Altronix MAXIMAL7D, MAXIMAL5D, MAXIMAL3D Installation Manual

Series
Access Power Controllers
Installation Guide
Models Include:
Maximal3D
- 12VDC @ 5 amp or 24VDC @ 5.4 amp.
- Sixteen (16) PTC protected Class 2 Rated power-limited outputs.
Maximal5D
- 12VDC @ 9 amp.
- Sixteen (16) PTC protected Class 2 Rated power-limited outputs.
Maximal7D
- 24VDC @ 9.4 amp.
- Sixteen (16) PTC protected Class 2 Rated power-limited outputs.
Altronix Corp.
140 58th St. Brooklyn, NY
Rev. SCB110912
More than just power.
TM
Table of Contents:
MaximalD Series Overview ............................................................................................. 3
MaximalD Series Configuration Chart ............................................................................. 3
MaximalD Series Features ............................................................................................... 3
MaximalD Installation Instructions ............................................................................... 4-5
Maintenance ...................................................................................................................... 5
Power Supply Board LED Diagnostics ............................................................................ 5
Access Power Controller LED Diagnostics ..................................................................... 6
Power Supply Board Terminal Identification .................................................................. 6
Access Power Controller Terminal Identification ............................................................ 6
Power Supply Board Stand-by Battery Specifications ..................................................... 7
Power Supply Board Output Voltage Settings ................................................................. 7
Access Power Controller Typical Application Diagram .................................................. 8
Maximal3D and Maximal5D Battery Hookup and Tamper Switch Installation ............. 9
Maximal7D Battery Hookup and Tamper Switch Installation ...................................... 10
NEC Power-Limited Wiring Requirements for Maximal3D ......................................... 11
NEC Power-Limited Wiring Requirements for Maximal5D ......................................... 12
NEC Power-Limited Wiring Requirements for Maximal7D ......................................... 13
FACP Hook-up Diagrams .............................................................................................. 14
Enclosure Dimensions .................................................................................................... 15
- 2 - Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC)
MaximalD Series Overview:
Maximal Access Power/Controllers distribute and switch power to access control systems and accessories. They convert a 115VAC 60Hz input into sixteen (16) independently controlled 12VDC or 24VDC Class 2 Rated PTC protected power­limited outputs. These Fail-Safe/Fail-Secure power outputs may be converted to dry form “C” contacts. The outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Keypad, Push Button, REX PIR, etc. Units will route power to a variety of access control hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the sixteen (16) outputs. All interconnecting equipment must be UL Listed.
MaximalD Series Configuration Chart:
Altronix
Model Number
Maximal3D
Power Supply
Board Output
Voltage Options
12VDC @ 5 amp or
24VDC @ 5.4 amp
Class 2 Rated PTC
Protected Power-
Limited Outputs
Maximum Current
Per ACM8CB
Output
115VAC 60Hz
Input
(current draw)
Power Supply
Board Input
Fuse Rating
Power Supply
16 2 amp 3.5 amp 5A/250V ------
Board Output
Fuse Rating
Agency Listings
and File Numbers
UL File # BP6714 UL 294 - UL Listed for Access ControlSystem Units.
Maximal5D
Maximal7D
12VDC @ 9 amp 16 2 amp 2.6 amp 5A/250V 15A/32V
24VDC @ 9.4 amp 16 2 amp 4.4 amp 5A/250V 15A/32V
General Signaling Equipment Evaluated to CSA Standard C22.2 No.205-M1983
Altronix Corp.
140 58th St. Brooklyn, NY
California State Fire Marshal Approved
MaximalD Series Features:
• Sixteen (16) independently trigger controlled outputs. Output options: a) Sixteen (16) Fail-Safe filtered and electronically regulated power outputs. b) Sixteen (16) Fail-Secure filtered and electronically regulated power outputs. c) Any combination of the above.
• Sixteen (16) Access Control System trigger inputs. Input trigger options: a) Sixteen (16) normally open (NO) dry trigger inputs. b) Sixteen (16) open collector inputs. c) Any combination of the above.
• Sixteen (16) unswitched filtered and electronically regulated aux. power outputs (outputs are rated @ 2 amp).
• Red LEDs on ACM8CB board indicate individual outputs are triggered (relays energized).
• Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the sixteen (16) outputs. Fire Alarm disconnect input trigger options: a) Normally open (NO) or normally closed (NC) dry trigger input. b) Polarity reversal input from FACP signaling circuit.
• Green LED on ACM8CB board indicates FACP disconnect is triggered.
• FACP output relay indicates that FACP input is triggered (form “C” contact rated @ 1 amp/28VDC not evaluated by UL).
• Power supply input is factory installed. It provides common power for both ACM8CB boards and all connected access control devices.
• ACM8CB board main fuses are rated @ 10 amp. Output PTCs are rated @ 2 amp.
• Built-in charger for sealed lead acid or gel type batteries.
- Maximum charge current is 0.7 amp for AL600ULXB and AL1012ULXB power supply boards.
- Maximum charge current is 3.6 amp for AL1024ULXB2 power supply board.
• Automatic switch over to stand-by battery when AC fails.
• Zero voltage drop when unit switches over to battery backup (AC failure condition).
• Short circuit and thermal overload protection with auto reset.
• Green AC input and red DC output LED indicators on power supply board(s).
• AC fail supervision (form “C” contact rated @ 1 amp/28VDC).
• Battery fail and battery presence supervision (form “C” contact rated @ 1 amp/28VDC).
• Enclosure accommodates up to four (4) 12VDC/12AH batteries. Enclosure dimensions (H x W x D): 26” x 19” x 6.25” (660.4mm x 482.6mm x 158.75mm).
Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC) - 3 -
MaximalD Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
Power Supply Board LED Diagnostics (pg. 5) Access Power Controller LED Diagnostics (pg. 6) Power Supply Board Terminal Identification (pg. 6) Access Power Controller Terminal Identification (pg. 6) Power Supply Board Stand-by Battery Specifications (pg. 7) Power Supply Board Output Voltage Settings (pg. 7) Access Power Controller Typical Application Diagram (pg. 8) FACP Hook-up Diagrams (pg. 14)
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws, level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the three upper screws. Install the three lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 15).
2. The power supply is pre-wired to the ground (chassis). Connect main incoming ground to the provided green grounding conductor lead. Connect unswitched AC power (115VAC 60Hz) to the terminals marked [L, N] on power supply board. Use 14 AWG or larger for all power connections. Keep power-limited wiring separate from non power-limited wiring. Minimum 0.25” spacing must be
provided (Figs. 5-7, pgs. 11-13). CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
3. Select desired DC output voltage by setting SW1 to the appropriate position on the Maximal3D power supply, (Figs. 1 and 1a, pg. 7). Maximal5D power supply is factory set at 12VDC and Maximal7D power supply is factory set at 24VDC.
4. Measure the output voltage of the unit before connecting any devices to ensure proper operation. Improper or high voltage will damage these devices.
5. Output options (Fig. 2, pg. 8): The unit will provide either sixteen (16) switched power outputs.
(a) Fail-Safe Switched Power outputs:
For Fail-Safe operation connect the positive (+) input of the access control devices to terminal marked [NC]. Connect the negative (-) input of the access control devices to terminal marked [COM]. (b) Fail-Secure Switched Power outputs: For Fail-Secure operation connect the positive (+) input of the access control devices to terminal marked [NO]. Connect the negative (-) input of the access control devices to terminal marked [COM].
6. Auxiliary Power outputs (unswitched): Connect access control devices that require constant power to the terminals marked [C] positive (+) and [COM] negative (-).
7. Input trigger options (Fig. 2, pg. 8):
(a) Normally Open [NO] input trigger:
Inputs 1-8 are activated by normally open or open collector sink inputs. Connect access control panel outputs, keypads, push buttons, REX PIRs, etc. to terminals marked [IN] and [GND].
(b) Open Collector Sink inputs:
Connect the access control panel open collector sink positive (+) to terminals marked [IN] and the negative (-) to terminals marked [GND].
8. Fire Alarm Interface options (Figs. 8-12, pg. 14): A normally closed [NC] or normally open [NO] input trigger from a fire alarm control panel or a polarity reversal input from an FACP signaling circuit will affect selected outputs. To enable FACP Disconnect for an output turn the corresponding switch(es) [SW1-SW8] ON on each ACM8CB board. To disable FACP disconnect for an output turn the corresponding switch(es) [SW1-SW8] OFF on each ACM8CB board.
(a) Normally Open [NO] input:
For non-latching hook-up refer to (Fig. 9, pg. 14). For latching hook-up refer to (Fig. 10, pg. 14).
(b) Normally Closed [NC] input:
For non-latching hook-up refer to (Fig. 11, pg. 14). For latching hook-up refer to (Fig. 12, pg. 14).
(c) FACP Signaling Circuit input trigger:
Connect the positive (+) and negative (-) from the FACP signaling circuit output to the terminals marked [+ INP -]. Connect the FACP EOL to the terminals marked [+ RET -] (polarity is referenced in an alarm condition). Jumper J3 must be cut (Fig. 8, pg. 14).
- 4 - Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC)
9. FACP Dry form “C” output (Fig. 2a, pg. 8): FACP form “C” contacts can be use to trigger reporting or signaling devices. These contact switch
upon a fire alarm input trigger to the ACM8CB boards.
10. Stand-by Battery Connections (Figs. 3-7, pgs. 9-13): For Access Control applications batteries are optional. If batteries are not used a loss of AC will result in the loss of output voltage. Batteries must be lead acid or gel type. Connect one (1) 12VDC battery to the terminals marked [+ BAT -] for 12VDC operation (Fig. 3a, pg. 9). Use two (2) 12VDC batteries wired in series for 24VDC operation.
11. Battery and AC Supervision outputs (Figs. 3-4, pgs. 9-10): It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT FAIL] supervisory relay outputs marked [NC, C, NO] to appropriate visual notification devices. Use 22 AWG to 18 AWG for AC Fail & Low/No Battery reporting.
12. Installation of tamper switch (Not Included) (Figs. 3b-4a, pgs. 9-10): Mount UL Listed tamper switch (Sentrol model 3012 or equivalent) at the top of the enclosure. Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Figs. 3b and 4a, pgs. 9-10). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the door of the enclosure.
Maintenance:
Unit should be tested at least once a year for the proper operation as follows: FACP Supervision: To ensure proper connection and operation of the Fire Alarm disconnect hookup. Please follow the appropriate procedure below: Normally Open Input: Placing a short between terminals marked [T] and [+ INP] will trigger the Fire Alarm Disconnect. Remove the short to reset. Normally Closed Input: Remove the wire from terminal marked [INP -- ] will trigger the Fire Alarm Disconnect. Replace the wire to terminal marked [INP -- ] to reset. FACP Signal Circuit Input: It is necessary to trigger the Fire Alarm System. In all of the above scenarios the green TRG LED of the ACM8CBs will illuminate. All outputs selected for Fire Alarm Disconnect will activate releasing locking devices. Note: All outputs [OUT 1 - OUT 8] must be in a normal (de-energized) condition prior to testing. When the unit is configured for Normally Open (Fig. 10, pg. 14) or Normally Closed (Fig. 12, pg. 14) latching operation it is necessary to reset the Fire Alarm Disconnect by activating the Normally Closed reset switch. Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level
(Power Supply Board Stand-by Battery Specifications, pg. 7).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage at the battery terminals and at the board terminals marked [+ BAT -] to ensure that there is no break in the battery connection wires. Note: AL600ULXB and AL1012ULXB Power Supply Board maximum charge current is 0.7 amp. AL1024ULXB2 Power Supply Board maximum charge current is 3.6 amp. Expected battery life is 5 years; however, it is recommended to change batteries within 4 years or less if necessary.
Power Supply Board LED Diagnostics:
LED
Red (DC) Green (AC)
ON ON Normal operating condition. ON OFF Loss of AC. Stand-by battery supplying power. OFF ON No DC output. Short circuit or thermal overload condition. OFF OFF No DC output. Loss of AC. Discharged battery.
Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC) - 5 -
Power Supply Status
Loading...
+ 11 hidden pages