Description
Altronix MOM5C power distribution module converts one (1) non power-limited DC
voltage input to five (5) power-limited outputs. Each output will route power to a variety
of access control hardware and devices which includes Mag Locks, Electric Strikes,
Magnetic Door Holders, etc. These outputs will operate in both fail-safe and fail-secure
modes. Controlled trigger input is achieved through normally open (NO) or normally
closed (NC) supervised input or the polarity reversal from an FACP (Fire Alarm Control
Panel). A form “C” dry output relay will enable HVAC Shutdown, Elevator Recall or trigger
Specifications
Input
Voltage 12VDC or 24VDC from power supply.
Output
Voltage 12VDC or 24VDC. Current 2.5A continuos supply current.
Current limit is 2A per output. Other Short circuit and thermal overload protection.
Filtered and regulated.
Fire Alarm Interface
Fire Alarm Panel or Access Control System trigger inputs N.O. or N.C. supervised trigger input and polarity reversal trigger input.
Supervision
Power Failure Form “C” contact rated 1A 28VDC/115VAC. Trigger Form “C” contact rated 1A 28VDC/115VAC.
Indicators (LED)
Input Power is present. Input Trigger On. Outputs (Individual LEDs) Output fail.
Agency Listings
Access Control UL294. Fire Alarm UL1481. Burglar Alarm ULC-S318-96. CSFM Approved.
Physical and Environmental
Enclosure Dimensions (H x W x D)
8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm).
Product Weight 4.1 lbs. (1.85 kg). Shipping Weight 4.8 lbs. (2.18 kg). Temperature Operating 0ºC to 49ºC (32ºF to 120ºF). Storage -20ºC to 70ºC (-4ºF to 158ºF). Relative Humidity 85% +/-5%.
Rev. MOM5C-11102016