![](/html/c4/c4a4/c4a452e2771967397c7ac4617a6159b18ba48aa2a20eadb633e14941da6786e4/bg1.png)
™
LINQ8ACM and LINQ8ACMCB
Network Access Power Controllers
Description
Altronix LINQ8ACM and LINQ8ACMCB are dual input network access power controllers which can be
installed in Altronix wall and rack mount enclosures to facilitate access control deployment. Access
Power Controller’s dual input design allows power to be steered from one (1) or two (2) independent low
voltage 12 or 24 VDC Altronix power supplies to eight (8) independently controlled fuse (LINQ8ACM) or
PTC (LINQ8ACMCB) protected outputs. Outputs are activated by an open collector sink, normally open
(NO), normally closed (NC) dry trigger input, or wet output from an Access Control System, Card Reader,
Keypad, Push Button, PIR, etc. LINQ8ACM(CB) will route power to a variety of access control hardware
devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both
Fail-Safe and/or Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring,
or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually
selectable for any or all of the eight (8) outputs. The spade connectors allow you to daisy chain power
to multiple LINQ8ACM(CB) modules. This feature allows you to distribute the power over more outputs
for larger systems. Built-in LINQTM Network Power Management facilitates monitoring, reporting and
control of power/diagnostics.
LINQ8ACM
LINQ8ACM and LINQ8ACMCB have built-in LINQ technology which facilitates monitoring, reporting,
and control of one (1) or two (2) low voltage AC or supervised DC power supply/chargers over the
network. They report diagnostics via Email and Windows Dashboard Alert notifications, greatly
reducing system downtime and eliminating unnecessary service calls. LINQ8ACM and LINQ8ACMCB
retrofit with most currently installed multi-output power supply/chargers.
Board Dimensions (L x W x H) and Drawing
8” x 4.5” x 1.25” (203.2mm x 114.3mm x 31.8mm)
Mounting Holes’ Tolerance: +/- 0.04 in. (1mm).
2.4"
3.7"
(94mm)
(61mm)
4.5"
(114.3mm)
4.9"(124.5mm)
6.7" (170.2mm)
8’ (203.2mm)
Rev. LINQ8ACM - 10222019
![](/html/c4/c4a4/c4a452e2771967397c7ac4617a6159b18ba48aa2a20eadb633e14941da6786e4/bg2.png)
LINQ8ACM and LINQ8ACMCB
Network Access Power Controllers
Specifications
Input
Two (2) Independent Low Voltage Inputs.
Input Voltage Options:
Single Input:
Input1: 12 or 24 VDC from eFlow series power supply.
Dual Input Option 1:
- Input 1: 12 or 24 VDC from eFlow series power supply.
- Input 2:
a) 12 or 24 VDC from eFlow series power supply.
b) 5 or 12 VDC from VR6 voltage regulator.
Dual Input Option 2:
12 and 24 VDC from Tango1B PoE Driven Power Supply.
Voltage Range
LINQ8ACM: 5VDC to 24VDC, up to 10A each or
20A total input.
LINQ8ACMCB: 5VDC to 24VDC up to 10A each or
16A total input.
Current 0.6A @ 12V, 0.3A @ 24V
Consumption: with all relays energized.
Main Fuse Rating 15/32A.
Outputs
LINQ8ACM: Fuse protected outputs rated @ 2.5A per output,
non power-limited. Total output 20A max.
LINQ8ACMCB: PTC protected outputs rated @ 2A per output,
Class 2 power-limited. Total output 16A max.
Do not exceed the individual power supply ratings.
Any of the eight (8) fuse/PTC protected power outputs are selectable
to follow power Input 1 or Input 2.
Individual outputs may be set to OFF position for servicing.
Output Ratings:
LINQ8ACM: Fuses are rated 3A/32V each.
LINQ8ACMCB: PTCs are rated 2A each.
Total output current is determined by the power supply(ies),
not to exceed a maximum of 10A for each input.
Programming Features:
Eight (8) Programmable Outputs:
- Fail-safe, fail-secure or auxiliary outputs.
- Input controlled or manually controlled through software.
- High (over) and low (under) voltage and current monitoring by output.
- Multiple outputs may be programmed to be triggered by a single input.
- Battery back-up by output.
Programming Features (cont’d):
Eight (8) Programmable Trigger Inputs:
- Normally open (NO).
- Normally colsed (NC).
- Open collector sink inputs.
- Wet Input (5VDC - 24VDC) with 10k resistor.
- Any combination of the above.
Other Programmable Trigger Inputs:
- Monitor power supply(ies) input for voltage and currect limits (high/low).
- Input and output current calibration.
- Programmable timer events.
- Programmable user levels.
- Enable or disable alerts by type.
- Programmable alert reporting delay.
Fire Alarm Disconnect
Supervised Inactive, latching or non-latching, individually
selectable for any or all of the eight (8) outputs.
EOL 10K Resistor.
LED Indicators
Green AC LED: indicates AC trouble condition.
Green BAT LED: indicates battery trouble condition.
Green FACP LED: indicates FACP disconnect is triggered.
Flashing Blue Heartbeat LED: indicates network connection.
Individual OUT1 - OUT8 Red LEDs: indicate outputs are triggered.
Individual Voltage LEDs: indicate 12VDC (Green) or 24VDC (Red).
Physical and Environmental
Dimensions (W x L x H)
8” x 4.5” x 1.25” (203.2mm x 114.3mm x 31.8mm).
Product Weight 0.7 lb. (0.32 kg).
Shipping Weight 0.95 lb. (0.43 kg).
Temperature
Operating 0ºC to 49ºC (32ºF to 120ºF).
Storage -20ºC to 70ºC (-4ºF to 158ºF).
Relative Humidity 93% +/-5%.
BTU/Hr. (approx.): 4 BTU/Hr.
Mounting hardware included.
Accessories
VR6
Voltage Regulator
Converts a 24VDC input into a regulated 5VDC
or 12VDC selectable output at up to 6A.
Altronix VR6 & LINQ8ACM(CB) easily snap
together to provide 5VDC or 12VDC and 24VDC
simultaneously – individually selectable for each of
the 8 outputs... all on one footprint!
phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com
Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA
Tango1B
PoE Driven Power Supply
Converts an IEEE802.3bt 4PPoE input into a
regulated 24VDC and/or 12VDC output up to 65W.
Eliminates the need for high voltage power supply
inside of an enclosure. 8-pin connector allows for
stacking with compatible Altronix sub-assemblies
such as LINQ8ACM(CB), saving enclosure space.