Altronix MAXFIT7F8AP Specsheet

MaxFit7F8AP
Access Power Controller
Description
Altronix MaxFit7F8AP Access Power Controller distributes and switches power to
access control systems and accessories. It converts a 120VAC, 60Hz input into eight
(8) distributed 24VDC fuse protected outputs and eight (8) independently controlled
24VDC fuse protected relay outputs. Fail-Safe/Fail-Secure power outputs may be
converted to dry form “C” contacts. Relays are activated by an open collector sink or
normally open (NO) dry trigger input from an Access Control System, Keypad, Push
Button, REX PIR, etc. Unit will route power to a variety of access control hardware
Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger
other auxiliary devices. The fire alarm disconnect feature is individually selectable for
any or all of the eight (8) relay outputs.
Key Features
Rev. MaxFit7F8AP - 04162020
MaxFit7F8AP
- 24VDC @ 10A power supply/charger.
- Supervision
- AC Fail
- Low Battery and Battery Presence
- Low power shutdown.
- Convenient knockout configuration:
- Twelve (12) double knockouts (1” and 0.75”).
- 16 AWG powder-coated steel enclosure simplifies board layout and wire management.
- Enclosure accommodates up to four (4) 12VDC/12AH batteries.
- Outputs:
- Eight (8) distributed 24VDC fuse protected outputs
- Eight (8) independently controlled 24VDC fuse protected relay outputs.
Accessories
Network Supervision
Altronix model LINQ2 Network Communication Module provides remote supervision,
control and monitoring over LAN/WAN
- Remotely reports accurate power diagnostics
- Controls power and resets devices
- Reports system diagnostics via Email
Lifetime Warranty / Made in the U.S.A.
phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com
Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA
MaxFit7F8AP
Access Power Controller
Specifications
Power Supply (eFlow104NB):
Input
Voltage 120VAC, 60Hz, 4.5A max. Input Fuse 6.3A/250V.
Outputs
Voltage 24VDC @ 10A. Auxiliary 1A (unswitched). Protection Overvoltage protection.
Filtered and regulated.
Battery Backup
Type Sealed lead acid or gel type. Fuse Rating 10A @ 32VDC. Failover Upon AC loss, instantaneous.
Fire Alarm Disconnect
Supervised Latching or non-latching. EOL 10K Resistor.
Supervision
AC Failure Form “C” contacts. Battery Form “C” contacts. Low DC Power Shutdown
Shuts down DC output terminals if battery voltage drops below 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
Indicators (LED)
AC Input 120VAC is present. DC Output Powered. Battery Discharged or not connected.
Power Distribution Module (PD8UL):
Input
Voltage 24VDC from eFlow104NB.
Outputs
Voltage 24VDC. Eight (8) fuse protected outputs.
3.5A per output max. Output Fuses 3.5A / 32VDC.
Indicators (LED)
Green LED DC Output.
Access Power Controller (ACM8):
Input
Voltage 24VDC from eFlow104NB. Main Fuse 10A / 32V.
Outputs
Voltage 24VDC. Eight (8) independently controlled fused outputs:
a) Fail-Safe and/or Fail-Secure power outputs. Form “C” Relays rated 28VAC or VDC @ 2.5A.
b) Auxiliary power outputs (unswitched). c) Any combination of the above. Output Fuses 3.5A / 32VDC.
Indicators (LED)
Red LEDs Outputs are triggered (relays energized). Green LED FACP disconnect is triggered.
MaxFit7F8AP:
Physical and Environmental
Dimensions (H x W x D)
20.5” x 16.5” x 6.25” (520.7 mm x 419.1 mm x 158.8 mm).
Weight (approx.) Product 26.9 lb. (12.2 kg). Shipping 32.9 lb. (14.9 kg). Temperature Operating 0ºC to 50ºC (32ºF to 122ºF). Storage -20ºC to 70ºC (-4ºF to 158ºF). Relative Humidity 85% +/-5%. BTU/Hr (approx.): 145 BTU/Hr.
Lifetime Warranty / Made in the U.S.A.
phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com
Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA