Altronix eFlow6N8V, eFlow6N16V, eFlow6NX16V, eFlow6N8DV, eFlow6NX8DV Installation Manual

...
Page 1
Power Supply/Chargers
Installation Guide
Models Include:
eFlow6NV/eFlow6NXV
- 6 amp @ 12VDC or 24VDC
eFlow6N8V/eFlow6NX8V eFlow6N8DV/eFlow6NX8DV
- 6 amp @ 12VDC or 24VDC - 6 amp @ 12VDC or 24VDC
- Eight (8) Fused Outputs - Eight (8) PTC Outputs
- 6 amp @ 12VDC or 24VDC - 6 amp @ 12VDC or 24VDC
- Sixteen (16) Fused Outputs - Sixteen (16) PTC Outputs
Rev. 6NVRP052213 More than just power.™
Installing Company: _____________________ Service Rep. Name: __________________________________________
Address: ________________________________________________________ Phone #: _________________________
Page 2
Overview:
The eFlow6NV power supply/chargers convert a 220VAC (working range 198VAC - 256VAC), 50/60Hz input to a 12VDC or 24VDC nominal output (see Power Supply Configuration Reference Chart and Specifications).
eFlow6NV Series Power Supply Configuration Reference Chart:
Nominal DC Outputs
[DC] [AUX]
Altronix
Model Number
eFlow6NV
eFlow6NXV
eFlow6N8V
eFlow6NX8V 2.5A
eFlow6N8DV
eFlow6NX8DV 2A
eFlow6N16V
eFlow6NX16V 2 - PD8 2.5A
eFlow6N16DV
eFlow6NX16DV
12VDC Output
Range (volts)
10.0-
13.2
10.0-
13.2
9.78-
13.2
10.0-
13.2
9.78-
13.2
20.19-
26.4
20.19-
26.4
20.0-
26.4
20.19-
26.4
20.0-
26.4
24VDC Output
Range (volts)
12VDC Output
Range (volts)
10.03-
13.2
10.03-
13.2
10.03-
13.2
10.03-
13.2
10.03-
13.2
24VDC Output
20.19-
26.4
20.19-
26.4
20.19-
26.4
20.19-
26.4
20.19-
26.4
Maximum Supply
Current for Main and
Aux. Outputs (amp)
Input Rating:
220VAC, 50/60Hz
Range (volts)
6 2.1A 5A/250V 10A/32V 910 N/A 1
6 2.1A 5A/250V 10A/32V 910 PD8 8
6 2.1A 5A/250V 10A/32V 910 PD8CB 8
6 2.1A 5A/250V 10A/32V 910
6 2.1A 5A/250V 10A/32V 910
Input Fuse Rating
Battery Fuse Rating
Ripple Voltage (mV)
Under low battery condition
PD16W
PD16WCB
2 - PD8CB
Power Distribution
Modiule
Number of Outputs
Fused Output Ratings
2.5A
2A
2.5A
16
2A
16
2A
PTC Output Ratings
3
3
3
3
3
Accommodates up to
7AH Batteries
Accommodates up to
12AH Batteries
3
3
3
3
3
European Conformity
Stand-by Specifications:
Fire Applications
24 hr. Stand-by/
5 min. Alarm
Battery
Burg. Applications
4 hr. Stand-by/
15 min. Alarm
7AH 0.4 amp/6 amp N/A 10 Mins./6 amp 12AH 1 amp/6 amp 0.3 amp/6 amp 25 Mins./6 amp 40AH (for eFlow6NXV refer to Fig. 8, pg. 10) 6 amp/6 amp 1.2 amp/6 amp Over 4 Hours/6 amp 65AH (for eFlow6NXV refer to Fig. 8, pg. 10) 6 amp/6 amp 1.5 amp/6 amp Over 4 Hours/6 amp
Access Control
Applications
Stand-by
Specifications:
Input:
• 220VAC (working range 198VAC - 256VAC), 50/60Hz.
Output:
• For output voltage and supply current refer to eFlow6NV Series Power Supply Configuration Reference Chart, pg. 2.
• Auxiliary output rated @ 1 amp (unswitched).
• Overvoltage protection.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 1.54 amp.
• Automatic switch over to stand-by battery when AC fails. Transfer to stand-by battery power is instantaneous with no interruption.
Fire Alarm Disconnect:
• Supervised Fire Alarm disconnect (latching or non-latching) 10K EOL resistor. Operates on a normally open (NO) or normally closed (NC) trigger.
Supervision:
• AC fail supervision (form “C” contacts).
• Battery fail and presence supervision (form “C” contacts).
- 2 - eFlow6NV Series
Supervision (cont’d):
• Low power shutdown. Shuts down DC output terminals if battery voltage drops below 71-73% for 12V units and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
Fuse Ratings:
• Refer to eFlow6NV Series Power Supply Configuration Reference Chart, pg. 2.
Visual Indicators:
• Green AC Power LED indicates 220VAC present.
• AC input and DC output LED indicators.
Additional Features:
• Short circuit and overload protection.
• Unit is complete with power supply, enclosure, battery leads and cam lock.
Enclosure Dimensions (approximate H x W x D):
eFlow6NV, eFlow6N8V, eFlow6N8DV, eFlow6N16V, eFlow6N16DV:
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)
eFlow6NXV, eFlow6NX8V, eFlow6NX8DV, eFlow6NX16V, eFlow6NX16DV:
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
Page 3
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, the Canadian Electri­cal Code, Part 1 and with all local codes and authorities having jurisdiction. The product must be located indoors within the protected premises.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 11-12). Secure enclosure to earth ground.
2. Set desired DC output voltage by setting SW1 to the appropriate position on the power supply board (Fig. 1i, pg. 5).
3. Connect unswitched AC power (220VAC 50/60Hz) to terminals marked [L, N] (Fig. 1a, pg. 5). Use 14 AWG or larger for all power connections. Secure green wire lead to earth ground.
Keep power-limited wiring separate from non power-limited wiring (220VAC 50/60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided. CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
For Fire Alarm applications the outputs are “Special Applications” only, see list (refer to Appendix A, pg. 12).
4. Measure output voltage before connecting devices. This helps avoiding potential damage.
5. Connect devices to be powered: a. For eFlow6NV/eFlow6NXV connect devices to terminals marked [- DC +] (Fig. 1h, pg. 3). b. For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 3a & 3b, pg. 6) or 1 to 16 marked [1P & 1N] through [16P & 16N] (Fig. 4a & 4b, pg. 6) carefully observing correct polarity. For auxiliary device connection: this output will not be affected by Low Power Disconnect or Fire Alarm Interface. Connect device to terminals marked [+ AUX -- ] (Fig. 1f, pg. 5).
6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. Connect battery to terminals marked [-- BAT + ] (Fig. 1g, pg. 5). Use two (2) 12VDC batteries connected in series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH), CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or BAZR2 batteries of an appropriate rating.
7. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1b, pg. 5) supervisory relay outputs.
8. To delay AC reporting for 2 hrs. set dip switch [AC Delay] to OFF position (Fig. 1c, pg. 5). To delay AC reporting for 1 min. set dip switch [AC Delay] to ON position (Fig. 1c, pg. 5). Note: Must be set to ON position for Burglar Alarm Applications.
9. To enable Fire Alarm Disconnect set dip switch [Shutdown] to ON position (Fig. 1c, pg. 5). To disable Fire Alarm Disconnect set dip switch [Shutdown] to OFF position (Fig. 1c, pg. 5).
10. Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger terminals will cause [DC] output to shutdown (Fig. 1d, pg. 5).
11. Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching [Trigger EOL Shutdown] (Fig. 1e, pg. 5).
12. For Access Control Applications: mount tamper switch (Sentrol model 3012 or equivalent) at the top of the enclosure. Slide tamper switch bracket onto the edge or the enclosure approx. 2” from the right side (Fig. 5, pg. 7 or Fig. 7, pg. 9). Connect tamper switch wiring to the Access Control Panel input or the appropriate reporting device.
Use 18 AWG or larger for all low voltage power connections. Note: Take care to keep power-limited circuits separate from non power-limited wiring (220VAC, Battery).
Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level eFlow6NV: 12VDC or 24VDC nominal rated @ 6 amp max. Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage (12VDC @ 13.2 or 24VDC @ 26.4) both at the battery terminal and at the board terminals marked [-- BAT + ] to ensure that there is no break in the battery connection wires.
Note: Maximum charging current under discharges is 1.54 amp. Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.
eFlow6NV Series - 3 -
Wiring:
Maintenance:
Page 4
LED Diagnostics:
Power Supply/Charger
Red (DC) Green (AC/AC1) Power Supply Status
ON ON Normal operating condition. ON OFF Loss of AC. Stand-by battery supplying power. OFF ON No DC output. OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Power Distribution Module
Green (AC) Power Distribution Module Status
ON Normal operating condition. OFF No power output.
Terminal Identification:
Power Supply/Charger
Terminal Legend Function/Description
L, N
– DC + 12VDC or 24VDC nominal @ 6 amp continuous output (non power-limited output) (Fig. 1h, pg. 5). Trigger EOL
Supervised NO, GND RESET FACP interface latching or non-latching (power-limited) (Fig. 1e, pg. 5). + AUX – Auxiliary power-limited output rated @ 1 amp (unswitched) (power-limited output) (Fig. 1f, pg. 5). AC Fail
NC, C, NO
Bat Fail NC, C, NO
– BAT + Stand-by battery connections. Maximum charge current 1.54 amp (non power-limited) (Fig. 1g, pg. 5).
Connect 220VAC 50/60Hz to these terminals: L to hot, N to neutral (non power-limited) (Fig. 1a, pg.5).
Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open, normally closed from an FACP output circuit (power-limited input) (Fig. 1d, pg. 5).
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1 amp @ 30VDC (power-limited) (Fig. 1b, pg. 5).
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1 amp @ 30VDC. A removed battery is reported within 5 minutes. Battery reconnection is reported within 1 minute (power-limited) (Fig. 1b, pg. 5).
Terminal Identification:
Power Distribution Module
Terminal Legend PD8/PD8CB
1P to 8P 1P to 16P Positive DC power outputs. 1N to 8N 1N to 16N Negative DC power outputs.
Terminal Legend PD16W/PD16WCB
Function/Description
- 4 - eFlow6NV Series
Page 5
Fig. 1 - eFlow6NV Board configuration
OFF --- 24V
ON
1i
ON --- 12V
1h
--- DC +
10A
1g
--- BAT +
5A 250V
5A 250V
AC1
LG N
NC C NO NC C NO
1a 1b
AC FAIL
BAT FAIL
AC
AC DELAY SHUTDOWN
O N
DC
1 min. 2 hr.
enable disable
10A 32V
TRIGGER EOL
SUPERVISED
NO GND
RESET
1e 1f1d1c
+ AUX –
Trouble/Time Limited Warning of Stand-by Batteries:
The Time Limited Warning circuit must be connected for local or remote annunciation with an Amber or Red LED to indi­cate DC Trouble (low battery, loss of battery or when 95% of the stand-by battery has been depleted). Connect the circuit to the Batt Fail relay contacts to an appropriate input of a Burglar Alarm or Access Control Panel. The following figure shows the circuitry needed for local annunciation.
Fig. 2 - Battery trouble indication - For Canadian use, a red indicating lamp must be visible from the exterior of this enclosure. Wire one leg of a power source to the indicating lamp. Wire the second leg of the power source to the indicating lamp in series with the battery fail relay contact terminals marked [BAT FAIL - C, NO] (Fig. 2, pg. 5).
BAT FAILAC FAIL
eFlow6NV Series - 5 -
POWER
SOURCE
NC C NO NC C NO
RED INDICATING
LAMP
Page 6
Power Distribution Module(s):
Replace fuses with the same type and rating 3.5A, 250V.
(
)
(
)
Installed)
DC Output to devices
Fig. 3a - PD8 Power Distribution Board Fig. 3b - PD8CB - Power Distribution Board Non Power-Limited Outputs Power-Limited Outputs
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
P
D1
FUSED POWER OUTPUTS
N
COMMON POWER OUTPUTS
DC Output to devices
1P-8P Power Outputs,
1N-8N Common Outputs
From Power Supply
(Factory Installed)
R1
Board
LED
INPUT
Fig. 4a - PD16W Power Distribution Board Fig. 4b - PD16WCB - Power Distribution Board Non Power-Limited Outputs Power-Limited Outputs
DC Output to devices
1P-16P Power Outputs,
()
1N-16N Common Outputs
P
FUSED POWER OUTPUTS
N
COMMON POWER OUTPUTS
DC Output to devices
1P-8P Power Outputs,
1N-8N Common Outputs
1P-16P Power Outputs,
1N-16N Common Outputs
D1
LED
R1
INPUT
From Power Supply
(Factory Installed)
Board
)(
3.5A 250V
common
outputs
protected
outputs
For continuous protection against risk of fire
12345678
9 10 11 12 13 14 15 16
replace fuses with same type and rating.
N
P
N
From
N P S
Power
Supply
Board
P
(Factory
Input
12345678
common
outputs
protected
outputs
9 10 11 12 13 14 15 16
N
P
NP
From
NPS
Power
Supply
Board
(Factory
Installed)
Input
- 6 - eFlow6NV Series
Page 7
Edge of
Enclosure
to Access Control
Panel or
U.L. Listed
Reporting
Device
Enclosure
Sentrol
model # 3012
Tamper Switch
or equivalent
(Not Included)
Fig. 5 - eFlow6NV configuration
5A 250V
Door
Wire Strap (from Enclosure to Door)
Green
Lead
(ground)
L
G
NC
NO
NC
NO
C
C
2 hr.
disable
TRIGGER EOL
RESET
N
1 min.
enable
SUPERVISED
GND NO
– AUX +
220VAC
power mains
AC1
Battery and AC
AC FAIL
BAT FAIL
AC
DC
AC DELAY
O
N
SHUTDOWN
Supervision
Circuit
Battery
Connections
--- BAT +
Switch Detail
ON
Switch On - 12V Switch Off - 24V
OFF --- 24V ON --- 12V
--- DC +
PD8/PD8CB PD16W/
1
DC Output to devices*
(refer to Fig. 3a, 3b, 4a or 4b
for board configuration pg. 6)
ON
PD16WCB
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
eFlow6NV Series - 7 -
7AH Rechargeable batteries are the largest batteries that can fit in this enclosure. An external battery enclosure must be used if using 12AH, 40AH or 65AH batteries.
Optional Rechargeable
Stand-by Battery
Optional Rechargeable
Stand-by Battery
Page 8
NEC Power-Limited Wiring Requirements for eFlow6NV Models:
Incorrect Wire
Correct Wire
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). Optional battery enclosure must be mounted adjacent to the power supply. Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 7a).
Fig. 7
220VAC Input
50/60Hz
(non power-
limited)
Supervisory,
Fire Alarm
Interface and
Aux. output
Connections
(power-limited)
Optional Battery
Enclosure
(non power-limited)
Fig. 7a
Battery
Connections
(non power-limited)
Solid Copper
Conductors
Handling
Insulation
External Jacketed
Wire
Shield
Handling
Pull back external jacketed shield approx. 1/2”.
*Outputs are non power-limited: eFlow6NV, eFlow6N8V, eFlow6N16V. Outputs are power-limited: eFlow6N8DV, eFlow6N16DV.
Power
Distribution
DC Outputs*
- 8 - eFlow6NV Series
Page 9
Edge of
Enclosure
to Access Control
Panel or
U.L. Listed
Reporting
Device
Enclosure
Sentrol
model # 3012
Tamper Switch
or equivalent
(Not Included)
Fig. 8 - eFlow6NXV configuration
Door
Wire Strap (from Enclosure to Door)
Battery and
AC Supervision
TRIGGER EOL
RESET
– AUX +
GND NO
--- BAT +
Battery
SUPERVISED
disable enable
SHUTDOWN
NO
2 hr. 1 min.
AC DELAY
DC
AC
O N
BAT FAIL
connections
--- DC +
OFF --- 24V ON --- 12V
ON
PD8/PD8CB
DC Output to devices*
(refer to Fig. 3a, 3b
for board configuration pg. 6)
Circuit
Green
Lead
(ground)
NC
NC
NO
C
C
AC1
AC FAIL
Switch Detail
ON
Switch On - 12V Switch Off - 24V
DC Output to devices*
for board configuration pg. 6)
220VAC
power mains
G
L
N
1
PD8/PD8CB
(refer to Fig. 3a, 3b
5A 250V
Optional Rechargeable
Stand-by Battery
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
12AH Rechargeable batteries are the largest batteries that can fit in this enclosure. An external battery enclosure must be used if using the 40AH or 65AH batteries.
eFlow6NV Series - 9 -
Optional Rechargeable
Stand-by Battery
Page 10
NEC Power-Limited Wiring Requirements for eFlow6NXV Models:
Incorrect Wire
Correct Wire
x. 1/2”.
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). Optional battery enclosure must be mounted adjacent to the power supply.
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 9a).
Fig. 9
Supervisory, Fire Alarm Interface
and Aux. output Connections
(power-limited)
Fig. 9a
Optional Battery
Enclosure
(non power-limited)
DC Output*
Handling
External Jacketed
Shield
220VAC Input
50/60Hz
(non power-
limited)
Power
Distribution
Battery Connections (non power-
limited)
Handling
Wire
Insulation
Solid Copper
Conductors
Pull back external jacketed shield appro
*Outputs are non power-limited:
eFlow6NXV, eFlow6NX8V, eFlow6NX16V.
Outputs are power-limited:
eFlow6NX8DV, eFlow6NX16DV.
- 10 - eFlow6NV Series
Page 11
Enclosure Dimensions (BC300) (approximate H x W x D):
(
)
(
)
(
)
eFlow6NV, eFlow6N8V, eFlow6N8DV, eFlow6N16V, eFlow6N16DV
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)
1.40”
(36mm)
5.10”
(130mm)
1.20”
(31mm)
13.0”
(330mm)
(36mm)
0.75”
(19mm)
1.40”
4.85”
(123mm)
12.5”
(318mm)
11.0”
(279mm)
4.85”
(123mm)
1.40”
(36mm)
(19mm)
0.75”
1.20”
(31mm)
0.9375” (24mm)
3.25”
(83mm)
1.20”
(31mm)
1.40”
(36mm)
5.10”
(130mm)
5.10”
(130mm)
3.25”
(83mm)
1.0”
(25mm)
1.0”
25mm
10.5”
267mm
1.0”
25mm
0.9375” (24mm)
1.0”
(25mm)
3.25”
(83mm)
3.25”
(83mm)
6.5625”
(167mm)
eFlow6NV Series - 11 -
Page 12
Enclosure Dimensions (BC400) (approximate H x W x D):
eFlow6NXV, eFlow6NX8V, eFlow6NX8DV, eFlow6NX16V, eFlow6NX16DV
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
1.5”
(38.1mm)
2.0”
(50.8mm)
1.25”
(31.75mm)
4.5”
(114.3mm)
0.91”
(23.114mm)
1.5”
(38.1mm)
1.1”
(27.94mm)
4.615”
(117.22mm)
12.23”
(310.64mm)
4.615”
(117.22mm)
1.5”
(38.1mm)
1.1”
(27.94mm)
1.75”
(44.45mm)
0.91”
(23.114mm)
(393.7mm)
1.375”
(34.925mm)
1.125”
(28.575mm)
15.5”
4.5”
(114.3mm)
1.25”
(31.75mm)
1.5”
(38.1mm)
2.0”
(50.8mm)
5.0”
(127.0mm)
1.25”
(31.75mm)
1.5”
(38.1mm)
4.615”
(117.22mm)
4.615”
(117.22mm)
1.1”
(27.94mm)
1.5”
(38.1mm)
0.79”
(20.06mm)
1.75”
(44.45mm)
1.25”
(31.75mm)
5.0”
(127.0mm)
- 12 - eFlow6NV Series
Page 13
Appendix A - Compatible Devices
A.1 Four (4) Wire Smoke Detectors
Table A-1 below lists four (4) wire smoke detectors compatible with eFlow6NV output.
System Sensor Smoke Detector/Base
Detector Type
Max Stand-by Current (mA)
Alarm Current
(mA)
B112LP Base 0.12 36 B114LP Base * * B404B Base * * DH100ACDC Photoelectric 0.15 0.70 DH100ACDCLP Photoelectric 0.15 0.70 DH100ACDCLPW Photoelectric 0.15 0.70 DH400ACDCI Ionization Duct 25 95 DH400ACDCP Photoelectric Duct 25 95 1112/24/D Ionization 0.05 50 1424 Ionization 0.10 41 1451 (w/B402B Base) Ionization 0.10 39 2112/24ATR Photoelectric 0.50 60/70 2112/24AITR Photoelectric 0.50 60/70 2112/24/D Photoelectric 0.05 50
o
2112/24T/D Photoelectric w/135
o
2112/24TSRB Photoelectric w/135
Thermal Supervisory Relay 15 45
Thermal 0.05 50
2312/24TB Photoelectric 0.12 50 2412 (12 volt) Photoelectric 0.12 77 2424 Photoelectric 0.10 41 2451 Photoelectric 0.10 39 2451TH (with/B402B Base) Photoelectric 0.10 39 2W-MOD Loop Test/Maintenance Mod. 30 50 4W-B (12/24 volt) Photoelectric I
3
4WT-B (12/24 volt) Photoelectric I
3
4WTA-B (12/24 volt) I 4WTR-B (12/24 volt) I
3
4WITAR-B (12/24 volt) I
Photo w/Isolated Therm/Sounder/Relay 0.05 50 2W-MOD2 I RRS-MOD I
Photo w/Therm/Sounder 0.05 35
3
Photo w/Therm/Relay 0.05 35
3
Loop Test/Maintenance Mod. 0.05 *
3
Reversing Relay/Sync Module 0.05 *
w/Therm 0.05 23
3
0.05 23
6424 Projected Beam 10 28.4 Beam 1224(S) Projected Beam 17 38.5
* Contact manufacturer for current draws.
A.2 Relays
Table A-2 below lists relays compatible with eFlow6NV output.
Manufacturer Model Current (mA) Manufacturer Model Current (mA)
PR-1**
PR-2*
System Sensor
* Compatible only with eFlow6NV, eFlow6NXV, eFlow6N8V, eFlow6NX8V, eFlow6N16V, eFlow6NX16V. ** Compatible only when unit is set for 24VDC.
eFlow6NV Series - 13 -
PR-3*
EOLR-1
R-10T** R-14T**
15 30 30 30 23 23
System Sensor
R-20T** R-24T** R-10E** R-14E** R-20E** R-24E**
40 40 23 23 40 40
Page 14
Notes:
- 14 - eFlow6NV Series
Page 15
Notes:
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 website: www.altronix.com, e-mail: info@altronix.com. Made in U.S.A. IIeFlow6NV Series H27O
eFlow6NV Series - 15 -
MEMBER
Page 16
Power Supply/Chargers Operating Guide
Models Include:
Input
Model
220VAC,
50/60Hz
eFlow6NV, eFlow6N8V, eFlow6N8DV, eFlow6N16V, eFlow6N16DV
2.1 amp 6 amp 6 amp 1 amp 910mV
eFlow6NXV, eFlow6NX8V, eFlow6NX8DV, eFlow6NX16V, eFlow6NX16DV
Overview:
The eFlow6NV series power supply/chargers convert a 220VAC, 50/60Hz input, to a 12VDC or 24VDC output.
Stand-by Specifications:
Output
12VDC 24VDC
Auxiliary Power-Limited
Output (unswitched)
Ripple
Voltage
Battery
7AH 0.4 amp/6 amp N/A 10 Mins./6 amp
12AH 1 amp/6 amp 0.3 amp/6 amp 25 Mins./6 amp
40AH 6 amp/6 amp 1.2 amp/6 amp Over 4 Hours/6 amp
65AH 6 amp/6 amp 1.5 amp/6 amp Over 4 Hours/6 amp
Burg. Applications
4 hr. Stand-by/15 min. Alarm
Fire Applications
24 hr. Stand-by/5 min. Alarm
Access Control
Applications Stand-by
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 1.54 amp.
• Automatic switch over to stand-by battery when AC fails. Transfer to stand-by battery power is instantaneous with no interruption.
LED Diagnostics:
Red (DC) Green (AC/AC1) Power Supply Status
ON ON Normal operating condition. ON OFF Loss of AC. Stand-by battery supplying power. OFF ON No DC output. OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
CUT ALONG DOTTED LINE
Installing Company: _________________________________ Service Rep. Name: ___________________________________________________
Address: _______________________________________________________________________ Phone #: _______________________________
Refer to the eFlow Power Supply/Chargers Installation Guide: IIeFlow6NV Series, Rev. 6NVRP052213 for complete instructions. This sheet is to be removed, framed and posted next to the unit.
Rev. 6NVRP052213
Loading...