- 2 - Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused)
Maximal Series Overview:
Maximal Access Power/Controllers distribute and switch power to access control systems and accessories. They convert a
115VAC 60Hz input into sixteen (16) independently controlled 12VDC or 24VDC fuse protected outputs. These Fail-Safe/
Fail-Secure power outputs may be converted to dry form “C” contacts. The outputs are activated by an open collector sink
or normally open (NO) dry trigger input from an Access Control System, Keypad, Push Button, REX PIR, etc. Units will
route power to a variety of access control hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders,
etc. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices.
The fire alarm disconnect feature is individually selectable for any or all of the sixteen (16) outputs. All interconnecting
equipment must be UL Listed.
Maximal Series Configuration Chart:
Altronix
Model
Number
Maximal11
Maximal33
Maximal55
Maximal75
Maximal77
Output Voltage Options
Power Supply 1 Power Supply 2
Total Output
Current
AL400ULXB2AL400ULXB2
12VDC @ 3.5A12VDC @ 3.5A7A
12VDC @ 2.7A24VDC @ 2.7A5.4A
24VDC @ 3.5A24VDC @ 2.7A6.2A
AL600ULXBAL600ULXB
12VDC @ 5.5A12VDC @ 5.5A11A
12VDC @ 5.7A24VDC @ 5.7A11.4A
24VDC @ 5.5A24VDC @ 5.7A11.2A
AL1012ULXBAL1012ULXB
19165.2A2.5A5A/250V15A/32V
12VDC @ 9.5A12VDC @ 9.5A
AL1012ULXBAL1024ULXB2
19.2167A2.5A
12VDC @ 9.5A24VDC @ 9.5A
AL1024ULXB2AL1024ULXB2
19.4
24VDC @ 9.7A24VDC @ 9.7A
(16 outputs)
Fuse Protected
Outputs
115VAC 60 Hz
Input (current)
Current per
ACM8 output
Power Supply
Board Input
Fuse Rating
Power Supply
16*7A2.5A5A/250V15A/32V
167A2.5A5A/250V---
5A/250V
(AL1012ULXB)
and
AL1024ULXB2)
15A/32V
(AL1012ULXB)
AL1024ULXB2)
168.8A2.5A5A/250V15A/32V
Board Output
Fuse Rating
and
Agency Listings
and File
UL File #
BP6714
UL 294
UL Listed for
Access Control
System Units.
General
Signaling
Equipment
Evaluated to
CSA Standard
C22.2
No.205-M1983
Altronix Corp.
140 58th St. Brooklyn, NY
California
State Fire
Marshal
Approved
Numbers
*Maximal11 outputs are power-limited.
Maximal Series Features:
• Sixteen (16) independently trigger controlled outputs.
Output options:
a) Sixteen (16) Fail-Safe filtered and electronically regulated power outputs.
b) Sixteen (16) Fail-Secure filtered and electronically regulated power outputs.
c) Sixteen (16) form “C” relay outputs (rated @ 5 amp/28VDC or VAC).
d) Any combination of the above.
• Sixteen (16) Access Control System trigger inputs.
Input trigger options:
a) Sixteen (16) normally open (NO) dry trigger inputs.
b) Sixteen (16) open collector inputs.
c) Any combination of the above.
• Sixteen (16) unswitched filtered and electronically regulated aux. power outputs (outputs are rated @ 2.5 amp).
• ACM8 maximum current is 2.5 amp per output.
Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused) - 3 -
• Red LEDs on ACM8 board indicate individual outputs are triggered (relays energized).
• Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the sixteen (16) outputs.
Fire Alarm disconnect input trigger options:
a) Normally open (NO) or normally closed (NC) dry trigger input.
b) Polarity reversal input from FACP signaling circuit.
• Green LED on ACM8 board indicates FACP disconnect is triggered.
• FACP output relay indicates that FACP input is triggered (form “C” contact rated @ 1 amp/28VDC not evaluated by UL).
• Power supply input options:
a) Factory installed power supplies provide common power for both ACM8 boards and all connected
access control devices.
b) An optional UL Listed power-limited external access control power supply may be connected to isolate
the ACM8 boards from the access control devices (only applicable on Maximal11).
• ACM8 board main fuses are rated @ 10 amp. Output fuses are rated @ 2.5 amp.
• Built-in charger for sealed lead acid or gel type batteries.
- Maximum charge current is 0.7 amp for AL400ULXB2, AL600ULXB and AL1012ULXB power supply boards.
- Maximum charge current is 3.6 amp for AL1024ULXB2 power supply board.
• Automatic switch over to stand-by battery when AC fails.
• Zero voltage drop when unit switches over to battery backup (AC failure condition).
• Short circuit and thermal overload protection with auto reset.
• Green AC input and red DC output LED indicators on power supply board(s).
• Enclosure accommodates up to four (4) 12VDC/12AH batteries.
Enclosure dimensions: 26” x 19” x 6.25” (660.4mm x 482.6mm x 158.75mm).
Maximal Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and
authorities having jurisdiction. Product is intended for indoor use only.
Power Supply Board LED Diagnostics (pg. 6)
Access Power Controller LED Diagnostics (pg. 6)
Power Supply Board Terminal Identification (pg. 6)
Access Power Controller Terminal Identification (pg. 7)
Power Supply Board Stand-by Battery Specifications (pg. 7)
Power Supply Board Output Voltage Settings (pg. 8)
Access Power Controller Typical Application Diagram (pg. 8)
FACP/Optional Power Supply Hook-up Diagrams (pg. 16)
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top three keyholes in the
enclosure. Install three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the three upper screws, level and secure. Mark the position of the lower three holes.
Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes
over the three upper screws. Install the three lower screws and make sure to tighten all screws
Enclosure Dimensions, pg. 18).
2. The power supply is pre-wired to the ground (chassis). Connect main incoming ground to the provided green grounding conductor lead. Connect unswitched AC power (115VAC 60Hz) to the terminals marked [L, N] on both
power supply boards. Use 14 AWG or larger for all power connections.
Keep power-limited wiring separate from non power-limited wiring (120VAC 60Hz Input, Battery Wires).
Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
3. Select desired DC output voltage by setting SW1 to the appropriate position on the power supply board (Maximal11
and Maximal33), (Fig. 1, pg. 9). Maximal55 power supply is factory set at 12VDC. Maximal77 power supply is
factory set at 24VDC. Maximal75 consists of one (1) power supply board that is factory set at 12VDC, and one (1)
power supply board that is factory set at 24VDC.
4. Measure the output voltage of the unit before connecting any devices to ensure proper operation.
Improper or high voltage will damage these devices.
- 4 - Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused)
5. Output options (Fig. 2, pg. 9):
The unit will provide either sixteen (16) switched power outputs, sixteen (16) dry form “C” outputs, or any
combination of both switched power and form “C” outputs.
(a) Fail-Safe Switched Power outputs:
For Fail-Safe operation connect the positive (+) input of the access control devices to the terminal marked [NC].
Connect the negative (-) input of the access control devices to the terminal marked [COM].
(b) Fail-Secure Switched Power outputs:
For Fail-Secure operation connect the positive (+) input of the access control devices to the terminal marked [NO].
Connect the negative (-) input of the access control devices to the terminal marked [COM].
(c) Form “C” outputs:
When form “C” outputs are desired the corresponding output fuses (1-8) of each ACM8 board must be removed.
6. Auxiliary Power outputs (unswitched):Connect access control devices that require constant power to terminals marked [C] positive (+) and [COM] negative (-).
7. Input trigger options (Fig. 2, pg. 9):
(a) Normally Open [NO] input trigger:
Inputs 1-8 are activated by normally open or open collector sink inputs.
Connect access control panel outputs, keypads, push buttons, REX PIRs, etc. to the terminals marked [IN] and [GND].
(b) Open Collector Sink inputs:
Connect the access control panel open collector sink positive (+) to the terminals marked [IN] and the negative (-) to
terminals marked [GND].
8. Fire Alarm Interface options (Figs. 10-15, pg. 17): A normally closed [NC] or normally open [NO] input trigger from a fire alarm control panel or a polarity reversal
input from an FACP signaling circuit will affect selected outputs. To enable FACP Disconnect for an output turn the
corresponding switch [SW1-SW8] ON. To disable FACP disconnect for an output turn the corresponding switch
[SW1-SW8] OFF.
(a) Normally Open [NO] input:
For non-latching hook-up refer to (Fig. 12, pg. 17). For latching hook-up refer to (Fig. 13, pg. 17).
(b) Normally Closed [NC] input:
For non-latching hook-up refer to (Fig. 14, pg. 17). For latching hook-up refer to (Fig. 15, pg. 17).
(c) FACP Signaling Circuit input trigger:
Connect the positive (+) and negative (-) from the FACP signaling circuit output to the terminals marked [+ INP -].
Connect the FACP EOL to the terminals marked [+ RET -] (polarity is referenced in an alarm condition).
Jumper J3 must be cut (Fig. 11, pg. 17).
9. FACP Dry form “C” output (Fig. 2a, pg. 9):FACP form “C” contacts can be use to trigger reporting or signaling devices. These contact switch
upon a fire alarm input trigger to the ACM8 boards.
10. Stand-by Battery Connections(Figs. 3-5, pgs. 10-12):
For Access Control applications batteries are optional. If batteries are not used a loss of AC will result in the loss of
output voltage. Batteries must be lead acid or gel type. Connect one (1) 12VDC battery to the terminals marked
[+ BAT -] for 12VDC operation (Figs. 3, 5, pgs. 10, 12). Use two (2) 12VDC batteries wired in series for
24VDC operation (Figs. 3-5, pgs. 10-12).
11. Battery and AC Supervision outputs (Figs. 3-5, pgs. 10-12): It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT FAIL] supervisory
relay outputs marked [NC, C, NO] to appropriate visual notification devices. Use 22 AWG to 18 AWG for
AC Fail & Low/No Battery reporting.
12. Installation of tamper switch (Not Included) (Figs. 3a, 4a, 5a, pgs. 10-12):Mount UL Listed tamper switch (Sentrol model 3012 or equivalent) at the top of the enclosure. Slide the tamper
switch bracket onto the edge of the enclosure approximately 2” from the right side. Connect tamper switch wiring to
the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the door
of the enclosure.
13. Multiple power supply inputs (Fig. 2, pg. 9): When using an additional UL Listed external power supply, jumpers J1 and J2 located on corresponding
ACM8 boards must be cut (Fig. 2b, pg. 9 & Fig. 10, pg. 17). Connect external UL Listed power-limited access control power supply to the terminals marked [- Power +] (only applicable on Maximal11). When using DC power
supplies polarity must be observed. When using AC power supplies polarity need not be observed. All field wiring
connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute),
(Fig. 6a-9a, pgs. 13-16).
Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused) - 5 -
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
FACP Supervision: To ensure proper connection and operation of the Fire Alarm disconnect hookup. Please follow the
appropriate procedure below:
Normally Open Input: Placing a short between terminals marked [T] and [+ INP] will trigger the Fire Alarm Disconnect. Remove the short to reset.
Normally Closed Input: Remove the wire from terminal marked [INP -- ] will trigger the Fire Alarm Disconnect. Replace the wire to terminal marked [INP -- ] to reset.
FACP Signal Circuit Input: It is necessary to trigger the Fire Alarm System.In all of the above scenarios the green TRG LED of the ACM8s will illuminate. All outputs selected for Fire Alarm
Disconnect will activate releasing locking devices.
Note: All outputs [OUT 1 - OUT 8] must be in a normal (de-energized) condition prior to testing. When the unit is
configured for Normally Open (Fig. 13, pg. 17) or Normally Closed (Fig. 15, pg. 17) latching operation it is
necessary to reset the Fire Alarm Disconnect by activating the Normally Closed reset switch.
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage at the battery
terminals and at the board terminals marked [+ BAT – ] to ensure that there is no break in the battery connection wires.
Note: AL400ULXB2, AL600ULXB and AL1012ULXB Power Supply Board maximum charge current is 0.7 amp.
AL1024ULXB2 Power Supply Board maximum charge current is 3.6 amp.
Expected battery life is 5 years; however, it is recommended to change batteries within 4 years or less if necessary.
Power Supply Board LED Diagnostics:
LED
Red (DC)Green (AC)
ONONNormal operating condition.
ONOFFLoss of AC. Stand-by battery supplying power.
OFFONNo DC output. Short circuit or thermal overload condition.
OFFOFFNo DC output. Loss of AC. Discharged battery.
LED 1- LED 8 (Red)Output relay(s) energized.Output relay(s) de-energized.
Trg (Green)FACP input triggered (alarm condition).FACP normal (non-alarm condition).
- 6 - Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused)
Power Supply Board Terminal Identification:
Terminal
Legend
L, NConnect 115VAC 60Hz to these terminals: L to hot, N to neutral.
+ DC -
Function/Description
Maximal11 - 12VDC @ 3.5 amp or 24VDC @ 2.7 amp to ACM8 boards (power-limited).
Maximal33 - 12VDC @ 5.5 amp or 24VDC @ 5.7 amp to ACM8 boards (non power-limited).
Maximal55 - 12VDC @ 9.5 amp to ACM8 boards (power-limited).
Maximal77 - 24VDC @ 9.7 amp to ACM8 boards (power-limited).
Maximal75 - one (1) power supply which is 12VDC @ 9.5 amp to ACM8 board (non power-limited)
and one (1) power supply which is 24VDC @ 9.7 amp to ACM8 board (non power-limited).
AC FAIL
NC, C, NO
Indicates loss of AC power. To meet with UL requirements it is mandatory to connect visual notification
devices, connecting audible notification devices is optional. Relay normally energized when AC power is
present. Contact rating 1 amp @ 28VDC. AC or brownout fail is reported within 1 minute of event.
Indicates low battery condition, e.g. connect to access control panel. Relay normally energized when
DC power is present. Contact rating 1 amp @ 28VDC. A removed battery is reported within 5 minutes.
BAT FAIL
NC, C, NO
Battery reconnection is reported within 1 minute.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC.
24VDC output threshold set @ approximately 21VDC.
Stand-by battery connections. Connect one (1) 12VDC battery to the terminals marked [+ BAT -]
+ BAT -
for 12VDC operation (Fig. 3, pg. 10, Fig. 5, pg. 12). Use two (2) 12VDC batteries wired in series for
24VDC operation (Figs. 3-5, pgs. 10-12).
Access Power Controller Terminal Identification:
Terminal LegendFunction/Description
- Control +12VDC or 24VDC input from power supply board.
- Power +
(only applicable for
Maximal11)
TRIGGER
INPUT 1-INPUT 8
IN, GND
These terminals can be connected to an external UL Listed power-limited access control
power supply to provide isolated operating power for the ACM8 (jumpers J1 and J2 Must be
removed). All field wiring connections must be made employing suitable gauge CM or FPL
jacketed wire (or equivalent substitute), (Figs. 6a-9a, pgs. 13-16).
From normally open and/or open collector sink trigger inputs
(request to exit buttons, exit pir’s, etc.)
12VDC to 24VDC trigger controlled outputs:
Fail-Safe [NC positive (+) & COM Negative (-)],
OUTPUT 1OUTPUT 8
NC, C, NO, COM
Fail-Secure [NO positive (+) & COM Negative (-)],
Auxiliary output [C positive (+) & COM Negative (-)]
(When using AC power supplies polarity need not be observed),
NC, C, NO convert to dry form “C” 5 amp 24VAC/VDC rated dry outputs when fuses
are removed. Contacts shown in a non-triggered state.
FACP INTERFACE
T, + INPUT --
FACP INTERFACE
NC, C, NO
Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused) - 7 -
Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open,
normally closed from an FACP signaling circuit output (Figs. 10-15, pg. 17).
Form “C” relay contact rated @ 1 amp 28VDC for alarm reporting (not evaluated by UL).
Power Supply Board Stand-by Battery Specifications:
Altronix
Model
Maximal11
Maximal33
Maximal55
Maximal75
Maximal75
Maximal77
Power Supply BoardBattery20 Min. of Backup 4 Hr. of Backup24 Hr. of Backup
For this application
corresponding
fuse F8 must be
removed.
F5
NC C NO COM
OUTPUT 5
IN GND
7
8
F6F7F8
LED6
NC C NO COM
OUTPUT 6
LED7
MAG.
LOCK
LED8
NC C NO COM
OUTPUT 7
ON
1 2 3 4
NC C NO COM
OUTPUT 8
ON
1 2 3 4
J2
J3
J2
TRG
10A 250V
J1
J1
MAIN
FACP
NO C NC
FACP INTERFACE
NO C NC + INP --- T + RET -
SW1-SW8
ON
1
FACP Interface Disabled
1
ON
FACP Interface Enabled
Control
--- +
Power
--- +
AC or DC
POWER
SUPPLY
(req'd.)
AC or DC
POWER
SUPPLY
(optional)
Fig. 2b
Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused) - 9 -
Fig. 3
Edge of
Enclosure
to Access Control Panel
or U.L. Listed
Reporting Device
Enclosure
Sentrol
model # 3012
Tamper Switch
or equivalent
(Not Included)
Maximal11
Maximal33
Maximal55
Tamper Switch
Wire
Strap
(from
Enclosure
to Door)
115VAC Input
60 Hz.
Power Supply Board
L G N
Line
BAT FAIL
Neutral
NC C NO NC C NO
AC FAIL
Power Supply Board
L G N
Line
Neutral
BAT FAIL
Earth
Ground
Optional
12VDC Battery**
NC C NO NC C NO
AC FAIL
Optional
12VDC Battery**
*12VDC operation: For 12VDC operation
only a single battery is needed.
Connect red battery lead
to terminal marked
[+ BAT] and to the
[positive (+)] terminal
of the battery. Connect
black battery lead to
terminal marked [BAT -]
and to the [negative (-)]
*12VDC operation: For 12VDC operation
only a single battery is needed.
Connect red battery lead
to terminal marked
[+ BAT] and to the
[positive (+)] terminal
of the battery. Connect
black battery lead to
terminal marked [BAT -]
and to the [negative (-)]
**24VDC operation: Connect two (2) 12VDC batteries in series.
- 12 - Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused)
Fig. 5a
NEC Power-Limited Wiring Requirements for Maximal11:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring
must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring
and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this
is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may
be used. For power-limited applications use of conduit is optional. All field wiring connections must be made employing
suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 6a).
Fig. 6
Optional Battery
Enclosure
(non power-limited)
External UL Listed Power-Limited,
Access Control Power Supply
12 to 24VAC or DC
Supervisory
Connections
(power-limited)
115VAC Input
60Hz
(non power-limited)
ACM8
outputs
(powerlimited)
Fig. 6a
Incorrect Wire
Handling
External
Jacketed
Shield
Correct Wire
Handling
Battery Connections
(non power-limited)
Wire
Insulation
Solid Copper
Conductors
Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused) - 13 -
Pull back
external jacketed
shield approx. 1/2”.
NEC Power-Limited Wiring Requirements for Maximal33 and Maximal55:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring
must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring
and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this
is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may
be used. For power-limited applications use of conduit is optional. All field wiring connections must be made employing
suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 7a).
Fig. 7
Supervisory
Connections
Optional Battery
Enclosure
(non power-limited)
(power-limited)
Fig.7a
Incorrect Wire
Handling
Wire
Insulation
External
Jacketed
Shield
115VAC Input
60Hz
(non power-limited)
Battery Connections
(non power-limited)
Correct Wire
Handling
ACM8
outputs
(non power-
limited)
Solid Copper
Conductors
- 14 - Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused)
Pull back
external jacketed
shield approx. 1/2”.
NEC Power-Limited Wiring Requirements for Maximal77:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring
must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring
and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this
is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may
be used. For power-limited applications use of conduit is optional. All field wiring connections must be made employing
suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 8a).
Fig. 8
Supervisory
Connections
Optional Battery
Enclosure
(non power-limited)
(power-limited)
115VAC Input
60Hz
(non power-limited)
ACM8
outputs
(non power-
Fig. 8a
Incorrect Wire
Handling
Correct Wire
Handling
External
Jacketed
Shield
limited)
Battery Connections
Wire
Insulation
Solid Copper
Conductors
Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused) - 15 -
Pull back
external jacketed
shield approx. 1/2”.
(non power-limited)
NEC Power-Limited Wiring Requirements for Maximal75:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring
must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring
and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this
is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may
be used. For power- limited applications use of conduit is optional. All field wiring connections must be made employing
suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 9a).
Fig. 9
Supervisory
Connections
Optional Battery
Enclosure
(non power-limited)
(power-limited)
115VAC Input
60Hz
(non power-limited)
ACM8
outputs
(non power-
Fig. 9a
Incorrect Wire
Handling
Correct Wire
Handling
External
Jacketed
Shield
limited)
Battery Connections
(non power-limited)
Wire
Insulation
Solid Copper
Conductors
- 16 - Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused)
Pull back
external jacketed
shield approx. 1/2”.
FACP/Optional Power Supply Hook-up Diagrams:
Fig. 10 Optional hook-up using two (2) isolated power
supply inputs (Only applicable on Maximal11):
CUT JUMPERS
J1 AND J2
ISOLATED POWER INPUT
12 OR 24 VAC OR VDC
(ACM8 POWER)
ISOLATED POWER INPUT
12 OR 24 VAC OR VDC
(LOCK POWER)
Fig. 12 Normally Open - Non-Latching FACP
trigger input:
Fig. 11 Polarity reversal input from FACP signaling circuit
output (polarity is referenced in alarm condition):
CUT
JUMPER J3
FACP
SIGNAL CIRCUIT
OUTPUT EOL
FROM FACP
--
SIGNAL OUTPUT
+
CIRCUIT
FACP INTERFACE
NO C NC
Fig. 13 Normally Open FACP Latching trigger input with reset:
(This output has not been evaluated by UL)
Fig. 15 Normally Closed - Latching FACP trigger input
with reset:
(This output has not been evaluated by UL)
N.C. RESET
SWITCH
JUMPER
N.C. TRIGGER
INPUT
Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused) - 17 -
Enclosure Dimensions (H x W x D approximate):
(
)
26” x 19” x 6.25” (660.4mm x 482.6mm x 158.75mm)
19”
2”
(50.8mm)
4”
(101.6mm)
(482.6mm)
7”
(177.8mm)
TOP
4”
(101.6mm)
2”
(50.8mm)
6.25”
(158.75mm)
26”
(660.4mm)
8.5”
(215.9mm)
7.5”
(190.5mm)
10”
(254mm)
19”
1.25”
(31.75mm)
0.85”
(21.59mm)
(38.1mm)
26”
(660.4mm)
1.5”
8.9”
(226.06mm)
(482.6mm)
8.4”
(213.36mm)
0.85”
(21.59mm)
1.5”
(38.1mm)
(127mm)
(190.5mm)
5”
7.5”
LEFTRIGHT
1.25”
(31.75mm)
1.5”
(38.1mm)
7”
(177.8mm)
8.5”
(215.9mm)
(660.4mm)
7”
(177.8mm)
26”
1”
(25.4mm)
0.85”
(21.59mm)
8.9”
(226.06mm)
BOTTOM
19”
482.6mm
8.4”
(213.36mm)
(101.6mm)
4”
(50.8mm)
2”
1”
(25.4mm)
0.85”
(21.59mm)
6.25”
(158.75mm)
1.25”
(31.75mm)
2”
(50.8mm)
- 18 - Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused)
Notes:
Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused) - 19 -
Notes:
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A.
IIMaximal11/33/55/75/77 Series G16O
- 20 - Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused)
MEMBER
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.