Altronix eFlow104N16V, eFlow104NXV, eFlow104NX16V, eFlow4NV, eFlow4NXV Installation Manual

...
Page 1
Rev. 104NVRP052213
More than just power.
TM
Power Supply/Chargers
Installation Guide
Models Include:
Installing Company: ________________ Service Rep. Name: ______________________________________
eFlow104NV/eFlow104NXV
- 10A @ 24VDC
eFlow104N8V/ eFlow104NX8V
- 10A @ 24VDC
- Eight (8) Fused Outputs
eFlow104N16V/ eFlow104NX16V
- 10A @ 24VDC
- Sixteen (16) Fused Outputs
eFlow104N8DV/ eFlow104NX8DV
- 10A @ 24VDC
- Eight (8) PTC Protected Outputs
eFlow104N16DV/ eFlow104NX16DV
- 10A @ 24VDC
- Sixteen (16) PTC Protected Outputs
Page 2
- 2 - eFlow104NV Series
Overview:
Altronix eFlow104NV power supply/chargers convert a 220VAC (working range 198VAC - 256VAC), 50/60Hz input to a 24VDC nominal output (see Power Supply Configuration Reference Chart and Specifications).
eFlow104NV Series Power Supply Configuration Reference Chart:
Altronix Model Number
Nominal DC
Outputs
Maximum Supply Current for
Main and Aux. Outputs (A)
Input Rating:
220VAC, 50/60Hz
Input Fuse Rating
Battery Fuse Rating
Ripple Voltage (mV)
Under low battery condition
Power Distribution
Modiule
Number of Outputs
Fused Output Ratings
Auto-Resettable
PTC Output Ratings
Accommodates up
to 7AH Batteries
Accommodates up
to 12AH Batteries
[DC] [AUX]
24VDC Output
Range (V)
24VDC Output
Range (V)
eFlow104NV
20.17-
26.4
20.28-
26.4
10A 2.7A
6.3A/ 250V
15A/
32V
700 N/A 1
P
eFlow104NXV
P
eFlow104N8V
20.17-
26.4
20.28-
26.4
10A 2.7A
6.3A/ 250V
15A/
32V
700 PD8 8
2.5A
P
eFlow104NX8V
2.5A
P
eFlow104N8DV
20.0-
26.4
20.28-
26.4
10A 2.7A
6.3A/ 250V
15A/
32V
700 PD8CB 8
2A
P
eFlow104NX8DV
2A
P
eFlow104N16V
20.17-
26.4
20.28-
26.4
10A 2.7A
6.3A/ 250V
15A/
32V
700
PD16W
16
2.5A
P
eFlow104NX16V
2 - PD8 2.5A
P
eFlow104N16DV
20.0-
26.4
20.28-
26.4
10A 2.7A
6.3A/ 250V
15A/
32V
700
PD16WCB
16
2A
P
eFlow104NX16DV
2 - PD8CB 2A
P
European Conformity
Stand-by Specifications:
Battery
Burg. Applications
4 hr. Stand-by/
15 min. Alarm
Fire Applications
24 hr. Stand-by/
5 min. Alarm
Access Control
Applications
Stand-by
7AH 0.4A/10A N/A 5 Mins./10A
12AH 1A/10A 0.3A/10A 15 Mins./10A
40AH
(for eFlow104NXV refer to Fig. 8, pg. 10) 6A/10A 1.2A/10A Over 2 Hours/10A
65AH (for eFlow104NXV refer to Fig. 8, pg. 10) 6A/10A 1.5A/10A Over 4 Hours/10A
Page 3
eFlow104NV Series - 3 -
Specifications:
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, The Canadian Electrical Code, Part 1 and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 11-12). Secure enclosure to earth ground.
2. Connect unswitched AC power (220VAC, 50/60Hz) to terminals marked [L, N] (Fig. 1a, pg. 5). Use 14 AWG or larger for all power connections. Secure green wire lead to earth ground lug.
Keep power-limited wiring separate from non power-limited wiring (220VAC 50/60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided. CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
For Fire Alarm applications the outputs are “Special Applications” only, see list (refer to Appendix A, pg. 12).
3. Measure output voltage before connecting devices. This helps avoiding potential damage.
4. Connect devices to be powered: a. For eFlow104NV/eFlow104NXV connect devices to terminals marked [– DC +] (Fig. 1h, pg. 5). b. For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 3a & 3b, pg. 6) or 1 to 16 marked [1P & 1N] through [16P & 16N] (Fig. 4a & 4b, pg. 6) carefully observing correct polarity. For auxiliary device connection: this output will not be affected by Low Power Disconnect or Fire Alarm Interface. Connect device to terminals marked [+ AUX –] (Fig. 1f, pg. 5).
5. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. Connect battery to terminals marked [– BAT + ] (Fig. 1g, pg. 5). Use two (2) 12VDC batteries connected in series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH), CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or BAZR2 batteries of an appropriate rating.
Input:
• 220VAC (working range 198VAC - 256VAC), 50/60Hz.
Output:
• For output voltage and supply current refer to eFlow104NV Series Power Supply Configuration Reference Chart, pg. 2.
• Auxiliary output rated @ 1A (unswitched).
• Overvoltage protection.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 1.54A.
• Automatic switch over to stand-by battery when AC fails. Transfer to stand-by battery power is instantaneous with no interruption.
Fire Alarm Disconnect:
• Supervised Fire Alarm disconnect (latching or non­ latching) 10K EOL resistor. Operates on a normally open (NO) or normally closed (NC) trigger.
Supervision:
• AC fail supervision (form “C” contacts).
• Battery fail and presence supervision (form “C” contacts).
Supervision (cont’d):
• Low power shutdown. Shuts down DC output terminals if battery voltage drops below 70-75% (depending on the power supply). Prevents deep battery discharge.
Fuse Ratings:
• Refer to eFlow104NV Series Power Supply Configuration Reference Chart, pg. 2.
Visual Indicators:
• Green AC Power LED indicates 220VAC present.
• AC input and DC output LED indicators.
Additional Features:
• Short circuit and overload protection.
• Unit is complete with power supply, enclosure, battery leads, and cam lock.
Enclosure Dimensions (approximate H x W x D):
eFlow104NV, eFlow104N8V, eFlow104N8DV, eFlow104N16V, eFlow104N16DV:
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)
eFlow104NXV, eFlow104NX8V, eFlow104NX8DV, eFlow104NX16V, eFlow104NX16DV:
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
Page 4
- 4 - eFlow104NV Series
6. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1b, pg. 5) supervisory relay outputs.
7. To delay AC reporting for 2 hrs. set dip switch [AC Delay] to OFF position (Fig. 1c, pg. 5). To delay AC reporting for 1 min. set dip switch [AC Delay] to ON position (Fig. 1c, pg. 5). Note: Must be set to ON position for Burglar Alarm Applications.
8. To enable Fire Alarm Disconnect set DIP switch [Shutdown] to ON position (Fig. 1c, pg. 5). To disable Fire Alarm Disconnect set DIP switch [Shutdown] to OFF position (Fig. 1c, pg. 5).
9. Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger terminals will cause [DC] output to shutdown (Fig. 1d, pg. 5).
10. Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching [Trigger EOL Shutdown] (Fig. 1e, pg. 5).
11. For Access Control Applications: mount tamper switch (Honeywell Model 112 or equivalent) at the top of the enclosure. Slide tamper switch bracket onto the edge or the enclosure approx. 2” from the right side (Fig. 5, pg. 7 or Fig. 7, pg. 9). Connect tamper switch wiring to the Access Control Panel input or the appropriate reporting device.
Wiring:
Use 18 AWG or larger for all low voltage power connections. Note: Take care to keep power-limited circuits separate from non power-limited wiring (220VAC, Battery).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level eFlow104NV: 24VDC nominal rated @ 10A max. Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage (24VDC @ 26.4) both at battery terminal and at the board terminals marked [– BAT +] to ensure that there is no break in the battery connection wires.
Note: Maximum charging current under discharges is 1.54A. Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.
LED Diagnostics:
Power Supply/Charger
Red (DC) Green (AC/AC1) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery supplying power.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Power Distribution Module
Green (AC) Power Distribution Module Status
ON Normal operating condition.
OFF No Power Output.
Page 5
eFlow104NV Series - 5 -
Terminal Identification:
Power Supply/Charger
Terminal Legend Function/Description
L, N
Connect 220VAC 50/60Hz to these terminals: L to hot, N to neutral (non power-limited) (Fig. 1a, pg. 5).
– DC + 24VDC nominal @ 10A continuous output (power-limited output) (Fig. 1h, pg. 5).
Trigger EOL Supervised
Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open, normally closed from an FACP output circuit (power-limited input) (Fig. 1d, pg. 5).
NO, GND RESET FACP interface latching or non-latching (power-limited) (Fig. 1e, pg. 5).
+ AUX – Auxiliary power-limited output rated @ 1A (unswitched) (Fig. 1f, pg. 5).
AC Fail NC, C, NO
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1A @ 30VDC (power-limited) (Fig. 1b, pg. 5).
Bat Fail NC, C, NO
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1A @ 30VDC. A removed battery is reported within 5 minutes. Battery reconnection is reported within 1 minute (power-limited) (Fig. 1b, pg. 5).
– BAT +
Stand-by battery connections. Maximum charge current 1.54A (non power-limited) (Fig. 1g, pg. 5).
Power Distribution Module
Terminal Legend PD8UL/PD8ULCB
Terminal Legend PD16W/PD16WCB
Function/Description
1P to 8P 1P to 16P Positive DC power outputs.
1N to 8N 1N to 16N Negative DC power outputs.
Fig. 1 - eFlow104NV Board configuration
Trouble/Time Limited Warning of Stand-by Batteries:
The Time Limited Warning circuit must be connected for local or remote annunciation with an Amber or Red LED to indicate DC Trouble (low battery, loss of battery or when 95% of the stand-by battery has been depleted). Connect the circuit to the Batt Fail relay contacts to an appropriate input of a Burglar Alarm or Access Control Panel. The following figure shows the circuitry needed for local annunciation.
LG N
NC C NO NC C NO
BAT FAILAC FAIL
--- DC +
AC
AC1
DC
--- BAT +
+ AUX –
enable disable
1 min. 2 hr.
AC DELAY SHUTDOWN
TRIGGER EOL SUPERVISED
NO GND
RESET
O N
5A 250V
1a 1b
1
g
1h
1e 1f1d
1c
Page 6
- 6 - eFlow104NV Series
Fig. 2 - Battery trouble indication - Wire one leg of a power-limited power source to the indicating lamp. Wire the second leg of the power source to the indicating lamp in series with the battery fail relay contact terminals marked [BAT FAIL - C, NO]. (Fig. 2, pg. 6).
NC C NO NC C NO
BAT FAILAC FAIL
POWER
SOURCE
RED INDICATING
LAMP
Power Distribution Module(s):
Fig. 3a - PD8 Power Distribution Board Fig. 3b - PD8CB - Power Distribution Board Non Power-Limited Outputs Power-Limited Outputs
Fig. 4a - PD16W Power Distribution Board Fig. 4b - PD16WCB - Power Distribution Board Non Power-Limited Outputs Power-Limited Outputs
N
COMMON POWER OUTPUTS
P
FUSED POWER OUTPUTS
1 2 3 4 5 6 7 8
D1
INPUT
R1
LED
From Power Supply
Board
(Factory Installed)
Replace fuses with the same type and rating 3.5A, 250V.
DC Output to devices
1P-8P Power Outputs,
1N-8N Common Outputs
(
)
N
COMMON POWER OUTPUTS
P
FUSED POWER OUTPUTS
1 2 3 4 5 6 7 8
D1
INPUT
R1
LED
From Power Supply
Board
(Factory Installed)
DC Output to devices
1P-8P Power Outputs,
1N-8N Common Outputs
(
)
common
outputs
protected
outputs
P
N
N P S
Input
12345678
9 10 11 12 13 14 15 16
P
N
3.5A 250V
For continuous protection against risk of fire
replace fuses with same type and rating.
From Power Supply
Board
(Factory
Installed)
DC Output to devices
1P-16P Power Outputs,
1N-16N Common Outputs
()
P
N
NPS
Input
NP
common
outputs
protected
outputs
12345678
9 10 11 12 13 14 15 16
From Power Supply
Board
(Factory
Installed)
DC Output to devices
1P-16P Power Outputs,
1N-16N Common Outputs
)(
Page 7
eFlow104NV Series - 7 -
Fig. 5 - eFlow104NV configuration
* Outputs are non power-limited: eFlow104NV, eFlow104N8V, eFlow104N16V. Outputs are power-limited: eFlow104N8DV, eFlow104N16DV.
L
G
N
NC
C
NO
NC
C
NO
BAT FAIL
AC FAIL
--- DC +
AC
AC1
DC
--- BAT +
– AUX +
TRIGGER EOL
SUPERVISED
5A 250V
RESET
GND NO
disable
enable
2 hr.
1 min.
AC DELAY
SHUTDOWN
O
N
Door
Wire Strap (from Enclosure to Door)
220VAC
power mains
Battery and AC
Supervision
Circuit
Battery
Connections
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
7AH Rechargeable batteries are the largest batteries that can fit in this enclosure. An external battery enclosure must be used if using 12AH, 40AH or 65AH batteries.
DC Output to devices*
(refer to Fig. 3a, 3b, 4a or 4b
for board configuration pg. 6)
PD8/PD8CB PD16W/
PD16WCB
Optional Rechargeable
Stand-by Battery
Optional Rechargeable
Stand-by Battery
Ground
Lug
Edge of
Enclosure
to Access Control
Panel or
U.L. Listed
Reporting
Device
Enclosure
Tamper Switch
(Not Included)
Page 8
- 8 - eFlow104NV Series
NEC Power-Limited Wiring Requirements for eFlow104NV Models:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Optional battery enclosure must be mounted adjacent to the power supply.
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 6a).
Fig. 6
Fig. 6a
External Jacketed
Shield
Incorrect Wire
Handling
Correct Wire
Handling
Pull back external jacketed shield approx. 1/2”.
Wire
Insulation
Solid Copper
Conductors
* Outputs are non power-limited:
eFlow104NV, eFlow104N8V, eFlow104N16V.
Outputs are power-limited:
eFlow104N8DV, eFlow104N16DV.
Input 220VAC 50/60Hz
(non power-limited)
Optional Battery
Enclosure
(non power-limited)
Supervisory,
Fire Alarm
Interface and
Aux. output
Connections
(power-limited)
Battery
Connections
(non power-limited)
DC Outputs*
Power
Distribution
Page 9
eFlow104NV Series - 9 -
Fig. 7 - eFlow104NXV configuration
Door
Wire Strap (from Enclosure to Door)
Battery and AC
Supervision Circuit
L
G
N
NC
C
NO
NC
C
NO
BAT FAIL
AC FAIL
--- DC +
AC
AC1
DC
--- BAT +
– AUX +
TRIGGER EOL SUPERVISED
5A 250V
RESET
GND NO
disable enable
2 hr. 1 min.
AC DELAY
SHUTDOWN
O N
220VAC
power mains
Battery
connections
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
12AH Rechargeable batteries are the largest batteries that can fit in this enclosure. An external battery enclosure must be used if using the 40AH or 65AH batteries.
DC Output to devices*
(refer to Fig. 3a, 3b
for board configuration pg. 6)
PD8/PD8CB
DC Output to devices*
(refer to Fig. 3a, 3b
for board configuration pg. 6)
PD8/PD8CB
Optional Rechargeable
Stand-by Battery
Optional Rechargeable
Stand-by Battery
Ground
Lug
* Outputs are non power-limited:
eFlow104NXV, eFlow104NX8V, eFlow104NX16V.
Outputs are power-limited: eFlow104NX8DV, eFlow104NX16DV.
Edge of
Enclosure
to Access Control
Panel or
U.L. Listed
Reporting
Device
Enclosure
Tamper Switch
(Not Included)
Page 10
- 10 - eFlow104NV Series
NEC Power-Limited Wiring Requirements for eFlow104NXV Models:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Optional battery enclosure must be mounted adjacent to the power supply.
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 8a).
Fig. 8
Fig. 8a
External Jacketed
Shield
Incorrect Wire
Handling
Correct Wire
Handling
Pull back external jacketed shield approx. 1/2”.
Wire
Insulation
Solid Copper
Conductors
* Outputs are non power-limited:
eFlow104NXV, eFlow104NX8V, eFlow104NX16V.
Outputs are power-limited:
eFlow104NX8DV, eFlow104NX16DV.
Input
220VAC 50/60Hz
(non power-
limited)
Optional Battery
Enclosure
(non power-limited)
Supervisory, Fire Alarm Interface
and Aux. output Connections
(power-limited)
Battery Connections (non power-
limited)
DC Output*
Power
Distribution
Page 11
eFlow104NV Series - 11 -
Enclosure Dimensions (BC300):
eFlow104NV, eFlow104N8V, eFlow104N8DV, eFlow104N16V, eFlow104N16DV
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)
1.40”
(36mm)
1.40”
(36mm)
4.85”
(123mm)
4.85”
(123mm)
1.40”
(36mm)
1.40”
(36mm)
5.10”
(130mm)
5.10”
(130mm)
13.0”
(330mm)
5.10”
(130mm)
6.5625”
(167mm)
1.20”
(31mm)
1.20”
(31mm)
1.20”
(31mm)
3.25”
(83mm)
3.25”
(83mm)
3.25”
(83mm)
3.25”
(83mm)
1.0”
(25mm)
1.0”
(
25mm
)
10.5”
(
267mm
)
1.0”
(
25mm
)
1.0”
(25mm)
0.75”
(19mm)
0.75”
(19mm)
0.9375” (24mm)
0.9375” (24mm)
11.0”
(279mm)
12.5”
(318mm)
Page 12
- 12 - eFlow104NV Series
1.5”
(38.1mm)
1.5”
(38.1mm)
1.5”
(38.1mm)
5.0”
(127.0mm)
5.0”
(127.0mm)
1.5”
(38.1mm)
2.0”
(50.8mm)
2.0”
(50.8mm)
1.75”
(44.45mm)
1.75”
(44.45mm)
4.5”
(114.3mm)
1.25”
(31.75mm)
4.5”
(114.3mm)
1.25”
(31.75mm)
1.25”
(31.75mm)
1.25”
(31.75mm)
1.1”
(27.94mm)
1.1”
(27.94mm)
0.79”
(20.06mm)
1.1”
(27.94mm)
0.91”
(23.114mm)
0.91”
(23.114mm)
1.375”
(34.925mm)
1.125”
(28.575mm)
15.5”
(393.7mm)
4.615”
(117.22mm)
12.23”
(310.64mm)
4.615”
(117.22mm)
1.5”
(38.1mm)
1.5”
(38.1mm)
4.615”
(117.22mm)
4.615”
(117.22mm)
Enclosure Dimensions (BC400):
eFlow104NXV, eFlow104NX8V, eFlow104NX8DV, eFlow104NX16V, eFlow104NX16DV
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
Page 13
eFlow104NV Series - 13 -
Appendix A - Compatible Devices
A.1 Four (4) Wire Smoke Detectors
Table A-1 below lists four (4) wire smoke detectors compatible with eFlow104NV output.
System Sensor Smoke Detector/Base
Detector Type
Max
Stand-by
Current
(mA)
Alarm
Current
(mA)
B112LP Base 0.12 36
B114LP Base * *
B404B Base * *
DH100ACDC Photoelectric 0.15 0.70
DH100ACDCLP Photoelectric 0.15 0.70
DH100ACDCLPW Photoelectric 0.15 0.70
DH400ACDCI Ionization Duct 25 95
DH400ACDCP Photoelectric Duct 25 95
1112/24/D Ionization 0.05 50
1424 Ionization 0.10 41
1451 (w/B402B Base) Ionization 0.10 39
2112/24ATR Photoelectric 0.50 60/70
2112/24AITR Photoelectric 0.50 60/70
2112/24/D Photoelectric 0.05 50
2112/24T/D Photoelectric w/135
o
Thermal 0.05 50
2112/24TSRB Photoelectric w/135
o
Thermal Supervisory Relay 15 45
2312/24TB Photoelectric 0.12 50
2412 (12 volt) Photoelectric 0.12 77
2424 Photoelectric 0.10 41
2451 Photoelectric 0.10 39
2451TH (with/B402B Base) Photoelectric 0.10 39
2W-MOD Loop Test/Maintenance Mod. 30 50
4W-B (12/24 volt) Photoelectric I
3
0.05 23
4WT-B (12/24 volt) Photoelectric I3 w/Therm 0.05 23
4WTA-B (12/24 volt) I3 Photo w/Therm/Sounder 0.05 35
4WTR-B (12/24 volt) I3 Photo w/Therm/Relay 0.05 35
4WITAR-B (12/24 volt) I3 Photo w/Isolated Therm/Sounder/Relay 0.05 50
2W-MOD2 I3 Loop Test/Maintenance Mod. 0.05 *
RRS-MOD I3 Reversing Relay/Sync Module 0.05 *
6424 Projected Beam 10 28.4
Beam 1224(S) Projected Beam 17 38.5
* Contact manufacturer for current draws.
A.2 Relays
Table A-2 below lists relays compatible with eFlow104NV output.
Manufacturer Model Current (mA) Manufacturer Model Current (mA)
System Sensor
PR-1 PR-2 PR-3
EOLR-1
R-10T R-14T
15 30 30 30 23 23
System Sensor
R-20T R-24T R-10E R-14E R-20E R-24E
40 40 23 23 40 40
Page 14
- 14 - eFlow104NV Series
eFlow Power Supply/Chargers can be
Controlled and Monitored while Reporting
Power/Diagnostics from Anywhere
over the Network...
LINQ2 Mounts Inside any eFlow Enclosure
LINQ2 - Network Communication Module
LINQ2 provides remote IP access to real-time data from eFlow power supply/chargers to help keep systems up and running at optimal levels. It facilitates fast and easy installation and set-up, minimizes system downtime, and eliminates unnecessary service calls, which helps reduce Total Cost of Ownership (TCO) - as well as creating a new source of Recurring Monthly Revenue (RMR).
LINQ2
Features:
- UL Listed in the U.S. and Canada.
- Local or remote control of up to (2) two Altronix eFlow power output(s) via LAN and/or WAN.
- Monitor real time diagnostics: DC output voltage, output current, AC & battery status/service, input trigger state change, output state change and unit temperature.
- Access control and user managment: Restrict read/write, Restrict users to specific resources
- Two (2) integral network controlled Form “C” Relays.
- Three (3) programmable input triggers: Control relays and power supplies via external hardware sources.
- Email and Windows Dashboard notifications
- Event log tracks history.
- Secure Socket Layer (SSL).
- Programmable via USB or web browser - includes operating software and 6 ft. USB cable.
LINQ2 Module
Network Connection:
Installation, Programming and Monitoring
L
G
N
NC
C
NO
NC
C
NO
BAT FAIL
AC FAIL
AC
AC1
DC
TRIGGER EOL
SUPERVISED
disable
enable
2 hr.
1 min.
AC DELAY
SHUTDOWN
O
N
eFlow
Power
Supply/Charger
Page 15
eFlow104NV Series - 15 -
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056 website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty | Made in U.S.A. IIeFlow104NV Series G25R
MEMBER
Notes:
Page 16
CUT ALONG DOTTED LINE
Power Supply/Chargers Operating Guide
Models Include:
Model
Input
220VAC,
50/60Hz
Output
Auxiliary Power-Limited
Output (unswitched)
Ripple
Voltage
12VDC 24VDC
eFlow104NV, eFlow104N8V, eFlow104N8DV, eFlow104N16V, eFlow104N16DV
2.7A 10A 1A 700mV eFlow104NXV, eFlow104NX8V, Flow104NX8DV, eFlow104NX16V, eFlow104NX16DV
Overview:
The eFlow104NV series power supply/chargers convert a 220VAC, 50/60Hz input to a 24VDC output.
Stand-by Specifications:
Battery
Burg. Applications
4 hr. Stand-by/
15 min. Alarm
Fire Applications
24 hr. Stand-by/
5 min. Alarm
Access Control
Applications Stand-by
7AH 0.4A/10A N/A 5 Mins./10A
12AH 1A/10A 0.3A/10A 15 Mins./10A
40AH 6A/10A 1.2A/10A Over 2 Hours/10A
65AH 6A/10A 1.5A/10A Over 4 Hours/10A
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 1.54A.
• Automatic switch over to stand-by battery when AC fails. Transfer to stand-by battery power is instantaneous with no interruption.
LED Diagnostics:
Red (DC) Green (AC/AC1) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery supplying power.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Installing Company: ________________ Service Rep. Name: ______________________________________
Refer to the eFlow Power Supply/Chargers Installation Guide: IIeFlow104NV Series, Rev. 104NVRP052213 for complete instructions. This sheet is to be removed, framed and posted next to the unit.
Rev. 104NVRP052213
Loading...