Altronix eFlow6NNX Installation Instructions

Page 1
Power Supply/Chargers
Installation Guide
Models Include:
eFlow6N/eFlow6NX
- 6 amp @ 12VDC or 24VDC
eFlow6N8/eFlow6NX8 eFlow6N8D/eFlow6NX8D
- 6 amp @ 12VDC or 24VDC - 6 amp @ 12VDC or 24VDC
- Eight (8) Fused Outputs - Eight (8) PTC Outputs
- 6 amp @ 12VDC or 24VDC - 6 amp @ 12VDC or 24VDC
- Sixteen (16) Fused Outputs - Sixteen (16) PTC Outputs
Altronix Corp.
140 58th St. Brooklyn, NY
Rev. 6NRP052213 More than just power.™
Installing Company: _____________________ Service Rep. Name: __________________________________________
Address: ________________________________________________________ Phone #: _________________________
Page 2
Overview:
The eFlow6N power supply/chargers convert a 120VAC / 60Hz input, to a 12VDC or 24VDC nominal output (see Power Supply Configuration Reference Chart and Specifications).
eFlow6N Series Power Supply Configuration Reference Chart:
Nominal DC Outputs
[DC] [AUX]
Altronix
Model Number
eFlow6N
eFlow6NX
eFlow6N8
eFlow6NX8 2.5A
eFlow6N8D
eFlow6NX8D 2A
eFlow6N16
eFlow6NX16 2 - PD8UL 2.5A
eFlow6N16D
eFlow6NX16D
12VDC Output
Range (volts)
24VDC Output
Range (volts)
10.0-13.2 20.19-26.4 10.03-13.2 20.19-26.4 6 3.5A 5A/250V 7.5A/32V 910 N/A 1
10.0-13.2 20.19-26.4 10.03-13.2 20.19-26.4 6 3.5A 5A/250V 7.5A/32V 910 PD8UL 8
9.78-13.2 20.0-26.4 10.03-13.2 20.19-26.4 6 3.5A 5A/250V 7.5A/32V 910 PD8ULCB 8
10.0-13.2 20.19-26.4 10.03-13.2 20.19-26.4 6 3.5A 5A/250V 7.5A/32V 910
9.78-13.2 20.0-26.4 10.03-13.2 20.19-26.4 6 3.5A 5A/250V 7.5A/32V 910
12VDC Output
Range (volts)
24VDC Output
Range (volts)
Maximum Supply
Current for Main and Aux.
Outputs (amp)
Input Rating:
120VAC, 60Hz
Input Fuse Rating
Battery Fuse Rating
Ripple Voltage (mV)
Under low battery condition
Power Distribution
PD16WCB
2 - PD8ULCB
Modiule
PD16W
Number of Outputs
Fused Output Ratings
PTC Output Ratings
2.5A
2A
2.5A
16
2A
16
2A
Accommodates up to
7AH Batteries
Accommodates up to
12AH Batteries
3
3
3
3
3
3
3
3
3
3
These units provide non power-limited outputs: eFlow6N, eFlow6NX, eFlow6N8, eFlow6NX8, eFlow6N16 and eFlow6NX16. These units provide power-limited outputs: eFlow6N8D, eFlow6NX8D, eFlow6N16D and eFlow6NX16D. If a power-limited output is required in the end-product application, the DC output from the power supply must be connected to a separately Listed control unit or accessory board that provides power-limited outputs. The product(s) providing the power-limited output(s) must be listed as appropriate for the particular end-product application (fire alarm, burglar alarm, access control), and wired in accordance with the products installation instructions. Class 1 wiring methods, separation of circuits, and proper fire-rated enclo­sures all must be considered when connecting the DC output of the power supply to the end-product devices. The auxiliary output of these units are power-limited.
UL Listings for US Installations:
UL 294 - UL Listed for Access Control System Units. UL 603 - UL Listed for Power Supplies for Use with Burglar-Alarms Systems. UL 1481 - UL Listed for Power Supplies for Fire Protective Signaling Systems.
UL Listings for Canadian Installations:
ULC-S318-96 - Power Supplies for Burglar Alarm Systems. Also suitable for Access Control.
Altronix Corp.
140 58th St. Brooklyn, NY
California State Fire Marshal (eFlow6N and eFlow6NX only)
European Conformity
Stand-by Specifications:
Fire Applications
24 hr. Stand-by/
5 min. Alarm
Battery
Burg. Applications
4 hr. Stand-by/
15 min. Alarm
7AH 0.4 amp/6 amp N/A 10 Mins./6 amp 12AH 1 amp/6 amp 0.3 amp/6 amp 25 Mins./6 amp 40AH (for eFlow6NX refer to Fig. 8, pg. 10) 6 amp/6 amp 1.2 amp/6 amp Over 4 Hours/6 amp 65AH (for eFlow6NX refer to Fig. 8, pg. 10) 6 amp/6 amp 1.5 amp/6 amp Over 4 Hours/6 amp
Access Control
Applications
Stand-by
- 2 - eFlow6N Series
Page 3
Specifications:
Input:
• 120VAC,60Hz.
Output:
• Foroutputvoltageandsupplycurrent,
refer to eFlow6N series Power Supply Configuration Reference Chart, pg. 2.
• AuxiliaryPower-Limitedoutput
rated @ 1 amp (unswitched).
• OverVoltageProtection.
Battery Backup:
• Built-inchargerforsealedleadacidorgeltypebatteries.
• Maximumchargecurrent1.54amp.
• Automaticswitchovertostand-bybatterywhenACfails.
Transfer to stand-by battery power is instantaneous with no interruption.
Fire Alarm Disconnect:
• SupervisedFireAlarmdisconnect(latchingor
non-latching) 10K EOL resistor. Operates on a normally open (NO) or normally closed (NC) trigger.
Supervision:
• ACfailsupervision(form“C”contacts).
Supervision (cont’d):
• Batteryfail&presencesupervision(form“C”contacts).
• Lowpowershutdown.ShutsdownDCoutputterminals
if battery voltage drops below 71-73% for 12V units and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
Fuse Ratings:
• RefertoeFlow6NSeriesPowerSupplyConfiguration
Reference Chart, pg. 2.
Visual Indicators:
• GreenACPowerLEDindicates120VACpresent.
• ACinputandDCoutputLEDindicators.
Additional Features:
• Shortcircuitandoverloadprotection.
• Unitiscompletewithpowersupply,enclosure,
battery leads and cam lock.
Enclosure Dimensions (approximate H x W x D):
eFlow6N, eFlow6N8, eFlow6N8D, eFlow6N16, eFlow6N16D:
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)
eFlow6NX, eFlow6NX8, eFlow6NX8D, eFlow6NX16, eFlow6NX16D:
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, The Canadian Elec­trical Code, Part 1 and with all local codes and authorities having jurisdiction. The product must be located indoors within the protected premises.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 11-12). Secure enclosure to earth ground.
2. Set desired DC output voltage by setting SW1 to the appropriate position on the power supply board (Fig. 1i, pg. 5).
3. Connect unswitched AC power (120VAC 60Hz) to terminals marked [L, N] (Fig. 1a, pg. 5). Use 14 AWG or larger for all power connections. Secure green wire lead to earth ground. Keep power-limited wiring separate from non power-limited wiring (120VAC 60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided. For Fire Alarm applications the outputs are “Special Applications” only, see list (refer to Appendix A, pg. 12).
4. Measure output voltage before connecting devices. This helps avoid potential damage.
5. Connect devices to be powered: a. For eFlow6N/eFlow6NX connect devices to terminals marked [- DC +] (Fig. 1h, pg. 3). b. For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 8 marked [1P & 1N thru 8P & 8N] (Fig. 3a & 3b, pg. 6) or 1 to 16 marked [1P & 1N thru 16P & 16N] (Fig. 4a & 4b, pg. 6) carefully observing correct polarity. For auxiliary device connection this output will not be affected by Low Power Disconnect or Fire Alarm Interface. Connect device to terminals marked [+ AUX -- ] (Fig. 1f, pg. 5).
6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. Connect battery to terminals marked [-- BAT + ] (Fig. 1g, pg. 5). Use two (2) 12VDC batteries connected in series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH), CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2 batteries of an appropriate rating.
7. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1b, pg. 5) supervisory relay outputs.
8. To delay AC reporting for 2 hrs. set dip switch [AC Delay] to OFF position (Fig. 1c, pg. 5). To delay AC reporting for 1 min. set dip switch [AC Delay] to ON position (Fig. 1c, pg. 5).
Note: Must be set to ON position for Burglar Alarm Applications.
eFlow6N Series - 3 -
Page 4
9. To enable Low Output Power Shutdown set dip switch [Shutdown] to ON position (Fig. 1c, pg. 5). To disable Low Output Power Shutdown set dip switch Shutdown] to OFF position (Fig. 1c, pg. 5).
10. Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger terminals will cause [DC] output to shutdown (Fig. 1d, pg. 5).
11. Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching [Trigger EOL Shutdown] (Fig. 1e, pg. 5).
12. For Access Control Applications: mount UL Listed tamper switch (Sentrol model 3012 or equivalent) at the top of the enclosure. Slide tamper switch bracket onto the edge or the enclosure approx. 2” from the right side (Fig. 5, pg. 7 or Fig. 7, pg. 9). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device.
Wiring:
Use 18 AWG or larger for all low voltage power connections. Note: Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level eFlow6N: 12VDC or 24VDC nominal rated @ 6 amp max. Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage (12VDC @ 13.2 or 24VDC @ 26.4) both at the battery terminal and at the board terminals marked [-- BAT + ] to ensure that there is no break in the battery connection wires.
Note: Maximum charging current under discharges is 1.54 amp. Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.
LED Diagnostics:
Power Supply/Charger
Red (DC) Green (AC/AC1) Power Supply Status
ON ON Normal operating condition. ON OFF Loss of AC, Stand-by battery supplying power. OFF ON No DC output. OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Power Distribution Module
Green (AC) Power Distribution Module Status
ON Normal operating condition. OFF No Power Output.
Terminal Identification:
Power Supply/Charger
Terminal Legend
L, N Connect 120VAC 60Hz to these terminals: L to hot, N to neutral (non power-limited) (Fig. 1a, pg.5). – DC + 12VDC or 24VDC nominal @ 6 amp continuous output (non power-limited output) (Fig. 1h, pg. 5). Trigger EOL
Supervised NO, GND
RESET + AUX – Auxiliary Power-Limited output rated @ 1 amp (unswitched) (power-limited output) (Fig. 1f, pg. 5). AC Fail
NC, C, NO
Bat Fail NC, C, NO
– BAT + Stand-by battery connections. Maximum charge current 1.54 amp (non power-limited) (Fig. 1g, pg. 5).
- 4 - eFlow6N Series
Function/Description
Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open, normally closed from an FACP output circuit (power-limited input) (Fig. 1d, pg. 5).
FACP interface latching or non-latching (power-limited) (Fig. 1e, pg. 5).
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1 amp @ 30VDC (power-limited) (Fig. 1b, pg. 5).
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1 amp @ 30VDC. A removed battery is reported within 5 minutes. Battery reconnection is reported within 1 minute (power-limited) (Fig. 1b, pg. 5).
Page 5
Power Distribution Module
g
Terminal Identification:
Terminal Legend PD8UL/PD8ULCB
Terminal Legend PD16W/PD16WCB
Function/Description
1P to 8P 1P to 16P Positive DC power outputs. 1N to 8N 1N to 16N Negative DC power outputs.
Fig. 1 - eFlow6N Board configuration
CLOSED --- 12V
OPEN --- 24V
1i
1h
--- DC +
1
--- BAT +
AC
AC DELAY SHUTDOWN
O N
DC
1 min. 2 hr.
1c
enable disable
TRIGGER EOL
SUPERVISED
NO GND
RESET
1e 1f1d
+ AUX –
5A 250V
AC1
LG N
NC C NO NC C NO
1a 1b
BAT FAILAC FAIL
Trouble/Time Limited Warning of Stand-by Batteries:
For compliance with ULC S318-96, the Time Limited Warning circuit must be connected for local or remote annunciation with an Amber or Red LED to indicate DC Trouble (low battery, loss of battery or when 95% of the stand-by battery has been depleted). Connect the circuit to the Batt Fail relay contacts to an appropriate input of a UL Listed Burglar Alarm or Access Control Panel. The following figure shows the circuitry needed for local annunciation.
Fig. 2 - Battery trouble indication - For Canadian use, a red indicating lamp must be visible from the exterior of this enclosure. Wire one leg of a UL Listed, power-limited power source to the indicating lamp. Wire the second leg of the power source to the indicating lamp in series with the battery fail relay contact terminals marked
BAT FAILAC FAIL
[BAT FAIL - C, NO] (Fig. 2, pg. 5).
POWER
SOURCE
NC C NO NC C NO
RED INDICATING
LAMP
eFlow6N Series - 5 -
Page 6
Power Distribution Module(s):
Replace fuses with the same type and rating 3.5A, 250V.
(
)
(
)
Installed)
DC Output to devices
Fig. 3a - PD8UL Power Distribution Board Fig. 3b - PD8ULCB - Power Distribution Board Non Power-Limited Outputs Power-Limited Outputs
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
P
D1
FUSED POWER OUTPUTS
N
COMMON POWER OUTPUTS
DC Output to devices
1P-8P Power Outputs,
1N-8N Common Outputs
From Power Supply
(Factory Installed)
R1
Board
LED
INPUT
Fig. 4a - PD16W Power Distribution Board Fig. 4b - PD16WCB - Power Distribution Board Non Power-Limited Outputs Power-Limited Outputs
DC Output to devices
1P-16P Power Outputs,
()
1N-16N Common Outputs
P
FUSED POWER OUTPUTS
N
COMMON POWER OUTPUTS
DC Output to devices
1P-8P Power Outputs,
1N-8N Common Outputs
1P-16P Power Outputs,
1N-16N Common Outputs
D1
LED
R1
INPUT
From Power Supply
(Factory Installed)
Board
)(
3.5A 250V
common
outputs
protected
outputs
For continuous protection against risk of fire
12345678
9 10 11 12 13 14 15 16
replace fuses with same type and rating.
N
P
N
From
N P S
Power
Supply
Board
P
(Factory
Input
12345678
common
outputs
protected
outputs
9 10 11 12 13 14 15 16
N
P
NP
From
NPS
Power
Supply
Board
(Factory
Installed)
Input
- 6 - eFlow6N Series
Page 7
Edge of
Enclosure
to Access Control
Panel or
U.L. Listed
Reporting
Device
Enclosure
Sentrol
model # 3012
Tamper Switch
or equivalent
(Not Included)
Fig. 5 - eFlow6N configuration
5A 250V
Door
Wire Strap (from Enclosure to Door)
Green
Lead
(ground)
Power­limited
G
NC
NO
NC
NO
L
C
C
2 hr.
TRIGGER EOL
RESET
N
1 min.
disable
SUPERVISED
GND NO
– AUX +
enable
120VAC
power mains
Non Power-
limited
AC1
AC FAIL
(Power-limited)
BAT FAIL
AC
DC
AC DELAY
O
N
SHUTDOWN
Power-limited)
Battery & AC
Supervision
Circuit
Battery
Connections
(Non
--- BAT +
Switch Detail
OPEN 24V
CLOSED 12V
OPEN --- 24V CLOSED --- 12V
--- DC +
PD8UL/PD8ULCB PD16W/
DC Output to devices*
(refer to Fig. 3a, 3b, 4a or 4b for board configuration pg. 6)
PD16WCB
Optional Rechargeable Stand-by
Battery for UL294 Applications.
Note: 12V batteries required for UL603,
UL1481 and Canadian installations.
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
Optional Rechargeable Stand-by
Battery for UL294 Applications.
Note: 12V batteries required for UL603,
UL1481 and Canadian installations.
7AH Rechargeable batteries are the largest batteries that can fit in this enclosure. A UL Listed external battery enclosure must be used if using 12AH, 40AH or 65AH batteries.
*Outputs are non power-limited: eFlow6N, eFlow6N8, eFlow6N16. Outputs are power-limited: eFlow6N8D, eFlow6N16D.
eFlow6N Series - 7 -
Page 8
NEC Power-Limited Wiring Requirements for eFlow6N Models:
Incorrect Wire
Correct Wire
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power- limited applications, use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods. For Canadian installations use shielded wiring for all connections. Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire, (Fig, 7a).
Fig. 7
120VAC Input
60Hz
(non power-
limited)
Optional UL Listed
Battery Enclosure
(non power-limited)
Supervisory,
Fire Alarm
Interface &
Aux. output
Connections
(power-limited)
Fig. 7a
Handling
External Jacketed
Shield
Handling
Power
Distribution
DC Outputs*
Battery
Connections
(non power-limited)
Wire
Insulation
Solid Copper
Conductors
Pull back external jacketed shield approx. 1/2”.
*Outputs are non power-limited: eFlow6N, eFlow6N8, eFlow6N16. Outputs are power-limited: eFlow6N8D, eFlow6N16D.
- 8 - eFlow6N Series
Page 9
Edge of
Enclosure
to Access Control
Panel or
U.L. Listed
Reporting
Device
Enclosure
Sentrol
model # 3012
Tamper Switch
or equivalent
(Not Included)
Fig. 8 - eFlow6NX configuration
Door
Wire Strap (from Enclosure to Door)
power-limited
Battery & AC Supervision
– AUX +
--- BAT +
Battery connections
RESET
GND NO
SUPERVISED
2 hr.
disable
1 min.
enable
SHUTDOWN
AC DELAY
O N
TRIGGER EOL
(non power-limited)
--- DC +
OPEN --- 24V CLOSED --- 12V
PD8UL/PD8ULCB
Circuit (power-limited)
NO
DC
AC
C
BAT FAIL
C
AC FAIL
NC
NC
NO
Switch Detail
OPEN 24V
CLOSED 12V
120VAC power mains
(non power-limited)
Class 1
Green
Lead
(ground)
G
L
N
AC1
PD8UL/PD8ULCB
5A 250V
DC Output to devices*
(refer to Fig. 3a, 3b
for board configuration pg. 6)
DC Output to devices*
(refer to Fig. 3a, 3b
for board configuration pg. 6)
*Outputs are non power-limited: eFlow6NX, eFlow6NX8, eFlow6NX8D, eFlow6NX16. Outputs are power-limited: eFlow6NX8D, eFlow6NX16D.
Optional Rechargeable Stand-by
Battery for UL294 Applications.
Note: 12V batteries required for UL603,
UL1481 and Canadian installations.
Optional Rechargeable Stand-by
Battery for UL294 Applications.
Note: 12V batteries required for UL603,
UL1481 and Canadian installations.
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
12AH Rechargeable batteries are the largest batteries that can fit in this enclosure. A UL Listed external battery enclosure must be used if using the 40AH or 65AH batteries.
eFlow6N Series - 9 -
Page 10
NEC Power-Limited Wiring Requirements for eFlow6NX Models:
Incorrect Wire
Correct Wire
x. 1/2”.
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power- limited applications, use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods. For Canadian installations use shielded wiring for all connections.
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire, (Fig, 9a).
Fig. 9
Supervisory, Fire Alarm Interface
& Aux. output Connections
(power-limited)
Fig. 9a
Optional UL Listed
Battery Enclosure
(non power-limited)
DC Output*
Handling
External Jacketed
Shield
120VAC Input
60Hz
(non power-
limited)
Power
Distribution
Battery Connections (non power-
limited)
Handling
Wire
Insulation
Solid Copper
Conductors
Pull back external jacketed shield appro
*Outputs are non power-limited:
eFlow6NX, eFlow6NX8, eFlow6NX16.
Outputs are power-limited:
eFlow6NX8D, eFlow6NX16D.
- 10 - eFlow6N Series
Page 11
Enclosure Dimensions (BC300) (approximate H x W x D):
(
)
(
)
(
)
eFlow6N, eFlow6N8, eFlow6N8D, eFlow6N16, eFlow6N16D
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)
1.40”
(36mm)
1.20”
(31mm)
(36mm)
0.75”
(19mm)
1.40”
4.85”
(123mm)
12.5”
(318mm)
11.0”
(279mm)
4.85”
(123mm)
1.40”
(36mm)
(19mm)
0.75”
1.20”
(31mm)
0.9375” (24mm)
3.25”
(83mm)
1.20”
(31mm)
1.40”
(36mm)
5.10”
(130mm)
5.10”
(130mm)
3.25”
(83mm)
13.0”
(330mm)
1.0”
(25mm)
0.9375” (24mm)
1.0”
(25mm)
3.25”
(83mm)
3.25”
(83mm)
5.10”
(130mm)
6.5625”
(167mm)
1.0”
25mm
10.5”
267mm
1.0”
25mm
eFlow6N Series - 11 -
Page 12
Enclosure Dimensions (BC400) (approximate H x W x D):
eFlow6NX, eFlow6NX8, eFlow6NX8D, eFlow6NX16, eFlow6NX16D
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
1.5”
(38.1mm)
1.25”
(31.75mm)
4.5”
(114.3mm)
0.91”
(23.114mm)
1.5”
(38.1mm)
1.1”
(27.94mm)
4.615”
(117.22mm)
12.23”
(310.64mm)
4.615”
(117.22mm)
1.5”
(38.1mm)
1.1”
(27.94mm)
1.75”
(44.45mm)
0.91”
(23.114mm)
1.375”
(34.925mm)
1.125”
(28.575mm)
4.5”
(114.3mm)
1.25”
(31.75mm)
1.5”
(38.1mm)
2.0”
(50.8mm)
2.0”
(50.8mm)
5.0”
(127.0mm)
1.25”
(31.75mm)
1.5”
(38.1mm)
4.615”
(117.22mm)
4.615”
(117.22mm)
1.1”
(27.94mm)
1.5”
(38.1mm)
(393.7mm)
0.79”
(20.06mm)
1.75”
(44.45mm)
15.5”
1.25”
(31.75mm)
5.0”
(127.0mm)
- 12 - eFlow6N Series
Page 13
Appendix A - UL Listed Compatible Devices
A.1 Four (4) Wire Smoke Detectors
Table A-1 below lists four (4) wire smoke detectors compatible with eFlow6N output.
System Sensor Smoke Detector/Base
Detector Type
Max Stand-by Current (mA)
Alarm
Current (mA)
B112LP Base 0.12 36 B114LP Base * * B404B Base * * DH100ACDC Photoelectric 0.15 0.70 DH100ACDCLP Photoelectric 0.15 0.70 DH100ACDCLPW Photoelectric 0.15 0.70 DH400ACDCI Ionization Duct 25 95 DH400ACDCP Photoelectric Duct 25 95 1112/24/D Ionization 0.05 50 1424 Ionization 0.10 41 1451 (w/B402B Base) Ionization 0.10 39 2112/24ATR Photoelectric 0.50 60/70 2112/24AITR Photoelectric 0.50 60/70 2112/24/D Photoelectric 0.05 50
o
2112/24T/D Photoelectric w/135
o
2112/24TSRB Photoelectric w/135
Thermal Supervisory Relay 15 45
Thermal 0.05 50
2312/24TB Photoelectric 0.12 50 2412 (12 volt) Photoelectric 0.12 77 2424 Photoelectric 0.10 41 2451 Photoelectric 0.10 39 2451TH (with/B402B Base) Photoelectric 0.10 39 2W-MOD Loop Test/Maintenance Mod. 30 50 4W-B (12/24 volt) Photoelectric I
3
4WT-B (12/24 volt) Photoelectric I
3
4WTA-B (12/24 volt) I 4WTR-B (12/24 volt) I
3
4WITAR-B (12/24 volt) I
Photo w/Isolated Therm/Sounder/Relay .05 50 2W-MOD2 I RRS-MOD I
Photo w/Therm/Sounder .05 35
3
Photo w/Therm/Relay .05 35
3
Loop Test/Maintenance Mod. .05 *
3
Reversing Relay/Sync Module .05 *
w/Therm .05 23
3
.05 23
6424 Projected Beam 10 28.4 Beam 1224(S) Projected Beam 17 38.5
* Contact manufacturer for current draws.
A.2 Relays
Table A-2 below lists relays compatible with eFlow6N output.
Manufacturer Model Current (mA) Manufacturer Model Current (mA)
PR-1**
PR-2*
System Sensor
PR-3*
EOLR-1
R-10T** R-14T**
* Compatible only with eFlow6N, eFlow6NX, eFlow6N8, eFlow6NX8, eFlow6N16, eFlow6NX16. ** Compatible only when unit is set for 24VDC.
eFlow6N Series - 13 -
15 30 30 30 23 23
System Sensor
R-20T** R-24T** R-10E** R-14E** R-20E** R-24E**
40 40 23 23 40 40
Page 14
Notes:
- 14 - eFlow6N Series
Page 15
Notes:
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 website: www.altronix.com, e-mail: info@altronix.com, Made in U.S.A. IIeFlow6N Series J17M
eFlow6N Series - 15 -
Page 16
Power Supply/Chargers Operating Guide
Models Include:
Model
Input
120VAC, 60Hz
eFlow6N, eFlow6N8, eFlow6N8D, eFlow6N16, eFlow6N16D
3.5 amp 6 amp 6 amp 1 amp 910mV
eFlow6NX, eFlow6NX8, eFlow6NX8D, eFlow6NX16, eFlow6NX16D
Overview:
The eFlow6N series power supply/chargers convert a 120VAC, 60Hz input, to a 12VDC or 24VDC output.
Stand-by Specifications:
Output
12VDC 24VDC
Auxiliary Power-Limited
Output (unswitched)
Ripple
Voltage
Battery
CUT ALONG DOTTED LINE
7AH 0.4 amp/6 amp N/A 10 Mins./6 amp
12AH 1 amp/6 amp 0.3 amp/6 amp 25 Mins./6 amp
40AH 6 amp/6 amp 1.2 amp/6 amp Over 4 Hours/6 amp
65AH 6 amp/6 amp 1.5 amp/6 amp Over 4 Hours/6 amp
Burg. Applications
4 hr. Stand-by/15 min. Alarm
Fire Applications
24 hr. Stand-by/5 min. Alarm
Access Control
Applications Stand-by
Battery Backup:
• Built-inchargerforsealedleadacidorgeltypebatteries.
• Maximumchargecurrent1.54amp.
• Automaticswitchovertostand-bybatterywhenACfails.Transfertostand-bybatterypowerisinstantaneous
with no interruption.
LED Diagnostics:
Red (DC) Green (AC/AC1) Power Supply Status
ON ON Normal operating condition. ON OFF Loss of AC, Stand-by battery supplying power. OFF ON No DC output. OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Installing Company: _________________________________ Service Rep. Name: ___________________________________________________
Address: _______________________________________________________________________ Phone #: _______________________________
Refer to the eFlow Power Supply/Chargers Installation Guide: IIeFlow6N Series, Rev. 6NRP052213 for complete instructions. This sheet is to be removed, framed and posted next to the unit.
Rev. 6NRP052213