Altronix MAXFIT7FA8PS, MAXFIT7F8AP, MAXFIT7F16APS, MAXFIT7F16AP Installation Guide

Access Power Controllers
MaxFit7F8AP
Fully assembled kit includes:
- One (1) ACM8 - Fuse Protected Access Power Controller
- One (1) PD8UL - Fuse Protected Power Distribution Module
- BC750 enclosure
MaxFit7F16AP
Fully assembled kit includes:
- Two (2) ACM8 - Fuse Protected Access Power Controllers
- One (1) PD16W - Fuse Protected Power Distribution Module
- BC750 enclosure
MaxFit7F8APS
Fully assembled kit includes:
- One (1) ACM8 - Fuse Protected Access Power Controller
- One (1) PDS8 - Dual Input Fuse Protected Power Distribution Module
- One (1) VR6 - Voltage Regulator
- BC750 enclosure
MaxFit7F16APS
Fully assembled kit includes:
- Two (2) ACMS8 - Dual Input Fuse Protected Access Power Controllers
- One (1) VR6 - Voltage Regulator
- One (1) PD16W - Fuse Protected Power Distribution Module.
- BC750 enclosure
Installation Guide
Rev. MFKF_083019
Installing Company: _____________________ Service Rep. Name: __________________________________________
Address: ________________________________________________________ Phone #: _________________________
More than just power.™
Overview:
Tamper Switch
To Access Control Panel or UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Altronix fused Access Power Controller kits distribute and switch power to access control systems and accessories. They convert a 120VAC 60Hz input into eight (8) or sixteen (16) independently controlled 12VDC or 24VDC fuse protected outputs. These Fail-Safe/ Fail-Secure power outputs may be converted to dry form “C” contacts. Relays are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Keypad, Push Button, REX PIR, etc. Units will route power to a variety of access control hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the eight (8) Fail-Safe/Fail-Secure power outputs. Additional fuse protected outputs provide power for connected devices.
Configuration Chart:
Altronix Model Number
MaxFit7F8AP
MaxFit7F16AP
MaxFit7F8APS
MaxFit7F16APS
Power Supply Board
Input Fuse Rating
Power Supply Board
Battery Fuse Rating
120VAC 60Hz
6.3A/
15A/
250V
32V
4.5
Maximum Supply Current for Main and Aux. Outputs
on Power Supply
board and ACM8/
ACMS8 Access
Power Controllers’
Input Current (A)
outputs
24VDC @ 9.7A
24VDC @ 9.4A 16 16
24VDC @ 9.4A 8 8
24VDC @ 9.4A 16 16
Nominal DC
Output Voltage
[DC] [Aux]
Output
Range
(VDC)
20.17-
26.4
Output
Range (VDC)
20.28-
26.4
Fail-Safe/Fail-Secure
or Dry Form “C”
Outputs
Additional Fused
Outputs
ACM8 Board
Input Fuse Rating
8 8
10A/
250V
10A/
250V
10A/
250V
ACM8 Board
Output Fuse Rating
ACMS8 Board
Input Fuse Rating
2.5A/ 250V
2.5A/ 250V
2.5A/ 250V
15A/
32V
ACMS8 Board
Output Fuse Rating
PDS8 Board
Input Fuse Rating
10A/
32V
3A/
32V
PDS8 Board
Output Fuse Rating
PD8UL/PD16W Board
3.5A/ 250V
3.5A/ 250V
3A/
32V
3.5A/ 250V
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws, level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the three upper screws. Install the three lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 8).
2. Connect unswitched AC power (120VAC 60Hz) to terminals marked [L, N] (Fig. 2-5, pg. 3-6). Use 14 AWG or larger for all power connections. Secure green wire lead to earth ground.
Keep power-limited wiring separate from non power-limited wiring. Minimum 0.25” spacing must be provided (Fig. 2-5, pg. 3-6). CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
3. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired location, opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 1, pg. 2). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the door of the enclosure.
4. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow104NB and corresponding Sub-Assembly Installation Guides for ACM8, ACMS8, PDS8, VR6, PD8UL and PD16W for further installation instructions.
Fig. 1
Output Fuse Rating
- 2 - MaxFit Kits Fused
MaxFit7F8AP: NEC Power-Limited Wiring Requirements
1 2 3 4
ON
1 2 3 4
ON
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power-limited applications use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods. For Canadian installations use shielded wiring for all connections. Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 2a).
Fig. 2
Supervisory Connections, Aux. DC Output to Devices and
Fire Alarm Interface (power-limited)
Tamper Switch
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
Input 120VAC, 60Hz (non power-limited)
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
L G N
eFlow104NB
F1 F2 F3 F4 F5 F6 F7 F8
1 2 3 4
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
5 6 7 8
INPUT
TRIGGER
ACM8 Outputs
to Devices
(non power-
limited)
limited)
DC Output
(non power-
– DC +– BAT +
- + - + Power Control
ACM8
10A 250V
MAIN
ON
1 2 3 4
ON
1 2 3 4
NO C NC
FACP INTERFACE
+INP- T + RET-
FACP
TRG
(power-limited)
Optional
Rechargeable
Stand-by Batteries
for UL294
Applications
PD8UL
LED
INPUT
D1
R1
P N
Note:
12V batteries
are required for
ULC-S319
installations.
FUSED POWER OUTPUTS
COMMON POWER OUTPUTS
1 2 3 4 5 6 7 8
N
P
PD8UL Outputs
Connect red battery lead to the terminal marked [+ BAT] and to the [positive (+)] terminal of the battery. Connect black battery lead to terminal marked [BAT –] and to the [negative (–)] terminal of the battery. Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing. 12AH Rechargeable batteries are the largest batteries that can fit in this enclosure. A UL listed external battery enclosure must be used if using the 40AH or 65AH batteries.
Incorrect Wire
Handling
Supervisory
Connections
to Devices
(non power-
limited)
External Jacketed
Shield
Fig. 2a
Correct Wire
Handling
Wire
Insulation
Pull back external jacketed
Solid Copper
Conductors
shield approx. 1/2”.
MaxFit Kits Fused - 3 -
MaxFit7F16AP: NEC Power-Limited Wiring Requirements
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power-limited applications use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods. For Canadian installations use shielded wiring for all connections. Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 3a).
Fig. 3
Supervisory Connections, Aux. DC Output to Devices and
Fire Alarm Interface (power-limited)
Tamper Switch
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
Input 120VAC, 60Hz (non power-limited)
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
L G N
eFlow104NB
F1 F2 F3 F4 F5 F6 F7 F8
1 2 3 4
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
5 6 7 8
INPUT
TRIGGER
ACM8 Outputs
to Devices
(non power-
limited)
Optional
Rechargeable
Stand-by Batteries
for UL294
Applications
Note:
12V batteries
are required for
ULC-S319
installations.
PD16W Outputs
to Devices
(non power-
limited)
Connect red battery lead to the terminal marked [+ BAT] and to the [positive (+)] terminal of the battery. Connect black battery lead to terminal marked [BAT –] and to the [negative (–)] terminal of the battery. Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing. 12AH Rechargeable batteries are the largest batteries that can fit in this enclosure. A UL listed external battery enclosure must be used if using the 40AH or 65AH batteries.
PD16W
limited)
DC Output
(non power-
– DC +– BAT +
FACP
ON
1 2 3 4
ACM8
10A 250V
- + - + Power Control
N
NPS
P
MAIN
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
ON
1 2 3 4
NO C NC
FACP INTERFACE
TRG
+INP- T + RET-
F1 F2 F3 F4 F5 F6 F7 F8
1 2 3 4
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
5 6 7 8
INPUT
TRIGGER
Supervisory
Connections
(power-limited)
ACM8 Outputs
to Devices
(non power-
limited)
FACP
ON
1 2 3 4
ON
1 2 3 4
NO C NC
FACP INTERFACE
TRG
+INP- T + RET-
- + - + Power Control
ACM8
10A 250V
MAIN
Fig. 3a
External
Wire
Insulation
Jacketed
Shield
Correct Wire
Handling
Pull back external jacketed shield approx. 1/2”.
Incorrect Wire
Handling
Solid Copper
Conductors
- 4 - MaxFit Kits Fused
MaxFit7F8APS: NEC Power-Limited Wiring Requirements
1 2 3 4
ON
1 2 3 4
ON
+ INP1 - + INP2 -
PDS8
VR6
24VDC
from
eFlow104NB
12VDC
from VR6
+ IN -
24VDC
from
eFlow104NB
+ OUT -
12VDC
to
PDS8
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power-limited applications use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods. For Canadian installations use shielded wiring for all connections. Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 4a).
Fig. 4
Supervisory Connections, Aux. DC Output to Devices and
Fire Alarm Interface (power-limited)
Tamper Switch
PDS8/VR6
Out8
<
>
1 off 2
PWR1 +
Out7
<
>
1 off 2
Out6
<
>
1 off 2
Out5
<
>
1 off 2
Out4
<
>
1 off 2
Altronix PDS8
Out3
<
>
1 off 2
333333
Out2
<
>
1 off 2
10
IN1 Fuse
3
Out1
<
>
1 off 2
3
OFF
IN1
IN2
IN2 Fuse
10
PWR1 +
--
--
+ INP1
+ INP2
PWR2 +
Common (--- )
PDS8 Outputs
to Devices
(non power-
Power Input and
Output for VR6
(factory connected)
limited)
Common Power Outputs (NEG)
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
1 2 3 4 5 6 7 8
N
P
PWR2 +
Common (--- )
Input 120VAC, 60Hz (non power-limited)
L G N
eFlow104NB
limited)
DC Output
(non power-
– DC +– BAT +
Optional
Rechargeable
Stand-by Batteries
for UL294
Applications
Note:
12V batteries
are required for
ULC-S319
installations.
To PDS8 To VR6
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
- + - + Power Control
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
ACM8
10A 250V
F1 F2 F3 F4 F5 F6 F7 F8
1 2 3 4
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
5 6 7 8
ON
1 2 3 4
ON
1 2 3 4
MAIN
+INP- T + RET-
NO C NC
FACP INTERFACE
ACM8 Outputs
to Devices
(non power-
limited)
Power Inputs
for PDS8
(factory connected)
INPUT
TRIGGER
FACP
TRG
Supervisory
Connections
(power-limited)
Connect red battery lead to the terminal marked [+ BAT] and to the [positive (+)] terminal of the battery. Connect black battery lead to terminal marked [BAT –] and to the [negative (–)] terminal of the battery. Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing. 12AH Rechargeable batteries are the largest batteries that can fit in this enclosure. A UL listed external battery enclosure must be used if using the 40AH or 65AH batteries.
External
Wire
Insulation
Jacketed
Shield
Incorrect Wire
Handling
Solid Copper
MaxFit Kits Fused - 5 -
Conductors
Fig. 4a
Correct Wire
Handling
Pull back external jacketed shield approx. 1/2”.
MaxFit7F16APS: NEC Power-Limited Wiring Requirements
+ PWR1 - + PWR2 -
ACMS8
VR6
24VDC
from
eFlow104NB
12VDC
from VR6
+ IN -
24VDC
from
eFlow104NB
+ OUT -
12VDC
to
PDS8
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power-limited applications use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods. For Canadian installations use shielded wiring for all connections. Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 5a).
Fig. 5
Supervisory Connections, Aux. DC Output to Devices and
Fire Alarm Interface (power-limited)
Tamper Switch
Power Input and
Output for VR6
(factory connected)
Input 120VAC, 60Hz (non power-limited)
Optional
Rechargeable
Stand-by Batteries
for UL294
Applications
Note:
12V batteries
are required for
ULC-S319
installations.
PD16W Outputs
to Devices
(non power-
limited)
L G N
eFlow104NB
PD16W
limited)
DC Output
(non power-
– DC +– BAT +
To VR6 To ACMS8
+ PWR2
+ PWR1
--
COM -
--
PWR1
PWR2
+
+
ACMS8/
VR6
ACMS8
Outputs
to Devices
(non power-
limited)
PWR1
+
PWR2
+
COM -
ACMS8s are
factory
interconnected
+ PWR2
+ PWR1
--
COM -
N
NPS
P
--
PWR1
PWR2
+
+
Supervisory Connections
(power-limited)
Power Inputs
for ACMS8
(factory connected)
ACMS8
Outputs
to Devices
PWR1
+
PWR2
+
COM -
(non power-
limited)
ACMS8
Connect red battery lead to the terminal marked [+ BAT] and to the [positive (+)] terminal of the battery. Connect black battery lead to terminal marked [BAT –] and to the [negative (–)] terminal of the battery. Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing. 12AH Rechargeable batteries are the largest batteries that can fit in this enclosure. A UL listed external battery enclosure must be used if using the 40AH or 65AH batteries.
External
Wire
Insulation
Jacketed
Shield
Incorrect Wire
Handling
Solid Copper
- 6 - MaxFit Kits Fused
Conductors
Fig. 5a
Correct Wire
Handling
Pull back external jacketed shield approx. 1/2”.
eFlow Power Supply/Chargers can be Controlled and Monitored while
Reporting Power/Diagnostics from Anywhere over the Network...
LINQ2 - Network Communication Module
LINQ2 provides remote IP access to real-time data from eFlow power supply/chargers to help keep systems up and running at optimal levels. It facilitates fast and easy installation and set-up, mini­mizes system downtime, and eliminates unnecessary service calls, which helps reduce Total Cost of Ownership (TCO) - as well as creating a new source of Recurring Monthly Revenue (RMR).
LINQ2
Features:
- UL Listed in the U.S. and Canada.
- Local or remote control of up to (2) two Altronix eFlow power output(s) via LAN and/or WAN.
- Monitor real time diagnostics: DC output voltage, output current, AC & battery status/service, input trigger state change, output state change and unit temperature.
- Access control and user managment: Restrict read/write, Restrict users to specific resources
- Two (2) integral network controlled Form “C” Relays.
- Three (3) programmable input triggers: Control relays and power supplies via external hardware sources.
- Email and Windows Dashboard notifications
- Event log tracks history.
- Secure Socket Layer (SSL).
- Programmable via USB or web browser - includes operating software and 6 ft. USB cable.
LINQ2 Mounts Inside any MaxFit Enclosure
Network Connection:
Installation, Programming and Monitoring
Altronix
eFlow Power Supply
MaxFit Kits Fused - 7 -
MaxFit Enclosure Dimensions (approximate):
(
)
20.5” x 16.5” x 6.25” (520.7mm x 419.1mm x 158.8mm)
1.50”
(38.1mm)
8.75” (222.3mm)8.75” (222.3mm)
1.25” (31.8mm)
6.25” (158.8mm)
1.25” (31.8mm)
0.569” (14.5mm)
177.8mm
0.75” (19.1mm)
7.00”
16.50” (419.1mm)
7.00”
177.8mm
1.25” (31.8mm)
1.00” (25.4mm)
1.25” (31.8mm)
1.25” (31.8mm)
1.25” (31.8mm)
1.50”
(38.1mm)
8.75” (222.3mm)8.75” (222.3mm)
1.50”
(38.1mm)
1.25” (31.8mm)
1.25” (31.8mm) 1.25” (31.8mm)
7.00”
177.8mm
520.7mm
20.50”
1.50”
(38.1mm)
1.25” (31.8mm)
1.25” (31.8mm)
7.00”
177.8mm
Altronix is not responsible for any typographical errors.