Altronix MAXIMAL5, MAXIMAL3 Installation Manual

Page 1
Series
Access Power Controllers
Installation Guide
Models Include:
Maximal3
- 12VDC @ 5 amp or 24VDC @ 5.4 amp.
- Sixteen (16) fuse protected non power-limited outputs.
Maximal5
- 12VDC @ 9 amp.
Maximal7
- 24VDC @ 9.4 amp.
Altronix Corp.
140 58th St. Brooklyn, NY
Rev. SF110912
More than just power.
TM
Page 2
Table of Contents:
Maximal Series Overview ................................................................................................ 3
Maximal Series Configuration Chart................................................................................ 3
Maximal Series Features .................................................................................................. 3
Maximal Installation Instructions .................................................................................. 4-5
Maintenance ...................................................................................................................... 5
Power Supply Board LED Diagnostics ............................................................................ 5
Access Power Controller LED Diagnostics ..................................................................... 6
Power Supply Board Terminal Identification .................................................................. 6
Access Power Controller Terminal Identification ............................................................ 6
Power Supply Board Stand-by Battery Specifications ..................................................... 7
Power Supply Board Output Voltage Settings ................................................................. 7
Access Power Controller Typical Application Diagram .................................................. 8
Maximal3 and Maximal5 Battery Hookup and Tamper Switch Installation ................... 9
Maximal7 Battery Hookup and Tamper Switch Installation ......................................... 10
NEC Power-Limited Wiring Requirements for Maximal3 ............................................ 11
NEC Power-Limited Wiring Requirements for Maximal5 ............................................ 12
NEC Power-Limited Wiring Requirements for Maximal7 ............................................ 13
FACP Hook-up Diagrams .............................................................................................. 14
Enclosure Dimensions .................................................................................................... 15
- 2 - Maximal3/Maximal5/Maximal7 Access Power Controllers (Fused)
Page 3
Maximal Series Overview:
Maximal Access Power/Controllers distribute and switch power to access control systems and accessories. They convert a 115VAC 60Hz input into sixteen (16) independently controlled 12VDC or 24VDC fuse protected outputs. These Fail-Safe/ Fail-Secure power outputs may be converted to dry form “C” contacts. The outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Keypad, Push Button, REX PIR, etc. Units will route power to a variety of access control hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the sixteen (16) outputs. All interconnecting equipment must be UL Listed.
Maximal Series Configuration Chart:
Altronix
Model Number
Maximal3
Power Supply
Board Output
Voltage Options
12VDC @ 5 amp
or 24VDC @ 5.4 amp
Fuse Protected
Non Power-Limited
Outputs
Maximum Current
Per ACM8 Output
115VAC 60Hz Input
16
2.5
amp
3.5
amp
(current draw)
Power Supply Board
Input Fuse Rating
Power Supply
5A/
250V
------
Board Output
Fuse Rating
Agency Listings
and File Numbers
UL File # BP6714 UL 294 - UL Listed for Access ControlSystem Units.
Maximal5
Maximal7
12VDC @ 9 amp 16
24VDC @ 9.4 amp 16
2.5
amp
2.5
amp
2.6
amp
4.4
amp
5A/
250V
5A/
250V
15A/
32V
15A/
32V
General Signaling Equipment Evaluated to CSA Standard C22.2 No.205-M1983
Altronix Corp.
140 58th St. Brooklyn, NY
California State Fire Marshal Approved
Maximal Series Features:
• Sixteen (16) independently trigger controlled outputs. Output options: a) Sixteen (16) Fail-Safe filtered and electronically regulated power outputs. b) Sixteen (16) Fail-Secure filtered and electronically regulated power outputs. c) Sixteen (16) form “C” relay outputs (rated @ 5 amp/28VDC or VAC). d) Any combination of the above.
• Sixteen (16) Access Control System trigger inputs. Input trigger options: a) Sixteen (16) normally open (NO) dry trigger inputs. b) Sixteen (16) open collector inputs. c) Any combination of the above.
• Sixteen (16) unswitched filtered and electronically regulated aux. power outputs (outputs are rated @ 2.5 amp).
• Red LEDs on ACM8 board indicate individual outputs are triggered (relays energized).
• Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the sixteen (16) outputs. Fire Alarm disconnect input trigger options: a) Normally open (NO) or normally closed (NC) dry trigger input. b) Polarity reversal input from FACP signaling circuit.
• Green LED on ACM8 board indicates FACP disconnect is triggered.
• FACP output relay indicates that FACP input is triggered (form “C” contact rated @ 1 amp/28VDC not evaluated by UL).
• Power supply input is factory installed. It provides common power for both ACM8 boards and all connected access control devices.
• ACM8 board main fuses are rated @ 10 amp. Output fuses are rated @ 2.5 amp.
• Built-in charger for sealed lead acid or gel type batteries.
- Maximum charge current is 0.7 amp for AL600ULXB and AL1012ULXB power supply boards.
- Maximum charge current is 3.6 amp for AL1024ULXB2 power supply board.
• Automatic switch over to stand-by battery when AC fails.
• Zero voltage drop when unit switches over to battery backup (AC failure condition).
• Short circuit and thermal overload protection with auto reset.
• Green AC input and red DC output LED indicators on power supply board(s).
• AC fail supervision (form “C” contact rated @ 1 amp/28VDC).
• Battery fail and battery presence supervision (form “C” contact rated @ 1 amp/28VDC).
• Enclosure accommodates up to four (4) 12VDC/12AH batteries. Enclosure dimensions (H x W x D): 26” x 19” x 6.25” (660.4mm x 482.6mm x 158.75mm).
Maximal3/Maximal5/Maximal7 Access Power Controllers (Fused) - 3 -
Page 4
Maximal Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
Power Supply Board LED Diagnostics (pg. 5) Access Power Controller LED Diagnostics (pg. 6) Power Supply Board Terminal Identification (pg. 6) Access Power Controller Terminal Identification (pg. 6) Power Supply Board Stand-by Battery Specifications (pg. 7) Power Supply Board Output Voltage Settings (pg. 7) Access Power Controller Typical Application Diagram (pg. 8) FACP Hook-up Diagrams (pg. 14)
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws; level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the three upper screws. Install the three lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 15).
2. The power supply is pre-wired to the ground (chassis). Connect main incoming ground to the provided green grounding conductor lead. Connect unswitched AC power (115VAC 60Hz) to the terminals marked [L, N] on power supply board. Use 14 AWG or larger for all power connections. Keep power-limited wiring separate from non power-limited wiring. Minimum 0.25” spacing must be
provided (Figs. 5-7, pgs. 11-13). CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
3. Select desired DC output voltage by setting SW1 to the appropriate position on the Maximal3 power supply (Figs. 1 and 1a, pg. 7). Maximal5 power supply is factory set at 12VDC and Maximal7 power supply is factory set at 24VDC.
4. Measure the output voltage of the unit before connecting any devices to ensure proper operation. Improper or high voltage will damage these devices.
5. Output options (Fig. 2, pg. 8): The unit will provide either sixteen (16) switched power outputs, sixteen (16) dry form “C” outputs, or any combination of both switched power and form “C” outputs.
(a) Fail-Safe Switched Power outputs:
For Fail-Safe operation connect the positive (+) input of the access control devices to the terminal marked [NC]. Connect the negative (-) input of the access control devices to the terminal marked [COM]. (b) Fail-Secure Switched Power outputs: For Fail-Secure operation connect the positive (+) input of the access control devices to the terminal marked [NO]. Connect the negative (-) input of the access control devices to the terminal marked [COM].
(c) Form “C” outputs:
When form “C” outputs are desired the corresponding output fuses (1-8) of each ACM8 board must be removed.
6. Auxiliary Power outputs (unswitched): Connect access control devices that require constant power to the terminals marked [C] positive (+) and [COM] negative (-).
7. Input trigger options (Fig. 2, pg. 8):
(a) Normally Open [NO] input trigger:
Inputs 1-8 are activated by normally open or open collector sink inputs. Connect access control panel outputs, keypads, push buttons, REX PIRs, etc. to the terminals marked [IN] and [GND].
(b) Open Collector Sink inputs:
Connect the access control panel open collector sink positive (+) to the terminals marked [IN] and the negative (-) to terminals marked [GND].
8. Fire Alarm Interface options (Figs. 8-12, pg. 14): A normally closed [NC] or normally open [NO] input trigger from a fire alarm control panel or a polarity reversal input from an FACP signaling circuit will affect selected outputs. To enable FACP Disconnect for an output turn the corresponding switch(es) [SW1-SW8] ON on each ACM8 board. To disable FACP disconnect for an output turn the corresponding switch(es) [SW1-SW8] OFF on each ACM8 board.
(a) Normally Open [NO] input:
For non-latching hook-up refer to (Fig. 9, pg. 14). For latching hook-up refer to (Fig. 10, pg. 14).
(b) Normally Closed [NC] input:
For non-latching hook-up refer to (Fig. 11, pg. 14). For latching hook-up refer to (Fig. 12, pg. 14).
- 4 - Maximal3/Maximal5/Maximal7 Access Power Controllers (Fused)
Page 5
(c) FACP Signaling Circuit input trigger:
Connect the positive (+) and negative (-) from the FACP signaling circuit output to the terminals marked [+ INP -]. Connect the FACP EOL to the terminals marked [+ RET -] (polarity is referenced in an alarm condition). Jumper J3 must be cut (Fig. 8, pg. 14).
9. FACP Dry form “C” output (Fig. 2a, pg. 8): FACP form “C” contacts can be use to trigger reporting or signaling devices. These contact switch upon a fire alarm input trigger to the ACM8 boards.
10. Stand-by Battery Connections (Figs. 3-7, pgs. 9-13): For Access Control applications batteries are optional. If batteries are not used, a loss of AC will result in the loss of output voltage. Batteries must be lead acid or gel type. Connect one (1) 12VDC battery to the terminals marked [+ BAT -] for 12VDC operation (Fig. 3a, pg. 9). Use two (2) 12VDC batteries wired in series for 24VDC operation.
11. Battery and AC Supervision outputs (Figs. 3-4, pgs. 9-10): It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT FAIL] supervisory relay outputs marked [NC, C, NO] to appropriate visual notification devices. Use 22 AWG to 18 AWG for AC Fail and Low/No Battery reporting.
12. Installation of tamper switch (Not Included) (Figs. 3b-4a, pgs. 9-10): Mount UL Listed tamper switch (Sentrol model 3012 or equivalent) at the top of the enclosure. Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Figs. 3b and 4a, pgs. 9-10). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the door of the enclosure.
Maintenance:
Unit should be tested at least once a year for the proper operation as follows: FACP Supervision: To ensure proper connection and operation of the Fire Alarm disconnect hookup please follow the appropriate procedure below: Normally Open Input: Placing a short between terminals marked [T] and [+ INP] will trigger the Fire Alarm Disconnect. Remove the short to reset. Normally Closed Input: Removing the wire from terminal marked [INP -- ] will trigger the Fire Alarm Disconnect. Replace the wire to terminal marked [INP -- ] to reset. FACP Signal Circuit Input: It is necessary to trigger the Fire Alarm System. In all of the above scenarios the green TRG LED of the ACM8s will illuminate. All outputs selected for Fire Alarm Disconnect will activate releasing locking devices. Note: All outputs [OUT 1 - OUT 8] must be in a normal (de-energized) condition prior to testing. When the unit is configured for Normally Open (Fig. 10, pg. 14) or Normally Closed (Fig. 12, pg. 14) latching operation it is necessary to reset the Fire Alarm Disconnect by activating the Normally Closed reset switch. Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper voltage level
(Power Supply Board Stand-by Battery Specifications, pg. 7).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage at the battery terminals and at the board terminals marked [+ BAT -] to ensure that there is no break in the battery connection wires. Note: AL600ULXB and AL1012ULXB Power Supply Board maximum charge current is 0.7 amp. AL1024ULXB2 Power Supply Board maximum charge current is 3.6 amp. Expected battery life is 5 years, however it is recommended to change batteries within 4 years or less if necessary.
Power Supply Board LED Diagnostics:
LED
Red (DC) Green (AC)
ON ON Normal operating condition. ON OFF Loss of AC. Stand-by battery supplying power. OFF ON No DC output. Short circuit or thermal overload condition. OFF OFF No DC output. Loss of AC. Discharged battery.
Maximal3/Maximal5/Maximal7 Access Power Controllers (Fused) - 5 -
Power Supply Status
Page 6
Power Supply Board LED Diagnostics (cont’d):
Red (Bat) Battery Status
ON Normal operating condition. OFF Battery fail/low battery.
Access Power Controller LED Diagnostics:
LED ON OFF
LED 1- LED 8 (Red) Output relay(s) energized. Output relay(s) de-energized. Trg (Green) FACP input triggered (alarm condition). FACP normal (non-alarm condition).
Power Supply Board Terminal Identification:
Terminal Legend
L, G, N Connect 115VAC 60Hz to these terminals: L to hot, N to neutral.
+ DC --
Function/Description
Maximal3 - 12VDC @ 5 amp or 24VDC @ 5.4 amp to ACM8 boards (non power-limited) Maximal5 - 12VDC @ 9 amp to ACM8 boards (non power-limited). Maximal7 - 24VDC @ 9.4 amp to ACM8 boards (non power-limited).
AC FAIL NC, C, NO
BAT FAIL NC, C, NO
+ BAT --
Indicates loss of AC power. To meet with UL requirements it is mandatory to connect visual notification devices, connecting audible notification devices is optional. Relay normally energized when AC power is present. Contact rating 1 amp @ 28VDC. AC or brownout fail is reported within 1 minute of event.
Indicates low battery condition, e.g. connect to access control panel. Relay normally energized when DC power is present. Contact rating 1 amp @ 28VDC. A removed battery is reported within 5 minutes. Battery reconnection is reported within 1 minute. Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC. 24VDC output threshold set @ approximately 21VDC.
Stand-by battery connections. Connect one (1) 12VDC battery to the terminals marked [+ BAT -] for 12VDC operation (Figs. 3 and 3a, pg. 9). Use two (2) 12VDC batteries wired in series for 24VDC operation (Fig. 4, pg. 10).
Access Power Controller Terminal Identification:
Terminal Legend Function/Description
- Control + 12VDC or 24VDC input from power supply board.
- Power + Not applicable.
TRIGGER INPUT 1- INPUT 8 IN, GND
OUTPUT 1­OUTPUT 8 NC, C, NO, COM
FACP INTERFACE T, + INPUT --
FACP INTERFACE NC, C, NO
From normally open and/or open collector sink trigger inputs (request to exit buttons, exit pir’s, etc.).
12VDC to 24VDC trigger controlled outputs: Fail-Safe [NC positive (+) & COM Negative (-)], Fail-Secure [NO positive (+) & COM Negative (-)], Auxiliary output [C positive (+) & COM Negative (-)] (When using AC power supplies polarity need not be observed), NC, C, NO convert to dry form “C” 5 amp 24VAC/VDC rated dry outputs when fuses are removed. Contacts shown in a non-triggered state.
Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open, normally closed from an FACP signaling circuit output (Figs. 8-12, pg. 14).
Form “C” relay contact rated @ 1 amp 28VDC for alarm reporting (not evaluated by UL).
- 6 - Maximal3/Maximal5/Maximal7 Access Power Controllers (Fused)
Page 7
Power Supply Board Stand-by Battery Specifications:
ON
OFF - 24V
ON - 12V
Altronix Model:
Maximal3
Maximal5
Maximal7
*Note: Additional battery enclosure required (Figs. 5-7, pgs. 11-13).
Power Supply Board Battery
AL600ULXB
(Refer to Fig. 1a, pg. 7 for Switch
[SW1] location and position)
AL1012ULXB
(Factory set at 12VDC)
AL1024ULXB2
(Factory set at 24VDC)
12VDC/40AH* N/A 5.0 amp N/A
24VDC/40AH* N/A 5.4 amp 0.7 amp
12VDC/12AH 9.0 amp
24VDC/12AH 7.7 amp 1.2 amp 200mA
24VDC/65AH* N/A 7.7 amp 1.2 amp
Power Supply Board Output Voltage Settings:
Fig. 1
20 Min. of
Backup
4 hr. of
Backup
Battery capacity for
emergency stand-by
at least 20 min.
24 hr. of
Backup
N/A
Maximal3 Power Supply Board
OFF - 24V ON - 12V
ON
SW1
+ DC ---
Fig. 1a
Maximal3/Maximal5/Maximal7 Access Power Controllers (Fused) - 7 -
Page 8
Fig. 2
Access Power Controller Typical Application Diagram (for each ACM8):
ACCESS CONTROL
OUTPUT
RELAY
MAG. LOCK
KEYPAD
PANEL
NORMALLY OPEN
N.O. DOOR
RELEASING DEVICE
C
NO
NC
IN GND1IN GND2IN GND3IN GND4IN GND5IN GND6IN GND
F1
3.5A 250V 3.5A 250V 3.5A 250V3.5A 250V 3.5A 250V3.5A 250V3.5A 250V 3.5A 250V
LED1
NC C NO COM OUTPUT 1
LED2
NC C NO COM OUTPUT 2
F2
F3
LED3
NC C NO COM OUTPUT 3
F4
LED4
NC C NO COM OUTPUT 4
F5
LED5
NC C NO COM OUTPUT 5
IN GND
7
8
F6 F7 F8
LED6
NC C NO COM OUTPUT 6
LED7
NC C NO COM OUTPUT 7
ON
LED8
(Fire Alarm
Control Panel)
ON
1 2 3 4
NC C NO COM OUTPUT 8
FACP
J3
1 2 3 4
J2
TRG
10A 250V
J1
MAIN
Fig. 2a
FACP Dry
Form "C"
Output
FACP
NO C NC
FACP INTERFACE
NO C NC + INP --- T + RET -
Control
--- +
Power
--- +
SW1-SW8
1
ON
FACP Interface Disabled
1
ON
FACP Interface Enabled
ELECTRIC
STRIKE
ELECTROMAGNETIC
DOOR HOLDERS
UL Listed POWER SUPPLY
For this application corresponding fuse F8 must be removed.
MAG. LOCK
J2
J1
Fig. 2b
AC or DC
POWER
SUPPLY
(optional)
AC or DC
POWER SUPPLY
(req'd.)
- 8 - Maximal3/Maximal5/Maximal7 Access Power Controllers (Fused)
Page 9
Fig. 3
Edge of
Enclosure
to Access Control Panel
or U.L. Listed
Reporting Device
Enclosure
Sentrol
model # 3012
Tamper Switch
or equivalent
(Not Included)
Maximal3 Maximal5
Wire Strap (from Enclosure to Door)
Power Supply Board
Tamper Switch
Maximal5
--- DC +
+ DC ---
115VAC Input
60 Hz.
+ BAT ---
L G N
Line
Neutral
BAT FAIL
Earth
Ground
NO C NC NO C NC
AC FAIL
*12VDC operation: For 12VDC operation only a single battery is needed.
Connect red battery lead to terminal marked [+ BAT] and to the [positive (+)] terminal of the battery.
+ BAT ---
Connect black battery lead to terminal marked [BAT -- ] and to the [negative (--)] terminal of the battery.
Fig. 3a
Optional
12VDC Battery*
Optional
12VDC Battery**
Optional
12VDC Battery**
FACP INTERFACE
NO C NC + INP --- T + RET -
TRG
J3
1 2 3 4
ON
1 2 3 4
ON
8
F6 F7 F8
IN GND
7
IN GND
6
IN GND
F5
5
IN GND
F4
4
IN GND
3
IN GND
2
F3
IN GND
1
IN GND
F2
F1
3.5A 250V 3.5A 250V 3.5A 250V3.5A 250V 3.5A 250V3.5A 250V3.5A 250V 3.5A 250V
FACP INTERFACE
NO C NC + INP --- T + RET -
TRG
J3
1 2 3 4
ON
1 2 3 4
ON
8
F6 F7 F8
IN GND
7
IN GND
6
IN GND
F5
5
IN GND
F4
4
IN GND
3
IN GND
2
F3
IN GND
1
IN GND
F2
F1
3.5A 250V 3.5A 250V 3.5A 250V3.5A 250V 3.5A 250V3.5A 250V3.5A 250V 3.5A 250V
Control
Power
--- +
MAIN
MAIN
--- +
J1
10A 250V
J2
NC C NO COM
OUTPUT 8
LED8
NC C NO COM
OUTPUT 7
LED7
NC C NO COM
OUTPUT 6
LED6
NC C NO COM
OUTPUT 5
LED5
LED4
NC C NO COM
OUTPUT 4
NC C NO COM
OUTPUT 3
LED3
LED2
OUTPUT 2
NC C NO COM
LED1
OUTPUT 1
NC C NO COM
Control
Power
--- +
--- +
J1
10A 250V
J2
OUTPUT 8
NC C NO COM
LED8
OUTPUT 7
NC C NO COM
LED7
OUTPUT 6
NC C NO COM
LED6
OUTPUT 5
NC C NO COM
LED5
LED4
OUTPUT 4
NC C NO COM
OUTPUT 3
NC C NO COM
LED3
LED2
OUTPUT 2
NC C NO COM
LED1
OUTPUT 1
NC C NO COM
**24VDC operation: Connect two (2) 12VDC batteries in series
Fig. 3b
Maximal3/Maximal5/Maximal7 Access Power Controllers (Fused) - 9 -
Page 10
Fig. 4
Edge of
Enclosure
to Access Control Panel
or U.L. Listed
Reporting Device
Enclosure
Sentrol
model # 3012
Tamper Switch
or equivalent
(Not Included)
Maximal7
Tamper Switch
115VAC Input
60 Hz.
5A 250V
L G N
Line
12VDC Battery**
Power Supply Board
Neutral
Earth
Ground
Optional
BAT FAIL
NC C NO NC C NO
15A 32V
15
DCAC
AC FAIL
AC DELAY
Optional
12VDC Battery**
+ DC --- --- BAT +
FACP INTERFACE
NO C NC + INP --- T + RET -
TRG
J3
1 2 3 4
ON
1 2 3 4
ON
8
F6 F7 F8
IN GND
7
IN GND
6
IN GND
F5
5
IN GND
F4
4
IN GND
3
IN GND
2
F3
IN GND
1
3.5A 250V
IN GND
F2
3.5A 250V 3.5A 250V
F1
3.5A 250V 3.5A 250V 3.5A 250V3.5A 250V 3.5A 250V
FACP INTERFACE
NO C NC + INP --- T + RET -
TRG
J3
1 2 3 4
ON
1 2 3 4
ON
8
F6 F7 F8
IN GND
7
IN GND
6
IN GND
F5
5
IN GND
F4
4
IN GND
3
IN GND
2
F3
IN GND
1
IN GND
F2
F1
3.5A 250V 3.5A 250V 3.5A 250V3.5A 250V 3.5A 250V3.5A 250V3.5A 250V 3.5A 250V
Control
Power
--- +
MAIN
MAIN
--- +
J1
10A 250V
J2
NC C NO COM
OUTPUT 8
LED8
NC C NO COM
OUTPUT 7
LED7
NC C NO COM
OUTPUT 6
LED6
NC C NO COM
OUTPUT 5
LED5
LED4
NC C NO COM
OUTPUT 4
NC C NO COM
OUTPUT 3
LED3
LED2
NC C NO COM
OUTPUT 2
LED1
NC C NO COM
OUTPUT 1
Control
Power
--- +
--- +
J1
10A 250V
J2
NC C NO COM
OUTPUT 8
LED8
NC C NO COM
OUTPUT 7
LED7
NC C NO COM
OUTPUT 6
LED6
NC C NO COM
OUTPUT 5
LED5
LED4
NC C NO COM
OUTPUT 4
NC C NO COM
OUTPUT 3
LED3
LED2
NC C NO COM
OUTPUT 2
LED1
NC C NO COM
OUTPUT 1
**24VDC operation: Connect two (2) 12VDC batteries in series
Fig. 4a
- 10 - Maximal3/Maximal5/Maximal7 Access Power Controllers (Fused)
Page 11
NEC Power-Limited Wiring Requirements for Maximal3:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 5a).
Fig. 5
Supervisory
Connections
(power-limited)
Optional Battery
Enclosure
(non power-limited)
Fig. 5a
Incorrect Wire
Handling
Insulation
Solid Copper
Conductors
115VAC Input
60Hz
(non power-limited)
ACM8 outputs
(non power-
limited)
Battery
Connections
(non power-limited)
Correct Wire
Handling
External Jacketed
Shield
Wire
Pull back external jacketed shield approx. 1/2”.
Maximal3/Maximal5/Maximal7 Access Power Controllers (Fused) - 11 -
Page 12
NEC Power-Limited Wiring Requirements for Maximal5:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 6a).
Fig. 6
Supervisory
Connections
(power-limited)
Optional Battery
Enclosure
(non power-limited)
Fig. 6a
Incorrect Wire
Handling
Insulation
Solid Copper
Conductors
115VAC Input
60Hz
(non power-limited)
ACM8 outputs
(non power-
limited)
Battery
Connections
(non power-limited)
Correct Wire
Handling
External Jacketed
Shield
Wire
Pull back external jacketed shield approx. 1/2”.
- 12 - Maximal3/Maximal5/Maximal7 Access Power Controllers (Fused)
Page 13
NEC Power-Limited Wiring Requirements for Maximal7:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 7a).
Fig. 7
Supervisory
Connections
Optional Battery
Enclosure
(non power-limited)
(power-limited)
115VAC Input
60Hz
(non power-limited)
ACM8
outputs
(non power-
limited)
Incorrect Wire
Handling
Fig. 7a
Insulation
Solid Copper
Conductors
Maximal3/Maximal5/Maximal7 Access Power Controllers (Fused) - 13 -
External
Jacketed
Shield
Wire
Correct Wire
Handling
Battery
Connections
(non power-limited)
Pull back external jacketed shield approx. 1/2”.
Page 14
FACP Hook-up Diagrams:
Fig. 8 Polarity reversal input from FACP signaling circuit output (polarity is referenced in alarm condition):
CUT
JUMPER J3
FACP
SIGNAL CIRCUIT
OUTPUT EOL
FROM FACP
--
SIGNAL OUTPUT
+
CIRCUIT
FACP INTERFACE
NO C NC
Fig. 9 Normally Open - Non-Latching FACP trigger input:
N.O. TRIGGER
INPUT
FACP INTERFACE
NO C NC
Fig. 11 Normally Closed - Non-Latching FACP trigger input:
N.C. DRY
TRIGGER
INPUT
Fig. 10 Normally Open FACP Latching trigger input with reset: (This output has not been evaluated by UL)
N.O.
TRIGGER
INPUT
JUMPER
N.C.
RESET
SWITCH
NO C NC
Fig. 12 Normally Closed - Latching FACP trigger input with reset: (This output has not been evaluated by UL)
N.C. RESET
SWITCH
JUMPER
JUMPER
N.C. TRIGGER
INPUT
FACP INTERFACE
NO C NC
- 14 - Maximal3/Maximal5/Maximal7 Access Power Controllers (Fused)
Page 15
Enclosure Dimensions (H x W x D approximate):
(
)
26” x 19” x 6.25” (660.4mm x 482.6mm x 158.75mm)
19”
2”
(50.8mm)
4”
(101.6mm)
(482.6mm)
7”
(177.8mm)
TOP
4”
(101.6mm)
2”
(50.8mm)
6.25”
(158.75mm)
26”
(660.4mm)
8.5”
(215.9mm)
7.5”
(190.5mm)
10”
(254mm)
19”
1.25”
(31.75mm)
0.85”
(21.59mm)
(38.1mm)
26”
(660.4mm)
1.5”
8.9”
(226.06mm)
(482.6mm)
8.4”
(213.36mm)
0.85”
(21.59mm)
1.5”
(38.1mm)
(127mm)
(190.5mm)
5”
7.5”
LEFT RIGHT
1.25”
(31.75mm)
1.5”
(38.1mm)
7”
(177.8mm)
8.5”
(215.9mm)
(660.4mm)
7”
(177.8mm)
26”
1”
(25.4mm)
0.85”
(21.59mm)
8.9”
(226.06mm)
BOTTOM
19”
482.6mm
8.4”
(213.36mm)
(101.6mm)
4”
2”
(50.8mm)
1”
(25.4mm)
0.85”
(21.59mm)
6.25”
(158.75mm)
1.25”
(31.75mm)
2”
(50.8mm)
Maximal3/Maximal5/Maximal7 Access Power Controllers (Fused) - 15 -
Page 16
Notes:
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A. IIMaximal3/5/7 Series G16O
- 16 - Maximal3/Maximal5/Maximal7 Access Power Controllers (Fused)
MEMBER
Loading...