Altronix Maximal37FEV, Maximal13FEV, Maximal33FEV, Maximal35FEV, Maximal55FEV Installation Manual

...
Rev. MFEV031215
More than just power.
TM
Expandable Power Systems
Installation Guide
Models Include:
Maximal11FEV
Maximal13FEV
Maximal33FEV
Maximal35FEV
- Power Supply 2: 12VDC @ 10A.
Maximal37FEV
- Power Supply 2: 24VDC @ 10A.
Maximal55FEV
- Power Supply 1: 12VDC @ 10A.
- Power Supply 2: 12VDC @ 10A.
Maximal75FEV
- Power Supply 1: 24VDC @ 10A.
- Power Supply 2: 12VDC @ 10A.
Maximal77FEV
- Power Supply 1: 24VDC @ 10A.
- Power Supply 2: 24VDC @ 10A.
- 2 - MaximalFEV Expandable Power Systems
Table of Contents:
MaximalFEV Overview ................................................................................pg. 3
MaximalFEV Features ...........................................................pg. 3
Agency Listings .................................................................pg. 3
MaximalFEV Series Configuration Chart ...........................................pg. 4
MaximalFEV Installation Instructions .............................................pg. 5
Maintenance ...................................................................pg. 5
Power Supply Board Terminal Identification .......................................pg. 6
Power Supply Board Stand-by Battery Specifications ................................pg. 6
Power Supply Board LED Diagnostics .............................................pg. 7
Power Supply Board Output Voltage Settings .......................................pg. 7
Battery Setup and Tamper Switch Installation ......................................pg. 8
NEC Power-Limited Wiring Requirements for MaximalFEV ..........................pg. 9
Enclosure Dimensions ...........................................................pg. 11
MaximalFEV Expandable Power Systems - 3 -
MaximalFEV Overview:
Maximal Expandable Power Systems provide system designers and installers with optimum power choices and the highest levels of versatility. They provide 12VDC, 24VDC, or 12VDC and 24VDC simultaneously via two (2) single output power supply/chargers. Includes AC fail, low battery, and battery presence monitoring. Enclosure facilitates up to four (4) 12VDC/12AH batteries.
MaximalFEV Features:
Input:
• 220VAC (working range 198VAC - 256VAC), 50/60Hz.
Output:
• For output voltage and supply current, refer to MaximalFEV series Configuration Chart, pg. 4.
• Auxiliary power-limited output rated @ 1A (unswitched).
• Overvoltage protection.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 1.54A.
• Automatic switch over to stand-by battery when AC fails. Transfer to stand-by battery power is instantaneous with no interruption.
Fire Alarm Disconnect:
• Supervised Fire Alarm disconnect (latching or non­ latching) 10K EOL resistor. Operates on a normally open (NO) or normally closed (NC) trigger.
Supervision:
• AC fail supervision (form “C” contacts).
• Battery fail and presence supervision (form “C” contacts).
• Low power shutdown. Shuts down DC output terminals if battery voltage drops below 71-73% for 12V units and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
Fuse Ratings:
Refer to MaximalFEV series Configuration Chart, pg. 4.
Visual Indicators:
• Green AC Power LED indicates 220VAC present.
• AC input and DC output LED indicators.
Additional Features:
• Short circuit and overload protection.
• Unit is complete with power supply, enclosure, battery leads and cam lock.
- 4 - MaximalFEV Expandable Power Systems
MaximalFEV Series Configuration Chart:
Altronix Model Number
Nominal DC Output Voltage Options
Maximum Supply Current for Main and Aux.
Outputs (Power Supply 1/Power Supply 2) (A)
Non Power-Limited Outputs
Power-Limited Outputs
Aux. Power-Limited Outputs
Input Rating: 220VAC 50/60Hz (A)
Input Fuse Rating
(per eFlow Power Supply Board)
Battery Fuse Rating
(per eFlow Power Supply Board)
Ripple Voltage (mV)
Under low battery condition
Power Supply 1 Power Supply 2
[DC] [AUX] [DC] [AUX]
12VDC Output Range (V)
24VDC Output Range (V)
12VDC Output Range (V)
24VDC Output Range (V)
12VDC Output Range (V)
24VDC Output Range (V)
12VDC Output Range (V)
24VDC Output Range (V)
Maximal11FEV
eFlow4NBV eFlow4NBV
4A
+ 4A– 2 2 4.2 5A/250V 7.5A/32V 730
10.1-
13.2
10.05-
13.2
10.1-
13.2
10.05-
13.2
10.1-
13.2
10.05-
13.2
20.28-
26.4
20.2-
26.4
20.28-
26.4
20.2-
26.4
20.28-
26.4
20.2-
26.4
Maximal13FEV
eFlow4NBV eFlow6NBV
4A
+ 6A1 1 2 4.2 5A/250V
7.5A/32V
(eFlow4NBV)
10A/32V
(eFlow6NBV)
730
(eFlow4NBV)
910
(eFlow6NBV)
10.1-
13.2
10.05-
13.2
10.0-
13.2
10.03-
13.2
10.1-
13.2
10.05-
13.2
20.19-
26.4
20.19-
26.4
20.28-
26.4
20.2-
26.4
10.0-
13.2
10.03-
13.2
20.28-
26.4
20.2-
26.4
20.19-
26.4
20.19-
26.4
Maximal33FEV
eFlow6NBV eFlow6NBV
6A
+ 6A2 2 4.2 5A/250V 10A/32V 910
10.0-
13.2
10.03-
13.2
10.0-
13.2
10.03-
13.2
10.0-
13.2
10.03-
13.2
20.19-
26.4
20.19-
26.4
20.19-
26.4
20.19-
26.4
20.19-
26.4
20.19-
26.4
Maximal35FEV
eFlow6NBV eFlow102NBV
6A
+
10A
2 2 4.2 5A/250V
10A/32V
(eFlow6NBV)
15A/32V
(eFlow102NBV)
910
(eFlow6NBV)
760
(eFlow102NBV)
10.0-
13.2
10.03-
13.2
10.03-
13.2
10.03-
13.2
20.19-
26.4
20.19-
26.4
10.03-
13.2
10.03-
13.2
Maximal37FEV
eFlow6NBV eFlow104NBV
6A
+
10A
2 2 4.8
5A/250V
(eFlow6NBV)
6.3A/250V
(eFlow104NBV)
10A/32V
(eFlow6NBV)
15A/32V
(eFlow104NBV)
910
(eFlow6NBV)
700
(eFlow104NBV)
10.0-
13.2
10.03-
13.2
20.17-
26.4
20.28-
26.4
20.19-
26.4
20.19-
26.4
20.17-
26.4
20.28-
26.4
Maximal55FEV
eFlow102NBV eFlow102NBV
10A
+
10A
2 2 4.2 5A/250V 15A/32V 760
10.03-
13.2
10.03-
13.2
10.03-
13.2
10.03-
13.2
Maximal75FEV
eFlow102NBV eFlow104NBV
10A
+
10A
2 2 4.8
5A/250V
(eFlow102NBV)
6.3A/250V
(eFlow104NBV)
15A/32V
760
(eFlow102NBV)
700
(eFlow104NBV)
10.03-
13.2
10.03-
13.2
20.17-
26.4
20.28-
26.4
Maximal77FEV
eFlow104NBV eFlow104NBV
10A
+
10A
2 2 5.6 6.3A/250V 15A/32V 700
20.17-
26.4
20.28-
26.4
20.17-
26.4
20.28-
26.4
Loading...