 40VA) to terminals marked [AC].
2. Measure output voltage before connecting devices. This helps avoid potential damage.
3. Connect devices to be powered to terminals marked [- DC +], carefully observing polarity.
4. When the use of stand-by batteries are desired, they must be lead acid or gel type.
Connect battery to terminals marked [- BAT +] on the unit (battery leads included).
Note: When batteries are not used a loss of AC will result in the loss of output voltage.
5. Connect appropriate signaling notification devices to AC Fail & Low battery supervisory
relay output terminals marked [N.C., C, N.O. ].
Note: During normal operation (AC and battery connected). the N.C. and C relay contacts
will be in the closed position and the N.O. and C relay contacts will be in
the open position. These contacts are rated at 2 amps, 120VAC.
![](/html/69/69bd/69bd7c54a876b13ed816e78b2ef864a0f3c38518452168b9cae0ea280b2049c4/bg2.png)
Terminal Indentification:
Terminal Function/Description
Legend
AC / AC Low voltage AC input (24VAC / 40VA min.). Altronix part # TP2440.
+ DC - 24VDC 750 mA continuous power limited output.
AC FAIL Used to notify loss of AC power, e.g. connect to audible device or alarm
NC, C, NO panel. Relay normally energized when AC power is present.
Contact rating 2 amps @ 120VAC / 28VDC
Low Battery Used to indicate low battery condition, e.g. connect to alarm panel.
NC, C, NO Relay normally energized when DC power is present.
Contact rating 2 amps @ 120VAC / 28VDC
- BAT + Stand-by battery connections. Maximum charge rate 200mA.
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: info@altronix.com, Lifetime