Maximal11E
Expandable Power System
Overview
Maximal11E provides system designers and installers with “maximum” power choices
and the highest levels of versatility. It provides 12VDC, 24VDC, or 12VDC and 24VDC
simultaneously via two (2) single output power supply/chargers. It includes AC fail, low
battery and battery presence monitoring. Optional Altronix
sub-assemblies provide multiple outputs and a wide range of features for specific Access
Control and Fire Alarm applications.
Maximal11E
Specifications
Input:
• 115VAC 60Hz, 4.5 amp input.
Output:
• 12VDC and/or 24VDC outputs.
• Maximum output current:
Options P/S 1 P/S 2
A 12VDC @ 3.5 amp 12VDC @ 3.5 amp
B 24VDC @ 2.7 amp 24VDC @ 2.7 amp
C 12VDC @ 3.5 amp 24VDC @ 2.7 amp
• Class 2 Rated power limited outputs.
• Filtered and electronically regulated outputs (built-in
power supply).
• Thermal and short circuit protection with auto reset.
Fuse Ratings:
• Power Supply input fuse rated @ 3.5 amp/250V.
Features:
• AC fail supervision (form “C” contact).
• Low battery and battery presence supervision
(form “C” contact).
Battery Backup:
• Built-in charger for sealed lead acid or gel type
batteries.
Rev. DSMaximal11E - 06172013
®
field installable UL Listed
Battery Backup (cont’d):
• Maximum charge current 0.7 amp per p/s board.
• Automatic switch over to stand-by battery when
AC fails.
• Zero voltage drop when unit switches over to battery
backup (AC failure condition).
Visual Indicators:
• AC input and DC output LED indicators.
Electrical:
• Operating temperature: 0º C to 49º C ambient.
• BTU/Hr.:
- 12VDC: 43.00 BTU/Hr.
- 24VDC: 66.33 BTU/Hr.
- 12VDC & 24VDC: 54.66 BTU/Hr.
• System AC input VA requirement: 517.5VA.
Mechanical:
• Enclosure Dimensions (H x W x D approx.):
26” x 19” x 6.25” (660.4mm x 482.6mm x 158.75mm)
• Enclosure accommodates up to four (4)
12AH batteries.
• Product weight (approx.): 42.3 lbs. (19.17 kg).
• Shipping weight (approx.): 46.3 lbs. (21.00 kg).
Power Supply
Power Supply
Stand-by
Battery
(optional)
Stand-by
Battery
(optional)
Optional Field Installable UL Listed Sub Assembly Modules
Location A - ACM4, ACM4CB, MOM5, PD4UL, PD4ULCB,
PD8UL, PD8ULCB, PD16W & PD16WCB.
Location B - ACM4, ACM4CB, ACM8, ACM8CB, MOM5,
PD4UL, PD4ULCB, PD8UL, PD8ULCB, PD16W & PD16WCB.
Location C - ACM4, ACM4CB, ACM8, ACM8CB, MOM5,
PD4UL, PD4ULCB, PD8UL, PD8ULCB, PD16W & PD16WCB.
Stand-by
Battery
(optional)
Stand-by
Battery
(optional)
A
B
C
Agency Approvals
UL Listed for Access Control System Units
(UL 294).
Enclosure Dimensions (H x W x D approximate):
26” x 19” x 6.25” (660.4mm x 482.6mm x 158.75mm)
2”
(50.8mm)
4”
(101.6mm)
19”
(482.6mm)
7”
(177.8mm)
TOP
140 58th St. Brooklyn, NY
CSFM
California State Fire Marshal Approved.
4”
(101.6mm)
2”
(50.8mm)
6.25”
(158.75mm)
26”
(660.4mm)
8.5”
(215.9mm)
7.5”
(190.5mm)
10”
(254mm)
19”
1.25”
(31.75mm)
0.85”
(21.59mm)
(38.1mm)
26”
(660.4mm)
1.5”
8.9”
(226.06mm)
(482.6mm)
8.4”
(213.36mm)
0.85”
(21.59mm)
1.5”
(38.1mm)
(127mm)
(190.5mm)
5”
7.5”
LEFT RIGHT
1”
(25.4mm)
0.85”
(21.59mm)
8.9”
(226.06mm)
8.4”
(213.36mm)
1”
(25.4mm)
0.85”
(21.59mm)
1.25”
(31.75mm)
1.25”
(31.75mm)
1.25”
(31.75mm)
1.5”
(38.1mm)
7”
(177.8mm)
8.5”
(215.9mm)
(660.4mm)
7”
(177.8mm)
2”
(50.8mm)
26”
BOTTOM
482.6mm
Altronix Corp. - 140 58th Street, Brooklyn, NY 11220 • 718-567-8181 • 888-258-7669 • altronix.com
6.25”
(158.75mm)
4”
19”
(101.6mm)
2”
(50.8mm)